Installation Manual Senzafil Control Unit 1. Mounting Instructions The control unit has a construction with the ability to mount on a DIN rail. Nedap recommends to use the Nedap Light Controls Box to build-in the control unit.
(Nedap p/n ..) 2. Connections Note: The control unit must never be installed in a metal power cabinet. This would impede wireless communication. Use of error contact
+24Vdc OR To e.g. PLC Indicator
+24Vdc ON inputs 1-10V DIM inputs
Optional
+24Vdc / 2% power input Input current: 0.3Adc max gnd Details inputs and outputs
+24V*
RS232 CAN Group 1..8
* NOTE: Use isolated 24Vdc limited power supply with 2.5A max current. For US/Canada use a listed class 2 power ON/OFF Input Closed=ON Levels: <3.5Vdc OFF and >4.5Vdc ON DIM Input (Source current: 1mA (for light sensors)) Via switch:
Via 10k potmeter:
Via 1-10V Light Sensor:
Via 1-10V PLC/BMS:
Error Output Contact to gnd: 30V/2A max Closed=50%
0k=50%
1V=50%
1V=50%
Open=100%
10k=100%
10V=100%
10V=100%
ON DIM ERR Open=OFF Optional supply. (e.g. MAIN WELL type GS15E-6P1J) Control Unit Senzafil Copyright NEDAP Installation Manual 2. Led indications POWER CRTL RF LAMP ERROR x 4. Specifications On Off Fast blinking Regular blinking (1s) Off Regular blinking (1s) Off On Blinking Off Irregular blinking Power on Power off Controlling lamps EEPROM error (RF LED also blinking) Control ready Receiving RF packets EEPROM error (CTRL LED also blinking) Receiving no RF packets Lamp driver fault group x (>threshold) Lamp fault group x No errors group x Input Voltage Operating temperature 24Vdc 2%
0 60C Safety EMC EN60950 / Design to meet UL60950-1 EN301489-1 / FCC47 part 15 and 18 Dimensions (l x b x h) 145 x 120 x 65 mm FCC Declarations Compliance statement (part 15.19) This device complies with part 15 of the FCC Rules and to RSS210 of Industry Canada. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. Warning (part 15.21) Changes or modifications not expressly approved by the party responsible for compliance could void the users authority to operate the equipment. RF Exposure (OET Bulletin 65) To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter should only be used or installed at locations where there is at least 20cm separation distance between the antenna and all persons. Version:
Nedap P/N: 8015228 Control Unit Senzafil Copyright NEDAP 1.0 Installation Manual