all | frequencies |
|
|
|
|
exhibits | applications |
---|---|---|---|---|---|---|---|
manuals |
app s | submitted / available | |||||||
---|---|---|---|---|---|---|---|---|
1 2 |
|
Installation Manual 7-1 Part 1 | Users Manual | 253.15 KiB | October 07 2018 / June 01 2019 | |||
1 2 |
|
Installation Manual 7-2 Part 2 | Users Manual | 104.46 KiB | October 07 2018 / June 01 2019 | |||
1 2 |
|
Users Manual 7-3 Part 1 | Users Manual | 1.18 MiB | October 07 2018 / June 01 2019 | |||
1 2 |
|
Users Manual 7-3A Part 2 | Users Manual | 73.29 KiB | October 07 2018 / June 01 2019 | |||
1 2 | Test Report | October 07 2018 | ||||||
1 2 | Cover Letter(s) | October 07 2018 | ||||||
1 2 | Cover Letter(s) | October 07 2018 | ||||||
1 2 | External Photos | October 07 2018 / June 01 2019 | ||||||
1 2 | Internal Photos | October 07 2018 / June 01 2019 | ||||||
1 2 | ID Label/Location Info | October 07 2018 | ||||||
1 2 | Test Report | October 07 2018 | ||||||
1 2 | Test Setup Photos | October 07 2018 / June 01 2019 | ||||||
1 2 | Test Report | October 07 2018 |
1 2 | Installation Manual 7-1 Part 1 | Users Manual | 253.15 KiB | October 07 2018 / June 01 2019 |
ADT ADTHYBWL Series Security Systems Quick Installation Guide Ref: ADTHYBWL Series Connect the Power Supply & Battery (Continued) UL For UL installations and Residential fire installations, refer to the chart below for the correct battery size required to meet the mandatory standby time. OUTPUT LIMITATIONS AND REQUIRED BATTERIES Program the Control Refer to the to the MobileTech installer app for programming instructions. Test the System Output Current Limits Battery Information Refer to the Refer to the MobileTech installer app for testing instructions. Mount the Control 1, Open the cabinet door fully and remove by pulling to the left. 2. Remove the cabinet knockouts needed for wiring entry. 3. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes. 4. Install the ADTZWM (Wi-Fi and Z-Wave) and/or ADTLTE Communication Module(s) (if used). 5. When installation, wiring and programming is completed, install the cabinet door and secure with the provided screw. OPTIONAL KEY LOCK: If desired, a key lock can be installed (K4445V1). See Installation Instructions for details. SECURE WITH SCREW MOUNTING HOLES (3) LTE WiFi TX RXGND G E N E R A L TX RXGND BATT+ GND TAMPER MOUNTING HOLES (3) Mounting the Cabinet Optional ADTZWM and ADTLTE Communications Module Note: Refer to the Specific Module Installation section in the online Installation & Reference Guide for instructions on mounting this module. Connect the Power Supply & Battery Power Supply (P/N 300-10211 or 300-10211-CAN in Canada) Do not plug power supply into the AC outlet until all wiring connections to the control are complete. As a safety precaution, always power down the control when making such connections. Battery Connections After all connections to the control are completed and after AC power has been applied, connect the red and black flying leads on the control board to the battery. IMPORTANT: This control will not power-up on battery alone (AC power must be applied). However, once the system is powered up, it will operate on battery if AC is lost. CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE 24-HOUR BATTERY BACKUP REQUIREMENTS The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panels auxiliary power and bell output currents are limited as listed. 800-24126$
800-24126 2/18 Rev. A Part 1 (BETA) Current Total Max. Aux. Current
(Amp/Hrs) Battery (Yuasa No.) Battery Capacity Recommended 600mA maximum total of auxiliary power plus bell output currents 110mA 7AH NP7-12 Connect Devices, Zones and Sounder Refer to the Wiring Diagram on the reverse side for connection information. NOTE: This system uses a range of reserved addresses for each type of device. Securing the Cabinet Door 1. Connect keypads and other devices. Wire Size 50 mA or less
#22
#20
#18
#16 900ft (274m) 1400ft (427m) 1500ft (457m) 1500ft (457m) Total Current of All Devices Connected to a Single Wire Run 100 mA 450ft (137m) 700ft (213m) 1100ft (335m) 1500ft (457m) 300 mA 150ft (46m) 240ft (73m) 350ft (107m) 550ft (168m) 500 mA 90ft (27m) 140ft (43m) 220ft (67m) 350ft (107m) 600 mA 75ft (23m) 120ft (37m) 170ft (52m) 270ft (82m) The length of all wire runs for both partitions combined must not exceed 4000 feet (1219m) when unshielded quad conductor cable is used or 2000 feet (610m) if shielded cable is used. Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or block transmissions. Do not locate in an area of high RF interference (indicated by frequent or prolonged lighting of the receivers LED; random flicker is OK). Do not locate RF receiver closer than 10 feet from any keypads. Touchpad (WTP100) Connect touchpad field wiring to the GND, AUX, A and B terminals. Relay Modules Connect desired field wiring to the modules relay contact terminals. (when available) Communication Module (refer to the documentation provided with the module.) LTE (ADTLTE Series) WiFi/Z-Wave (ADTZWM) 2. Connect hardwire zones to the appropriate zone terminals. 3. On-Board Trigger Connections Connect field wiring to the appropriate trigger pin using the 4-wire cable (N4632-4, not supplied). Trigger outputs will go low on power-up. 4. Connect the external sounder to the GND and BELL terminals. If not using bell supervision, connect the supplied 820 ohm resistor across the GND and BELL terminals. If using bell supervision, see the next bullet point. If supervised output desired, see Sounder Supervision wiring diagram on reverse side, and program accordingly. 5. Install Wireless Zone Transmitters (Programmed via alarm.com). Major Features and Capacities Feature Partitions Hardwire Zones Maximum Devices Details 4 8 (1-7 and one dedicated smoke zone) 250 Devices (includes sensors, keypads, keyfobs, touch screens, Z-Wave, Bluetooth (for mobile devices), cameras and wiselink) 128 SiX Series sensors 32 Keyfobs (8 button) 6 Bluetooth (BLE Phones) 8 Touchpads/Touchscreens 8 Motion Viewers TBD Z-Wave Devices TBD IP Cameras Security Codes (Users) Outputs On-Board Triggers 96 Includes Master User (#1) 18 2 Specifications Dimensions:
Electrical:
Voltage Input:
Alarm Sounder:
Auxiliary Power Output:
Backup Battery 10-5/16 W x 12-1/4 H x 3.5 D (262mm x 311mm x 89mm) 13.5VDC, 1.8A from plug-in power supply, Part No. 300-
10211 or 300-10211-CAN (Canada) 10.5-13.8VDC, 2.0 Amp output can drive 12V Bell or 702 10.5-13.8VDC, 200mA max. 12VDC, 7AH (sealed lead acid type). Charging Voltage:
13.8VDC Communication Formats: 4-digit Contact ID Maximum Zone Resistance:
Zones 18 = 300 ohms excluding EOLR standard zones WARRANTY INFORMATION For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa. For patent information, see www.honeywell.com/patents Warranty Patents FOR DOCUMENTATION AND SUPPORT See Installation and Reference Guide P/N 800-24125 or higher, which can be ordered by contacting Customer Service at 1-800-238-2727 (1-800-ADT-ASAP). For technical support please call the ADT Product Support Group at 1-877-748-7628, option 3. A D T S e c u r i t y S e r v i c e s 1 5 0 1 Y a m a t o R o a d B o c a R a t o n , F L 3 3 4 3 1 2 0 1 8 A D T S e c u r i t y S e r v i c e s TO WiFi / ZWAVE SLOT 2 TO LTE SLOT 1 T N I T X E COMM TEST SLOT 1 LTE AUX/BELL_OC LED RUN LED IB2/ACTIVE LED RESERVED LED SLOT 2 WiFi / ZWAVE TAMPER SWITCH RJ-45 CONNECTOR G E N E R A L S L O T 3 TO INTERNET CONNECTION EARTH GROUND CONNECTION THIS CONTROL DOES NOT NORMALLY NEED AN EARTH GROUND FOR RESISTANCE TO DAMAGE FROM LIGHTNING AND ELECTRICAL DISCHARGE. FOR ADDITIONAL PROTECTION IN AREAS OF SEVERE ELECTRICAL ACTIVITY, CONNECT TERMINAL 25 TO A GOOD EARTH GROUND. EXAMPLES OF GOOD EARTH GROUNDS:
METAL COLD WATER PIPE:
USE A NON-CORROSIVE METAL STRAP (COPPER IS RECOMMENDED) FIRMLY SECURED TO THE PIPE TO WHICH THE GROUND LEAD IS ELECTRICALLY CONNECTED AND SECURED. AC POWER AND BATTERY CONNECTION AC POWER CONNECTION AC POWER CONNECTION TRANSFORMER 1. CONNECT THE POWER SUPPLY TO THE GND AND AC+ TERMINALS. SEE WIRE RUN CHART. USE CAUTION WHEN WIRING THE POWER SUPPLY TO THE CONTROL. POWER SUPPLY WIRE RUNS Distance from control Wire Size Up to 25 feet
# 22 25 - 50 feet 50 - 75 feet 75 - 150 feet
# 20
# 18
# 16 ADTZWM MODULE ADTLTE MODULE HARDWIRE ZONE CONNECTION 1. 2. OPEN CIRCUIT DEVICES CONNECT IN PARALLEL ACROSS THE LOOP; FOR EOLR ZONES, CONNECT THE EOLR ACROSS THE LOOP WIRES AT THE LAST DEVICE. CLOSED CIRCUIT DEVICES CONNECT IN SERIES IN THE HIGH (+) SIDE OF THE LOOP; FOR EOLR ZONES, CONNECT THE EOLR IN SERIES FOLLOWING THE LAST DEVICE. 3. USE ZONE 1 FOR 2-WIRE SMOKE DETECTORS. MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS IS 16. EOLR NOTE:
IF THE EOLR IS NOT AT THE END OF THE LOOP, THE ZONE IS NOT PROPERLY SUPERVISED AND THE SYSTEM MAY NOT RESPOND TO AN "OPEN" ON THE ZONE. UL NOTE:
FOR UL COMMERCIAL BURGLARY ALARM INSTALLATIONS, USE EOLR ZONES. 4. USE EOLR PART NUMBER P4100 (PART OF KIT SAHDWR1). 2-WIRE SMOKE DETECTORS Detector Type Photoelectric w/heat sensor Photoelectric Photoelectric System Sensor Model No. 2WT-B 2W-B
+
_ R W P X U A T U P T U O I S L A N M R E T OR 4-WIRE SMOKE DETECTOR CONNECTIONS RELAY PROGRAM RELAY AS ZONE TYPE FIRE ZONE RESET BLK _
+
RED N.C. N.O. CONTACT OPENS MOMENTARILY UPON FIRE ALARM RESET EOL POWER SUPERVISION RELAY MODULE EOLR-1. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED. TO OUTPUT TBD PROGRAM OUTPUT TBD FOR
"OUT NORM LOW"
AND AS FIRE ZONE RESET MAX. CURRENT = 100 mA
+
_ 4-WIRE SMOKE OR COMBUSTION DETECTOR VIOLET 2000 OHMS EOLR TO ZONE 1 7 TERM.
(+) _
( ) HEAT DETECTOR BATTERY POWER LED AC POWER LED BATT+ BATT -
D E S U T O N TRIGGER OUTPUT 1: 100mA MAX TRIGGER OUTPUT 2: 100mA MAX 2 R E G G R T I D N G V 2 1 1 R E G G R T I 8-PIN TRIGGER CONNECTOR AUX OUTPUT LED GND AUX B A D N G X U A
}
AUX. PWR OUTPUT 10.5-13.8VDC 200mA MAX.
(120mA MAX. FOR UL INSTALLATIONS) I H ALL OUTPUTS ARE POWER LIMITED. I H O L O L I H I H O L O L I H 1 E N O Z 2 E N O Z 3 E N O Z 4 E N O Z 2000 OHMS EOLR 2000 OHMS EOLR 2000 OHMS EOLR 2000 OHMS EOLR I H I H O L O L I H O L O L 5 E N O Z 6 E N O Z 7 E N O Z 8 E N O Z 2000 OHMS EOLR 2000 OHMS EOLR 2000 OHMS EOLR 2000 OHMS EOLR SOUNDER CONNECTION IF NOT USING A SOUNDER CONNECT THE 820 OHM BELL RESISTOR ACROSS CONTROLS BELL AND GND TERMINALS OTHERWISE SEE SOUNDER SUPERVISION BELOW. IF USING A SOUNDER CONNECT SOUNDER TO BELL AND GND TERMINALS. 820 OHMS EOLR ALARM OUTPUT 10.513.8VDC, 2A MAX. (600mA MAX. FOR UL USAGE, INCLUDING AUX POWER) STEADY FOR BURGLARY/PANIC, TEMPORAL PULSE SOUNDING FOR FIRE. USE 702 SIREN, OR 12V BELL. SEE INSTRUCTIONS. FOR BELL SUPERVISION SEE SOUNDER CONNECTION NOTES. N R U T E R
)
-
(
D N G D A P H C U O T K C A L B
:
)
+
(
R E W O P D A P H C U O T D E R
:
B 2 B I D A P H C U O T W O L L E Y
:
BLACK RED RECHARGEABLE BATTERY
(12V, 7AH) SEALED LEAD ACID TYPE
+
C D
-
C D EARTH GROUND 2151 w/B110LP base SOUNDER ACTIVATES UPON ALARM EVENT. ALARM OUTPUT: 10.513.8VDC, 2A MAX. (600mA MAX. FOR UL USAGE, INCLUDING AUX POWER). STEADY FOR BURGLARY/PANIC. TEMPORAL PULSE SOUNDING FOR FIRE. UL: MUST BE A UL LISTED AUDIBLE SIGNAL APPLIANCE RATED FOR 10.2-13.8 VDC AND BE MOUNTED INDOORS. USE ADEMCO No. 702 SIREN, OR 12V BELL. A BATTERY MUST BE INSTALLED BECAUSE THE BATTERY SUPPLIES THE SOUNDER CURRENT. UL: BELL SUPERVISION IS REQUIRED FOR FIRE ALARM INSTALLATIONS. EXTERNAL ALARM SOUNDER CONNECT AN 820 OHM RESISTOR ACROSS THE LAST EXTERNAL SOUNDER AS SHOWN BY THE DOTTED LINE. GND TERM. BELL TERM. OBSERVE POLARITY 820 OHM EOL RESISTOR DO NOT CONNECT THE RESISTOR DIRECTLY TO THE ALARM OUTPUT TERMINALS!
A 2 B I D A P H C U O T N E E R G
:
NOTE: DO NOT CONNECT TO A RECEPTCLE CONTROLLED BY A SWITCH. 2. AFTER ALL WIRING CONNECTIONS ARE COMPLETE, PLUG POWER SUPPLY INTO A 110VAC UNSWITCHED OUTLET (24HR).
"AC LOSS" DISPLAYED IF VOLTAGE FALLS BELOW 11 VDC. BATTERY 1. PLACE THE 12-VOLT BACKUP BATTERY IN THE CABINET. 300-10211 13.5 VDC, 1.8A POWER SUPPLY TO 110VAC UNSWITCHED OUTLET (24HR) 2. AFTER ALL CONNECTIONS TO THE CONTROL ARE MADE AND AFTER AC POWER HAS BEEN APPLIED, CONNECT THE RED AND BLACK FLYING LEADS TO THE BATTERY. IMPORTANT: THE PANEL WILL NOT POWER UP INITIALLY ON BATTERY POWER ONLY. YOU MUST PLUG THE POWER SUPPLY IN FIRST, AND THEN CONNECT THE BATTERY. DC+
DC -
POWER SHUTDOWN NOTE:
SYSTEM SHUTS DOWN SENSOR DETECTION PROCESSING IF CONTROLS VOLTAGE DROPS BELOW 9.6V. A L A R M S TAT U S T R O U B L E CANCEL AWAY STAY 1 PA N I C O F F 4 2 5 3 6 M A X T E S T B Y PA S S 7 8 9 I N S TA N T C O D E C H I M E 0
#
R E A DY WTP100 TOUCHPAD WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS. KEYPADS AND ADDRESSABLE DEVICE CONNECTION CONNECT KEYPADS AND OTHER ADDRESSABLE DEVICES TO A, B, AUX AND GND TERMINALS. GRIP-quick-guide_CL-V0
1 2 | Installation Manual 7-2 Part 2 | Users Manual | 104.46 KiB | October 07 2018 / June 01 2019 |
Install smoke detectors at both ends if the hallway is more than 40 feet Linstallation dun dtecteur de fume chaque extrmit dun corridor Recommendations for Proper Protection The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below. Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows:
For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended. For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. In addition, we recommend the following:
Install a smoke detector inside every bedroom where a smoker sleeps. Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed. Install a smoke detector inside bedrooms where electrical appliances
(such as portable heaters, air conditioners or humidifiers) are used.
(12 meters) long. Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion. This Control Complies with NFPA Requirements for Temporal Pulse Sounding of Fire Notification Appliances Recommendations for Proper Intrusion Protection For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would include any skylights that may be present, and the upper windows in a multi-level building. In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to the alarm monitoring station in the event that the communications are out of order
(if connected to an alarm monitoring station). KITCHEN DINING BEDROOM BEDROOM TV ROOM KITCHEN DINING BDRM LIVING ROOM BDRM LIVING ROOM BEDROOM BEDROOM Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection BEDROOM Heat-Activated Detectors BEDROOM TO BR BEDROOM KTCHN
. CLOSED DOOR GARAGE LVNG RM BASEMENT floor_plan-001-V1 Recommandations pour une protection adquate Les recommandations suivantes pour lemplacement des dispositifs de dtection dincendie et de vol aident procurer la couverture approprie pour les tablissements protgs. Recommandations pour les dtecteurs de fume et de chaleur En ce qui concerne le nombre et lemplacement des dtecteurs de fume/chaleur, nous souscrivons aux recommandations de la norme 72 de la NFPA (National Fire Protection Association) dcrites ci-dessous. Pour assurer une dtection dincendie rapide et efficace, des dispositifs de dtection dincendie doivent tre installs dans chacune des pices et dans chacune des aires communes de votre rsidence. Pour un minimum de protection, un dtecteur de fume doit tre install lextrieur de chaque chambre et sur chaque niveau dune maison plusieurs niveaux, y compris le sous-sol. Il nest normalement pas recommand dinstaller des dtecteurs de fume dans les cuisines, les greniers (amnags ou non) ou dans les garages. De plus, nous recommandons :
Linstallation dun dtecteur de fume dans chaque chambre o dort un fumeur. Contacting Technical Support PLEASE, before you call Technical Support, be sure you:
READ THE INSTRUCTIONS!
Determine that the power supply and/or backup battery are supplying proper voltages. Verify your programming information where applicable. Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. Note your ADT customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively. For Documentation and Online Support See Installation and Setup Guide P/N 800-24125 or higher, which can be ordered by contacting Customer Service at 1-800-238-2727 (1-
800-ADT-ASAP). For technical support please call the ADT Product Support Group at 1-877-748-7628, option 3. THE LIMITATIONS OF THIS ALARM SYSTEM While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm Linstallation dun dtecteur de fume dans chaque chambre o dort une warning device. personne et que la porte de cette chambre est partiellement ou compltement ferme. La fume pourrait tre arrte par une porte close. De plus, si la porte est ferme, une alarme dans le corridor ne rveillera peut-tre pas une personne. Linstallation dun dtecteur de fume lintrieur de chaque chambre o des appareils lectriques (par exemple des chaufferettes portatives, climatiseurs ou humidificateurs) sont utiliss. sil a plus de 12 mtres (40 pieds) de long. Linstallation de dtecteurs de fume dans chaque pice o se trouve un panneau dalarme ou dans chaque pice o des connexions de panneau dalarme sont faites sur une source dalimentation CA ou sur une ligne tlphonique. Si des dtecteurs ne sont pas installs ces endroits, un incendie dans la pice pourrait empcher le panneau de commande de rapporter un incendie ou une intrusion. Ce dispositif de contrle est conforme aux exigences de la NFPA relatives la sirne impulsion temporise des appareils de notification dincendie Recommandations pour une protection contre les intrusions adapte Pour une protection anti-intrusion adquate, les capteurs doivent tre situs chaque point dentre possible dune maison ou de locaux. Cela inclut toute ouverture znithale susceptible dtre prsente, et les fentres hautes dans un immeuble plusieurs niveaux. En outre, nous recommandons lutilisation dune radio de secours dans un systme de scurit. Cela permet dassurer lenvoi des signaux dalarme la station de surveillance des alarmes si les communications sont coupes (en cas de raccordement une station de surveillance des alarmes.) CUISINE CHAMBRE CHAMBRE SALLE MANGER BOUDOIR CUISINE SALLE MANGER CHAMBRE SALON CHAMBRE SALON CHAMBRE CHAMBRE Dtecteur de fume pour une protection minimum Dtecteur de fume pour une protection additionnelle Dtecteurs activs par la chaleur GARAGE
. PORTE FERME CHAMBRE CHAMBRE CHAMBRE SALON CUISINE SOUS-SOL Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery-
operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly. Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path. A user may not be able to reach a panic or emergency button quickly enough. While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second-floor detector, for example, may not sense a first-floor or basement fire. Moreover, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending upon the nature of the fire and/or the locations of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature;
however, as the ambient temperature of protected area approaches the temperature range of 90 to 105F, the detection performance can decrease. Alarm warning devices such as sirens, bells, or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices sound on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people or waken deep sleepers. Communications lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service. Communications lines are also subject to compromise by sophisticated intruders. Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately. This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 10 years, the electronic components could fail at any time. The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance. Homeowners, property owners, and renters should continue to act prudently in protecting themselves and continue to insure their lives and property. We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments. floor_plan_FR-001-V0 800-24126 2/18 Rev. A Part 3 FEDERAL COMMUNICATIONS COMMISSION & ISED STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
If using an indoor antenna, have a quality outdoor antenna installed. Reorient the receiving antenna until interference is reduced or eliminated. Move the radio or television receiver away from the receiver/control. Move the antenna leads away from any wire runs to the receiver/control. Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits. Consult the dealer or an experienced radio/TV technician for help. ISED CLASS B STATEMENT This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numrique de la classe B est conforme la norme NMB-003 du Canada. FCC / ISED STATEMENT This device complies with Part 15 of the FCC Rules, and ISEDs license-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Cet appareil est conforme la partie 15 des rgles de la FCC et exempt de licence RSS ISED. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer dinterfrences nuisibles. (2) Cet appareil doit accepter toute interfrence reue y compris les interfrences causant une rception indsirable. Warning Warning - The antenna(s) used for this device must be installed to provide a separation distance of at least 7.8 inches (20 cm) from all Warning Warning persons and must not be co-located or operating in conjunction with any other antenna or transmitter except in accordance with FCC and ISED multi-transmitter product procedures. RF Exposure Mise en Garde Exposition aux Frequences Radio: La/les antenne(s) utilise(s) pour cet metteur doit/doivent tre installe(s) une distance de sparation d'au moins 20 cm (7,8 pouces) de toute personne et ne pas tre situe(s) ni fonctionner paralllement tout autre transmetteur ou antenne, except en conformit avec les procdures de produit multi transmetteur FCC et ISEDs. This Control Complies with NFPA Requirements for Temporal Pulse Sounding of Fire Notification Appliances Recommendations for Proper Intrusion Protection For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would include any skylights that may be present, and the upper windows in a multi-level building. In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to the alarm monitoring station in the event that the communications are out of order (if connected to an alarm monitoring station). Ce dispositif de contrle est conforme aux exigences de la NFPA relatives la sirne impulsion temporise des appareils de notification dincendi Recommandations pour une protection contre les intrusions adapt Pour une protection anti-intrusion adquate, les capteurs doivent tre situs chaque point dentre possible dune maison ou de locaux. Cela inclut toute ouverture znithale susceptible dtre prsente, et les fentres hautes dans un immeuble plusieurs niveaux. En outre, nous recommandons lutilisation dune radio de secours dans un systme de scurit. Cela permet dassurer lenvoi des signaux dalarme la station de surveillance des alarmes si les communications sont coupes (en cas de raccordement une station de surveillance des alarmes). Avant de contacter le service technique, VEUILLEZ :
LIRE LES INSTRUCTIONS!
Vrifier que le bloc dalimentation et la batterie de secours fournissent les tensions appropries. Vrifier vos donnes de programmation, le cas chant. Prendre en note le numro de modle de ce produit et son numro de version (si celui-ci est connu) et avoir en main toute la documentation fournie avec le produit. Noter votre numro de client chez ADT et/ou le nom de votre entreprise. Ces renseignements nous permettront de vous servir plus rapidement et plus efficacement. Technical Support: Contact your ADT Customer Care Representative RESTRICTIONS DE CE SYSTME DALARME Quoique ce systme soit de conception avant-gardiste, il noffre pas de garantie de protection contre le vol, le feu ou toute autre urgence. Tout systme dalarme, commercial ou rsidentiel, peut faillir la tche pour plusieurs raisons. Par exemple :
Un intrus peut sintroduire par une ouverture non protge ou possder des connaissances approfondies lui permettant de contourner un dispositif de dtection ou de dbrancher un dispositif davertissement dalarme. Les dtecteurs dentre par effraction (par ex. : les dtecteurs infrarouge), les dtecteurs de fume et plusieurs autres dispositifs de dtection ne fonctionnent pas sans piles, avec des piles faibles ou si ces piles sont mal installes. Les dispositifs aliments par piles ne fonctionneront pas sans piles, avec des piles mortes, ou si les piles ne sont pas installes correctement. Les dispositifs qui sont aliments par le courant alternatif seulement ne fonctionnent pas si cette alimentation est coupe, mme brivement. Les signaux des transmetteurs sans fil peuvent tre arrts ou rflchis par le mtal avant quils atteignent le rcepteur dalarme. Mme si la trajectoire du signal a t rcemment vrifie par un test hebdomadaire, ce signal peut tre bloqu ou driv par une pice de mtal place dans son chemin. Un utilisateur peut ne pas atteindre assez rapidement un bouton de panique ou durgence. Lagence amricaine Federal emergency management Agency Nous informe que mme si les dtecteurs de fume ont jou un rle cl dans la prvention des mortalits causes par le feu dans les rsidences, il se peut que pour plusieurs raisons, ils navertissent pas assez vite dans 35
% des incendies. Voici quelques raisons pourquoi les dtecteurs de fume utiliss avec ce systme ne fonctionneront peut-tre pas : Les dtecteurs de fume peuvent avoir t installs incorrectement ou au mauvais endroit. Un incendie peut se dclarer dans un endroit ou la fume natteindra pas les dtecteurs, par ex. : les chemines, les murs, les toits ou bien de lautre ct dune porte close. Les dtecteurs de fume peuvent ne pas dtecter un incendie sur un autre tage. Un dtecteur au deuxime tage, par exemple, ne dtectera pas un incendie au rez-de-
chausse ou au sous-sol. De plus, la sensibilit des dtecteurs de fume est limite. Aucun dtecteur de fume ne peut tre sensible toutes les sortes dincendie en tout temps. En gnral, les dtecteurs ne peuvent pas toujours vous avertir des incendies causs par la ngligence et les dangers, comme fumer au lit, les explosions violentes, les gaz dchappement, le mauvais entreposage de matriaux inflammables, les circuits lectriques surchargs, les enfants qui jouent avec des allumettes, les incendies criminels. Selon la nature du feu et/ou lemplacement des dtecteurs de fume, mme sil fonctionne comme voulu, le dtecteur peut ne pas donner un avertissement suffisant pour permettre tous les occupants de sortir temps et dviter des blessures ou la mort. Les dtecteurs de mouvement passifs infrarouge ne peuvent dtecter une intrusion que dans des parties tablies dans le schma du manuel dinstallation. Les dtecteurs passifs infrarouge ne couvrent pas une zone de protection volumtrique. Ils protgent diffrents rayons de protection et une intrusion ne peut tre dtecte que dans les zones couvertes par les rayons. Ils ne peuvent dtecter le mouvement ou une intrusion de lautre ct des murs, plafonds, planchers, portes closes, cloisons de verre, portes en verre ou chssis. Laltration, le masquage, la peinture ou la vaporisation de quelque produit que ce soit sur les miroirs, les fentres ou toute pice optique du systme peuvent rduire leur capacit de dtection. Les dtecteurs passifs infrarouge sont sensibles aux variations de temprature; ds lors, lorsque la temprature ambiante de la zone protge approche de 32 40 C (90 105 F), la performance de dtection peut dcrotre. Les dispositifs dalarme, tels que les sirnes, cloches et Klaxons peuvent ne pas avertir ou rveiller les personnes de lautre ct dune porte close ou entrouverte. Si les dispositifs dalarme entrent en fonction sur un niveau autre que celui des chambres, alors, peut-tre ne pourront-ils veiller ou avertir les personnes qui se trouvent dans ces chambres. Mme les personnes veilles nentendront peut-tre pas le son de lalarme si celui-ci est couvert par le bruit dun systme de son, de la radio, dun climatiseur ou dun appareil mnager ou mme par la circulation automobile. Enfin, les dispositifs dalarme, mme sils ont un niveau sonore lev, ne parviendront peut-tre pas avertir les malentendants ou veiller des dormeurs profonds. Les lignes tlphoniques qui transmettent les signaux dalarme dun tablissement au poste de tlsurveillance peuvent tre en panne ou temporairement hors service. Des intrus expriments peuvent galement saboter les lignes tlphoniques. Toutefois, mme si le systme ragit comme voulu une urgence, les occupants peuvent ne pas avoir le temps de se prmunir contre une telle situation. Mme si le systme est sous tlsurveillance, les forces de lordre ou le service dincendie peuvent ne pas ragir au moment opportun. Comme tout autre appareil lectrique, cet quipement peut dfaillir. Mme si cet quipement a t conu pour une dure de vie dau moins vingt ans, ses composants lectroniques peuvent dfaillir tout moment. Le manque dentretien est la cause la plus commune du mauvais fonctionnement dun systme dalarme lors dune intrusion ou dun incendie. Ce systme dalarme devrait tre vrifi chaque semaine pour sassurer que tous les dtecteurs et les transmetteurs fonctionnent bien. Les claviers de scurit (et les tlcommandes) devraient galement tre vrifis. Les transmetteurs sans fil (utiliss avec certains systmes) sont conus pour procurer une longue dure de vie de la pile qui les alimente lorsquils sont utiliss dans des conditions normales dopration. Les piles peuvent durer de 4 7 ans selon lenvironnement, lutilisation et le type de dispositif sans fil utilis. Des facteurs externes se retrouvant dans une installation particulire telle que : de lhumidit, des tempratures basses ou leves aussi bien que de grandes variations de temprature sont tous sujets rduire la dure de vie de la pile. Toutefois, ce systme sans fil est conu pour dtecter une condition de pile faible sur les dispositifs et pour vous en avertir. Cette condition de dfectuosit vous permet ainsi de remplacer la pile afin de maintenir la zone de protection du systme couverte par le dispositif dfaillant. Linstallation dun systme dalarme peut vous rendre admissibles des tarifs rduits dassurance mais ne peut pas tre utilise comme substitut cette dernire. Les propritaires de commerces et de rsidences et les locataires doivent continuer dagir prudemment, de se protger et dassurer leur vie et leur proprit. Nous continuons imaginer et fabriquer des dispositifs de protection nouveaux et amliors. Les utilisateurs de systmes dalarme se doivent eux-mmes et leurs proches de connatre ces nouveaux produits.
1 2 | Users Manual 7-3 Part 1 | Users Manual | 1.18 MiB | October 07 2018 / June 01 2019 |
TESTING THE SYSTEM Using the Test mode allows each detection point to be checked for proper operation. Testing should be conducted weekly to ensure proper operation. The keypad sounds a single beep about every 60 seconds as a reminder that the system is in the Test mode. Alarm messages are not sent to Central Station when Test mode is on. If a problem is experienced with any detection point (no confirming sounds, no display), call for service immediately. 1. Disarm the system and close all protected windows, doors, etc. The READY indicator light should come on if all zones are intact 2. Enter 4-digit Master code +
3. Listen. The external sounder should sound for about 1 second then turn off. If the sounder does not sound, CALL FOR SERVICE. The Test in Progress display appears only on the keypad that started the test.
(walk)
+
1 5 4. Fault zones. Open each protected door and window in turn and listen for three beeps from the keypad. Each faulted detection point should appear on the display. The display clears when the door or window is closed. 5. Walk in front of any interior motion detectors (if used) and listen for three beeps. Each detector should appear on the display when it is activated. The display clears when no motion is detected. Note that if wireless motion detectors are used, there is a 3-minute delay between activations to conserve battery life. 6. Test all smoke detectors, following the manufacturer's instructions. 7. When all detection points have been checked and are intact
(closed), there should be no zone numbers displayed. 8. Exit test mode 4-digit code + 1 COMMUNICATION TEST Perform a Communication Test to verify the communication paths to the Central Station are working properly. Enter 4-digit Master code +
5
+
2 SHUTTING DOWN/REBOOTING THE SYSTEM Hard Reboot To avoid corrupting the controls memory, before removing power from the system perform the following:
1. Disarm the system 2. Enter 4-digit Master code +
#
+
+
9 3. Wait until all of the LEDs are blank before removing power Soft Reboot Perform the following when instructed by an ADT Service Representative. 1. Enter 4-digit Master code +
+ #
#
NOTES 800-24127-
800-24127 2/18 Rev A Part 1 (BETA) TROUBLE CONDITIONS The word CHECK on the keypad's display, accompanied by a
"beeping" at the keypad, indicates a trouble condition in the system at the displayed zone number sensor and requires your attention. Determine if the zone(s) displayed are intact and make them so if they are not. If the display persists, CALL FOR SERVICE. To silence the beeping for these conditions, press any key. Typical Trouble conditions include the following:
Trouble Message Meaning COMM. FAILURE A failure has occurred in the telephone
(or FC) communication portion of your system. SYSTEM LO BAT Low system battery condition exists.
(or BAT with no zone No.) LO BAT+ zone descriptor Low battery condition in the wireless
(or BAT with zone No.) transmitter. Either replace the battery yourself, or CALL FOR SERVICE. Rcvr Jam (or CHECK 90) RF interference in wireless system which may impede reception from wireless sensors. ALARM 1xx (or 91) A communication problem between the FAULT 1xx CHECK 1xx control and a connected device (e.g., RF receiver, zone expander) where the xx indicates the device address. MODEM COMM (or CC) Indicates that the control is on-line with the Central Monitoring Station's remote computer. AC LOSS (or NO AC) The system is operating on battery power only due to an AC power failure. If only some lights are out on the premises, check circuit breakers and fuses and reset or replace as needed. TELCO FAULT (or CHECK The telephone line has a problem. 94) Busy-Standby (or dI) If this message remains displayed for more than 1 minute, system is disabled. CALL FOR SERVICE. SERVICING INFORMATION Your local ADT Installer is the person best qualified to service your alarm system. Arranging some kind of regular service program with him is advisable. Your local Honeywell dealer is:
Name:
Address:
Phone:
A D T S e c u r i t y S e r v i c e s 1 5 0 1 Y a m a t o R o a d B o c a R a t o n , F L 3 3 4 3 1 2 0 1 8 A D T S e c u r i t y S e r v i c e s ADT ADTHYBWL SERIES SECURITY SYSTEMS Quick Guide to User Functions User Guide Available Online: This Quick Guide describes the most frequently used features and functions of your system. For full details of all user functions, please see the systems User Guide located online at: https://www.adt.com/help/faq/system-
user-guides (see ADTHYBWL Series Security System User Guide P/N 800-24128 or higher). The full version User Guide is also available from your installer upon request. Congratulations on your ownership of an ADT Security System. This system provides:
Three forms of detection: burglary, fire and emergency (see your installer for which forms of detection are installed) At least one keypad which provides control of system and displays system status Various sensors for perimeter and interior burglary detection Optional smoke or combustion detectors designed to provide early warning in case of fire. Your system may also be programmed to automatically send alarm and status messages to a Central Monitoring Station. SYSTEM BASICS The following is a list of some of the most common features and functions of your system:
Several modes of burglary detection: Stay, Night-Stay, Away, NOTES ON BURGLARY DETECTION The system must be armed before the burglary detection can sense intrusions. To arm your system, enter your security code followed by the Instant, Maximum. desired arming key. Bypass feature lets you bypass selected zones while leaving the To disarm the system, enter your security code then press rest of the system armed. the OFF key. Chime mode alerts you to the opening of protected doors and When an alarm occurs, the keypad sounds and displays the windows while the system is disarmed. Fire and carbon monoxide detection are always active (if installed);
an alarm sounds if a fire or carbon monoxide condition is detected. Fire, Police and Personal Panic keys (if programmed) let you manually initiate fire and personal alarms using the keypad. 4-digit security codes are used in conjunction with keypad commands to perform system functions. Each user can be assigned a different security code, each with different authority levels. The system sensors have been assigned to various zones, which are specific areas of detection (e.g., front door, kitchen window, etc.). Zone numbers (points of detection) are displayed at the keypad when an alarm or trouble condition occurs. Partitions provide independent areas of detection with each partition containing a group of zones that can be armed and disarmed without affecting other zones or users. ENTRY/EXIT DELAYS Entry Delays give you time to disarm the system when you enter through the designated entrance door. You must disarm the system before the entry delay period ends, or an alarm will occur (keypad beeps during the entry delay period, reminding you to disarm the system). Exit delay gives you time after arming the system to leave through the designated exit door(s) without setting off an alarm. If programmed, a slow beeping will sound during the exit delay period until the last 10 seconds, which then changes to fast beeping
(alerting you to the end of exit delay). If you cannot leave within this delay time period, you should stop, disarm the system, and start over to avoid a false alarm. See your installer for your delay times. See the full User Guide for details on Exit Error alarms. zone(s) causing the alarm. The external sounder may also sound. If your system is connected to a Central Monitoring Station, an alarm message is also sent (delayed 30 seconds by default to reduce false alarms). To stop the alarm sounding, simply disarm the system. Memory of Alarm: When an alarm condition occurs, the keypad displays the number(s) of the zone(s) that caused the problem, and displays the type of alarm. Clear the Memory of Alarm display by entering another off sequence. IMPORTANT: If you return to the premises and the main burglary sounder is on, or the keypad beeps rapidly upon entering the premises, it indicates that an alarm has occurred during your absence and an intruder may still be on the premises. LEAVE IMMEDIATELY and CONTACT THE POLICE from a nearby safe location. NOTES ON FIRE AND CO DETECTION Your fire alarm system (if installed) is on 24 hours a day, for continuous detection. In the event of an emergency, the smoke and heat detectors sound their alarms, triggering a loud, interrupted pulsed sound from the Keypad(s) and any external sounders. You can silence the alarm at any time by pressing the OFF key (the security code is not needed to silence fire alarms). Carbon monoxide (CO) detectors, if installed, provide continuous detection. If a high level of carbon monoxide is detected, an interrupted pulsed alarm sound occurs at the keypads and the detector(s). Immediately move to a spot where fresh air is available, preferably outdoors. From a safe area, call your security service provider for further instructions. To silence the keypad sounding, press the OFF key. To silence the detector, see its instructions. CHECKING OPEN ZONES Checking Zones: Before arming your system, all protected doors, windows and other detection zones must be closed or bypassed; otherwise the keypad displays "Not Ready."
GOTO: If the user is authorized, a keypad in one partition can be used to perform system functions in the other partition by using the GOTO command. Must use an Alpha keypad. Action Press these keys What happens Check Zones Displays all faulted zones. Audible Alarm audible alarm PANIC KEYS Your system may have been programmed to use special keys to manually activate emergency
(panic) functions as follows:
Function Silent Alarm Sends This Signal* With This Sounding silent alarm no audible alarm; displays, Press [] to show faults, indicating that a silent alarm has been initiated. a loud, steady alarm at keypad(s) and at any external sounders that may be connected. steady alarm sound at keypad(s), but not at external bells or sirens. temporal (pulsing) sound at external bells and sirens. auxiliary alarm Personal Alarm Fire Alarm
* All panic functions send signals to the Central Monitoring Station, if connected. fire alarm The Bypass feature allows you to arm your system with one or more zones intentionally unprotected. The system must be disarmed first. Up to 5 zones can be bypassed. To activate a Panic Function:
Press
+ Desired panic function within 10 seconds ARMING THE SYSTEM, CHIME MODE, and CONTROLLING DEVICES Before arming, close all perimeter doors and windows and make sure the Ready to Arm message is shown. After arming, leave the premises through an entry/exit door during the exit delay period and be sure the door is reclosed to avoid causing an alarm. Action Press these keys When to use an arming mode and what happens Used when you want to arm the system with persons Stay 4-digit code +
three beeps confirm 3 Night-Stay Instant Away Maximum Quick Arming Chime Mode 4-digit code +
three beeps confirm 3 3 4-digit code +
three beeps confirm 7 4-digit code +
two beeps confirm 2 4-digit code +
two beeps confirm 4 OR 9 4-digit code +
(enter again to turn Chime mode off) staying inside (or if you have pets that are moving throughout the premises). Arms perimeter zones; interior zones left disarmed. An alarm sounds if any protected window or non-
entry/exit door is opened. Use NIGHT-STAY mode to provide increased security while staying inside. Arms same as STAY mode, but also arms preselected interior sensors (set by your installer). If programmed, used when staying inside and do not expect anyone to use an entry/exit door. Same as STAY mode, except entry delay is off. An alarm sounds same as STAY mode, and sounds upon opening entry/exit doors. Used when nobody is staying inside (including pets). Arms the entire system (interior and perimeter). An alarm sounds if a protected window or any non-
entry/ exit door is opened, or if any movement is detected inside. If programmed, used when leaving the premises for extended periods (e.g., vacation). Same as Away mode, except entry delay is off. An alarm sounds same as Away mode, and sounds upon opening entry/exit doors. If programmed, you can press the [#] key in place of your security code when arming the system Alerts you to the opening of a perimeter door or window while the system is disarmed. Three tones sound at the keypad whenever a perimeter door or window is opened (interior zones do not produce a tone when they are faulted). Pressing the READY key displays the open zones. DISARMING THE SYSTEM AND SILENCING ALARMS The 1 OFF key is used to disarm the system, silence alarm and trouble sounds, and clear memory of alarm displays. GOTO 4-digit code +
+ partition number (1,2,3 = go to partition;
0 = return to home part.) The keypad beeps confirming partition change. Keypads automatically return to their original partition after 30 seconds with no keypad activity. BYPASSING ZONES Action Press these keys Bypass Zones 6 4-digit code +
+
3-digit zone number(s) to be bypassed What happens When finished, the keypad will momentarily display a
"Bypass" message for each bypassed zone number. Wait for all bypassed zones to be displayed. Arm the system as usual. When armed, the arming message is displayed with ZONE BYPASSED. Bypassed zones are unprotected and will not cause an alarm if violated. The system will not allow fire zones to be bypassed. Zones are automatically unbypassed when the system is disarmed. To display bypassed zones prior to arming, enter your security code and press the BYPASS key. Up to 5 zones can be bypassed SECURITY CODES Your installer assigned a master code that is used to perform all system functions. In addition, other security codes can be assigned for use by other users. Only the System Master and Partition Master can assign security codes to users. Users are identified by 2-digit user numbers. Only the System Master can change user partitions. In addition to a security code, each user is assigned an authority level and various system attributes. See the full User Guide for definitions of each Authority Level. Security codes can be used interchangeably within a partition when performing system functions
(a system armed with one security code can be disarmed by a different security code), with the exception of the Guest and Arm Only codes. Security code programming involves these steps:
Action Press these keys What happens 1. Choose a user number from the set of users assigned to the partition in which the user will be Disarm and Silence Alarms 4-digit code +
1 System is disarmed and alarm sounding is silenced. To clear the memory of alarm display (if present), enter 4-digit code + 1 again. To Silence a Fire Alarm or Carbon Monoxide Alarm Simply Press the 1 key (no code needed) When entering codes and commands, sequential key depressions must be made within 10 seconds of one another. If 10 seconds elapse without a key depression, the entry will be aborted and must be repeated from its beginning. If you make a mistake while entering a security code, stop, press the key, and then start over. If you stop in the middle while entering a code, and then immediately start the entry over, an erroneous code might be entered. CANCELING ALARMS In the event that an alarm has occurred entering the 4-digit code + 1 OR 4-digit code + CANCEL CANCEL
+ 4-digit code will silence the bell and send a cancel report to the Central Station OR
(when done within the SIA time window) Notes: Entering the 4-digit code will disarm the system and silence the sounder To clear alarm memory enter the 4-digit code +
OR code +
OR CANCEL 1 CANCEL
+ code CANCEL OR CANCEL
+ code will have no effect. Note: Entering code +
operating, and assign a 4-digit security code. 2. Assign an authority level to that user. 3. Assign other attributes as necessary. Assigning Security Codes and User Attributes The following lists the various command strings for adding security codes and attributes. Note: Partition Master codes apply only to those user numbers previously assigned (by the system master/installer) to the partition masters partition. Function Change System Master Code Add Security Code Delete Security Code Authority Level Users Partition System Master code +
8
+
0 1
+ new code + new code again Commands Master code +
The Keypad beeps once to confirm that new user was added.
+ user no. + new users security code 8 8
+ [user no.] + #
Master code +
The security code and all attributes* set for this user number, including any associated RF keys, are erased from the system.
(*except assigned partition) 0 Master code +
8
+ [user no.] +
#
1
+ auth. level Authority Levels: 0 = standard user 1 = arm only 2 = guest 3 = duress 4 = partition master System Master Code + 8 This assigns the partitions the user can access. If more than one, enter partition numbers sequentially, then press [#] to end.
+ [user no.] +
+ part. +
+
#
#
3 0 8
+ [user no.] + #
E.G. master code +
+
Gives the user access to partitions 1 and 2 and common partition. Partition Entries:
1 = partition 1 and common 2 = partition 2 and common 3 = common partition only
+
2 3 1
#
Keys
+
+
+
Zone Function 995 999 996 Fire Police Personal KEY/LED FUNCTIONS Icon & Text Function CANCEL STATUS System Status LED 1 4 5 6 7 8 9
#
TROUBLE System Trouble LED CANCEL Cancel key AWAY STAY PANIC OFF MAX TEST Arm Away key Army Stay key Panic Alarm key Disarm key Fire Panic key Arm Maximum key
(No Delay) System Test key BYPASS Bypass Zone key Police Panic key INSTANT Arm Instant key
(No Delay) CODE Add Security Codes key CHIME Chime Mode key Personal Panic key READY Check Zones key Quick Arm key STATUS TROUBLE CANCEL 1 PANIC OFF 4 AWAY STAY 2 5 3 6 MAX TEST BYPASS 7 8 9 INSTANT CODE CHIME 0
#
READY WTP100 Keypad
1 2 | Users Manual 7-3A Part 2 | Users Manual | 73.29 KiB | October 07 2018 / June 01 2019 |
IMPORTANT INFORMATION IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building. In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the Central Monitoring Station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines). EARLY WARNING FIRE DETECTION Early warning fire detection is important in a home. Smoke and heat detectors have played a key role in reducing fire deaths in the United States. With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's National Fire Alarm Code (NFPA 72). National Fire Protection Association Recommendations on Smoke Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's National Fire Alarm Code (NFPA 72). Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed outside of each separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics. In addition, the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. KITCHEN DINING BEDROOM BEDROOM TV ROOM KITCHEN DINING BDRM LIVING ROOM BDRM LIVING ROOM BEDROOM BEDROOM Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors BEDROOM BEDROOM TO BR BEDROOM KTCHN
. CLOSED DOOR GARAGE LVNG RM BASEMENT floor_plan-001-V1 Emergency Evacuation C L O S E T B E D M O O R H C R O P M O O R B E D B A T H M O O R B E D 2 FLOOR ND H E N M O O R B E D KIT C BACK DOOR M O B E D O R B A T H 1 FLOOR ST
BACK FRONT Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended by the National Fire Protection Association:
1. Position your detector or your interior and/or exterior sounders so that they can be heard by all occupants. 2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the building. The other may be a window, should your path be impassable. Station an escape ladder at such windows if there is a long drop to the ground. Sketch a floor plan of the building. Show windows, doors, stairs and rooftops that can be used to escape. Indicate escape routes for each room. Keep these routes free from obstruction and post copies of the escape routes in every room. 3. 4. Assure that all bedroom doors are shut while you are asleep. This will prevent deadly smoke from entering while you escape. Try the door. If the door is hot, check your alternate escape route. If the door is cool, open it cautiously. Be prepared to slam the door if smoke or heat rushes in. 5. 6. When smoke is present, crawl on the ground. Do not walk upright, since smoke rises and 7. 8. may overcome you. Clearer air is near the floor. Escape quickly; don't panic. Establish a common meeting place outdoors, away from your house, where everyone can meet and then take steps to contact the authorities and account for those missing. Choose someone to assure that nobody returns to the house many die going back SYSTEM COMPATIBILITY NOTICE Your Honeywell security system is designed for use with devices manufactured or approved by Honeywell for use with your security system. Your Honeywell security system is not designed for use with any device that may be attached to your security system's keypad or other communicating bus if Honeywell has not approved such device for use with your security system. Use of any such unauthorized device may cause damage or compromise the performance of your security system and affect the validity of your Honeywell limited warranty. When you purchase devices that have been manufactured or approved by Honeywell, you acquire the assurance that these devices have been thoroughly tested to ensure optimum performance when used with your Honeywell security system. THE LIMITATIONS OF THIS SECURITY SYSTEM WARNING!
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly. Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path. A user may not be able to reach a panic or emergency button quickly enough. While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement fire. Moreover, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending upon the nature of the fire and/or the locations of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death. Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of protected area approaches the temperature range of 90 to 105F, the detection performance can decrease. Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices sound on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people or waken deep sleepers. Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately. This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 10 years, the electronic components could fail at any time. The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property. We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments. 2 FEDERAL COMMUNICATIONS COMMISSION (FCC)/ISED STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. FCC CLASS B STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
If using an indoor antenna, have a quality outdoor antenna installed. Reorient the receiving antenna until interference is reduced or eliminated. Move the radio or television receiver away from the receiver/control. Move the antenna leads away from any wire runs to the receiver/control. Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits. Consult the dealer or an experienced radio/TV technician for help. ISED CLASS B STATEMENT This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numrique de la classe B est conforme la norme NMB-003 du Canada. FCC / ISED STATEMENT This device complies with Part 15 of the FCC Rules, and ISEDs License-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation. Cet appareil est conforme la partie 15 des rgles de la FCC et exempt de licence RSS dISED. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d' interfrences nuisibles. (2) Cet appareil doit accepter toute interfrence reue y compris les interfrences causant une rception indsirable. Warning - The antenna(s) used for this device must be installed to provide a separation distance of at least 7.8 inches (20 cm) from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter except in accordance with FCC and ISED multi-transmitter product procedures. Exposition aux Frequences Radio: La/les antenne(s) utilise(s) pour cet metteur doit/doivent tre installe(s) une distance de sparation d'au moins 20 cm (7,8 pouces) de toute personne et ne pas tre situe(s) ni fonctionner paralllement tout autre transmetteur ou antenne, except en conformit avec les procdures de produit multi transmetteur FCC et ISEDs. RF Exposure Mise en Garde 3 TWO YEAR LIMITED WARRANTY Honeywell International Inc., acting through its Security & Communications business (Seller), 2 Corporate Center Drive, Melville, New York 11747 warrants its products to be free from defects in materials and workmanship under normal use and service, normal wear and tear excepted, for 24 months from the manufacture date code; provided, however, that in the event the Buyer presents a proper invoice relating to the purchased product and such invoice bears a date later than the manufacture date, then Seller may at its discretion, reflect the warranty period as commencing at invoice date. Except as required by law, this Limited Warranty is only made to Buyer and may not be transferred to any third party. During the applicable warranty period, Seller will repair or replace, at its sole option and as the exclusive remedy hereunder, free of charge, any defective products. Seller shall have no obligation under this Limited Warranty or otherwise if the product:
is improperly installed, applied or maintained;
installed outside of stated operating parameters, altered or improperly serviced or repaired by anyone other than the Seller/Sellers Authorized Service/Repair Center;
damage is caused by outside natural occurrences, such as lightning, power surges, fire, floods, acts of nature, or the like;
or defects result from unauthorized modification, misuse, vandalism, alterations of serial numbers, other causes unrelated to defective materials or workmanship, or failures related to batteries of any type used in connection with the products sold hereunder.
(iii)
(iv)
(i)
(ii) Exceptions to Warranty with Respect to Honeywell Products listed below:
Hardwire Contacts and PIRs Seller warrants parts for hardwire contacts and PIRs in accordance with the terms of the above limited warranty for a period of five (5) years from the manufacture date code. EXCLUSION OF WARRANTIES, LIMITATION OF LIABILITY THERE ARE NO WARRANTIES OR CONDITIONS, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. TO THE FULLEST EXTENT PERMITTED BY LAW, IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY (i) CONSEQUENTIAL, INCIDENTAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES ARISING OUT OF OR RELATING IN ANY WAY TO THE PRODUCT AND/OR FOR BREACH OF THIS OR ANY OTHER WARRANTY OR CONDITION, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY SELLERS OWN NEGLIGENCE OR FAULT AND EVEN IF SELLER HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH LOSSES OR DAMAGES. Any product description (whether in writing or made orally by Seller or Sellers agents), specifications, samples, models, bulletin, drawings, diagrams, engineering sheets or similar materials used in connection with the Buyers order are for the sole purpose of identifying the Sellers products and shall not be construed as an express warranty or condition. Any suggestions by Seller or Sellers agents regarding use, applications, or suitability of the products shall not be construed as an express warranty or condition unless confirmed to be such in writing by Seller. Seller does not represent that the products it sells may not be compromised or circumvented; that the products will prevent any personal injury or property loss by burglary, robbery, fire or otherwise, or that the products will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm may only reduce the risk of a burglary, robbery or fire without warning, but it is not insurance or a guarantee that such will not occur or will not cause or lead to personal injury or property loss. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON ANY CLAIM AT ALL INCLUDING A CLAIM THE PRODUCT FAILED TO GIVE WARNING. However, if Seller is held liable whether directly or indirectly for any loss or damage with respect to the products it sells, regardless of cause or origin, its maximum liability shall not in any case exceed the purchase price of the product, which shall be fixed as liquidated damages and not as a penalty, and shall be the complete and exclusive remedy against the Seller. Should your product become defective during the warranty, please contact your installer to facilitate repair or replacement with Seller pursuant to the terms hereof. Seller reserves the right to replace any defective product under warranty with new, refurbished, or remanufactured product. ADT Security Services 1501 Yamato Road Boca Raton, FL 33431 2018 ADT Security Services 800-24127 2/18 Rev A Part 3
frequency | equipment class | purpose | ||
---|---|---|---|---|
1 | 2018-07-10 | 2405 ~ 2475 | DTS - Digital Transmission System | Original Equipment |
2 | 904.5 ~ 926.1 | DSS - Part 15 Spread Spectrum Transmitter |
app s | Applicant Information | |||||
---|---|---|---|---|---|---|
1 2 | Effective |
2018-07-10
|
||||
1 2 | Applicant's complete, legal business name |
Ademco Inc.
|
||||
1 2 | FCC Registration Number (FRN) |
0004071130
|
||||
1 2 | Physical Address |
2 Corporate Center Drive
|
||||
1 2 |
9040
|
|||||
1 2 |
Melville, New York 11747
|
|||||
1 2 |
United States
|
|||||
app s | TCB Information | |||||
1 2 | TCB Application Email Address |
h******@acbcert.com
|
||||
1 2 | TCB Scope |
A4: UNII devices & low power transmitters using spread spectrum techniques
|
||||
app s | FCC ID | |||||
1 2 | Grantee Code |
CFS
|
||||
1 2 | Equipment Product Code |
8DL-GRIPH
|
||||
app s | Person at the applicant's address to receive grant or for contact | |||||
1 2 | Name |
M******** A********
|
||||
1 2 | Title |
RF Compliance Engineer
|
||||
1 2 | Telephone Number |
516-5********
|
||||
1 2 | Fax Number |
516-5********
|
||||
1 2 |
m******@honeywell.com
|
|||||
app s | Technical Contact | |||||
1 2 | Firm Name |
Honeywell International Inc.
|
||||
1 2 |
Honeywell International Inc.
|
|||||
1 2 | Name |
M**** A******
|
||||
1 2 | Physical Address |
2 Corporate Center Drive
|
||||
1 2 |
Melville, Georgia 11747
|
|||||
1 2 |
Melville, 11747
|
|||||
1 2 |
United States
|
|||||
1 2 | Telephone Number |
51657********
|
||||
1 2 | Fax Number |
51657********
|
||||
1 2 |
m******@honeywell.com
|
|||||
app s | Non Technical Contact | |||||
n/a | ||||||
app s | Confidentiality (long or short term) | |||||
1 2 | Does this application include a request for confidentiality for any portion(s) of the data contained in this application pursuant to 47 CFR § 0.459 of the Commission Rules?: | Yes | ||||
1 2 | Long-Term Confidentiality Does this application include a request for confidentiality for any portion(s) of the data contained in this application pursuant to 47 CFR § 0.459 of the Commission Rules?: | Yes | ||||
1 2 | If so, specify the short-term confidentiality release date (MM/DD/YYYY format) | 01/06/2019 | ||||
if no date is supplied, the release date will be set to 45 calendar days past the date of grant. | ||||||
app s | Cognitive Radio & Software Defined Radio, Class, etc | |||||
1 2 | Is this application for software defined/cognitive radio authorization? | No | ||||
1 2 | Equipment Class | DTS - Digital Transmission System | ||||
1 2 | DSS - Part 15 Spread Spectrum Transmitter | |||||
1 2 | Description of product as it is marketed: (NOTE: This text will appear below the equipment class on the grant) | Hybrid Panel | ||||
1 2 | Related OET KnowledgeDataBase Inquiry: Is there a KDB inquiry associated with this application? | No | ||||
1 2 | Modular Equipment Type | Does not apply | ||||
1 2 | Purpose / Application is for | Original Equipment | ||||
1 2 | Composite Equipment: Is the equipment in this application a composite device subject to an additional equipment authorization? | Yes | ||||
1 2 | Related Equipment: Is the equipment in this application part of a system that operates with, or is marketed with, another device that requires an equipment authorization? | No | ||||
1 2 | Grant Comments | Power Output is Conducted. This filing meets KDB 447498 as a mobile device. Grantee must provide installation and operating instructions for complying with FCC multi-transmitter product procedures. The antenna(s) used for this transmitter must not transmit simultaneously with any other antenna or transmitter, except in accordance with FCC multi-transmitter product procedures. | ||||
1 2 | Is there an equipment authorization waiver associated with this application? | No | ||||
1 2 | If there is an equipment authorization waiver associated with this application, has the associated waiver been approved and all information uploaded? | No | ||||
app s | Test Firm Name and Contact Information | |||||
1 2 | Firm Name |
Ademco Inc.
|
||||
1 2 | Name |
M**** A********
|
||||
1 2 | Telephone Number |
516-5********
|
||||
1 2 | Fax Number |
000-0********
|
||||
1 2 |
m******@resideo.com
|
|||||
Equipment Specifications | |||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Line | Rule Parts | Grant Notes | Lower Frequency | Upper Frequency | Power Output | Tolerance | Emission Designator | Microprocessor Number | |||||||||||||||||||||||||||||||||
1 | 1 | 15C | CC | 2402 | 2480 | 0.00086 | |||||||||||||||||||||||||||||||||||
1 | 2 | 15C | CC | 2405 | 2475 | 0.144 | |||||||||||||||||||||||||||||||||||
Line | Rule Parts | Grant Notes | Lower Frequency | Upper Frequency | Power Output | Tolerance | Emission Designator | Microprocessor Number | |||||||||||||||||||||||||||||||||
2 | 1 | 15C | CC | 904.50000000 | 926.10000000 | 0.0340000 |
some individual PII (Personally Identifiable Information) available on the public forms may be redacted, original source may include additional details
This product uses the FCC Data API but is not endorsed or certified by the FCC