ClareOne 16 Zone Wired Input Module
Installation Sheet
Important safety instructions
•
Before you install this module, be sure to read, keep,
and follow all instructions.
• When using a supervised back up battery, if the
battery is low, replace it with a compatible lead-acid
rechargeable battery.
Installation
Use the included screws for installation. The included antennas
should be used regardless of location, for optimal RF
communication.
Note: If the module is being installed in a metal container or
equipment rack, the antennas must extend outside the
container to ensure that the RF communication is not
interrupted.
Last modified: 01/25/21
Part number: CLR-C1-WD16
Description
To install the module:
The ClareOne 16 Zone Wired Input Module allows the
takeover of hardwired security zones making them compatible
with the ClareOne panel. The input module has 16 wired zone
inputs each with LED status, a tamper switch input, a back-up
battery charging terminal, and 2 auxiliary power outputs for
powered sensors, capable of outputting 500mA @ 12VDC. The
module supports powered and unpowered sensors, including
contact zones (open/close), motion sensors, and glass break
detectors. Input zones 1 and 2 have an optional 2-minute
communication time delay which can be enabled to prevent
repeated signals from motion sensors being sent to the panel.
Once all sensors are wired to the module, the modules and
each zone can be paired to the ClareOne panel. Follow the
steps in this installation sheet for module and sensor
connection to the panel.
Notes
•
•
This wireless module works with most wired sensors
that do not require a smoke loop.
Sensors/zones must be in their normally closed state
when added to the module.
1. Carefully select the mounting location, verifying that the
module is vertical, and secure it in position using the
provided screws.
Note: The module should be within 1000 ft (304.8 m) of
the panel, however walls and other construction materials
may lessen that distance.
2. Attach each of the antennas to the module, one in each of
the ANT terminals on the top of the module.
Note: The antennas should be clear of obstructions and if
in a metal enclosure, should extend outside of it.
3. Wire the sensors/leads to the desired terminals marked
Zone 1 through 16.
Wiring notes:
•
The module requires 4.7kΩ of end of line (EOL)
resistance on each zone. Some existing installations
may already have EOL resistors installed; it is
important to determine if this is the case and make
appropriate adjustments as needed. How the EOL
resistor is installed depends on if the sensor is
normally open (N/O) or normally closed (N/C). Refer
to Determining EOL resistance and sensor type for
© 30SEP20 Clare Controls, LLC.
1 / 6
DOC ID – 1987 • Rev 03
•
•
•
•
details on determining EOL resistance and if a sensor
is N/O or N/C.
close the tamper switch or replace the wire across the
inputs.
Install one of the included 4.7k Ω resistors on each
zone that has a sensor attached. Install the resistor in
parallel for N/O and in series with N/C sensors.
For any powered sensors, such as motion sensors
and glass break sensors, wire the Positive and
Negative leads from the sensor to the “AUX” (+) and
“GND” (-) terminals for device power. See Figure 1:
Wiring diagram on page 3.
5. Follow the ClareOne panel on-screen prompts to complete
the process.
Note: If you are not adding a battery backup
(recommended), disable the low battery notifications by
setting “Low Battery Detection" to Off under the Wired
Input Module's sensor settings.
To pair the zones to the module:
4. Wire the tamper switch input.
Note: Each zone must be paired individually, one at a time.
Notes
1. Verify that the module’s Pairing LED is still illuminated.
If using a tamper switch, wire it directly to the tamper
terminals without the need for an EOL resistor.
Note: If the LED is no longer illuminated, press and hold
the Pair button for two seconds.
If not using a tamper switch, simply connect a short
piece of wire across the tamper input.
2. Put the ClareOne panel into sensor Pairing mode.
3. Trip the desired hardwired zone.
5.
(Recommended) For any security system that is
supervised, a battery should be connected to the CLR-C1-
WD16. To provide an independent battery back up to the
module, connect the included battery leads to a 12V, 5Ah
lead acid rechargeable battery (battery not included). This
battery type is common with most traditional hardwired
security panels, otherwise it is recommended that you
connect the module to an auxiliary 16-volt power supply
with its own battery backup. Connect the power supply
leads from the provided power supply to the terminals
labeled +16.0V and GND on the wired input module.
Note: The dashed wire is positive.
6. Plug the power supply into a 120VAC outlet.
Note: Once a zone is tripped, its module LED illuminates
and remains lit until the module exits Pairing mode.
4. Follow the ClareOne panel on-screen prompts to complete
the process.
Note: If using a motion sensor, it is recommended to
connect them to Zone 1 or 2, and then enable the
communication delay for that zone. To enable/disable this
feature, see Buttons and LEDs – Memory Reset, on page
2. If using more than 2 hardwired motions, allocate the
most active areas on these zones. If using motions in an
occupancy detection mode for automation, disable this
setting.
Note: Do not plug the module into a receptacle controlled
by a switch.
5. Repeat steps 1-4 for each zone.
6. Once all zones are paired, press the Pair button.
Programming
The Pairing LED extinguishes.
The following instructions step through pairing the module to
the ClareOne panel.
Buttons and LEDs
Note: The CLR-C1-WD16 hardwired input module must be
paired with the ClareOne panel to ensure proper system
operation.
Buttons
The following section details the buttons and LEDs found on
the module.
To add the module to the panel:
1. Once the module is plugged in, open the front cover.
2. Put the ClareOne panel into sensor pairing mode, and
then select "Wired Input Module" as the device type. For
detailed programming instructions, refer to the ClareOne
Wireless Security and Smart Home Panel User Manual
(DOC ID 1871).
3. After setting the ClareOne panel to “Add mode”, press and
hold the Pair button on the module for two seconds. All
zone LEDs flash and then extinguish. The Pairing LED
illuminates, indicating that the module is in “Pair Mode”.
Pair: The Pair button, when pressed, puts the module in/out of
“Pair Mode”.
Memory Reset: The Memory Reset button clears the module’s
memory and returns it to the factory default settings. The
Memory Reset button is also used to enable/disable the
communication timer delay for Zones 1 and 2.
To clear the memory:
1. Remove power from the module.
2. Press and hold the Memory Reset button.
4. Trip the tamper input, either by opening the tamper switch
or removing the wire across the inputs. Once complete,
button.
4. After 3 seconds, release the Memory Reset button.
3. Reapply power while continuing to hold the Memory Reset
2 / 6
DOC ID – 1987 • Rev 03
The Processor, RF XMIT, and Pairing LEDs flash,
indicating the module is reset.
Determining EOL resistance and
sensor type
To enable communication timer delay on zones 1 or 2:
1. Pair a sensor to zone 1 or 2.
Note: Complete the next step before adding another
sensor.
2. Press the Memory Reset button.
The zone’s yellow LED illuminates, signifying that the
2-minute communication timer delay is enabled for that
zone.
To disable communication timer delay on zones 1 or 2:
1. Enter Pairing Mode.
2. Trip the sensor on zone 1 or 2, and then immediately
press the Memory Reset button.
In some instances, it is not visually apparent what is physically
connected to a zone in terms of any pre-existing EOL resistors
and whether the sensor is N/O or N/C. Use a multimeter to
learn this information.
With a sensor in its active state (i.e. door/window contact is
separated from its magnet), take a multimeter set to measure
resistance and connect the multimeter across the zone wires. If
the multimeter reads a value of 10kΩ or less, the sensor is
N/O, if the multimeter reads an open or extremely high
resistance (1Ω or higher) than the sensor is N/C. The table
below provides guidance for using the measurements to
determine the EOL resistance value, as well as the line
resistance for N/O sensors. This is the case regardless of the
number of sensors connected to a single zone, so long as all
sensors on the same zone are in series or in parallel with one
another.
The zone’s yellow DLY LED extinguishes signifying that
the lockout delay is disabled for the zone.
Note: The module will not work if there is a combination of
series and parallel sensors connected to the same input zone.
Multimeter reads for
N/O
Multimeter reads for
N/C
Value for EOL resistor Open
Value of line resistance
(10Ω or less)
Value of EOL resistor
plus line resistance
Sensors active
(sensor away from
the magnet)
Sensors inactive
(Sensors connected
to the magnet)
EOL resistance on existing installations typically ranges from
1kΩ - 10kΩ while line resistance should be 10Ω or less.
However, there may be some installations that do not have any
EOL resistors installed and the measured EOL resistance may
be the same as the line resistance. If there is no EOL resistor
installed than simply installing the provided 4.7kΩ resistor is all
that is needed. Ideally, any existing EOL resistors would be
removed and replaced with a 4.7kΩ resistor. If that is not an
option, additional resistors must be appropriately added, to get
the EOL resistance to 4.7kΩ. For more information, refer to the
ClareOne 16 Zone Wired Input Manual (DOC ID 1992).
LEDs
Pairing: The Pairing LED illuminates when the module is in
“Pair Mode” and is off when the module is in “Normal
Operation Mode”. If there are no zones learned the Pairing
LED flashes.
Processor LED: This LED flashes when the module is in
“Normal Operation Mode”.
RF XMIT LED: The RF XMIT LED illuminates when RF
transmission is sent.
Zone LEDs: During "Normal Operation Mode" each LED
remains off until its representative zone is opened, then the
LED illuminates. At the beginning of "Pair Mode" all Zone
LEDs flash briefly, after which each Zone LED remains off until
the zone is learned in and then it turns on and remains on until
"Pair Mode" is complete.
DLY LEDs: Zones 1 and 2 each have a DLY LED. When a
zone’s DLY LED is illuminated yellow, that zone has the
2-minute communication timer delay enabled. When the DLY
LED is off, that zone’s communication timer delay is disabled.
When the DLY LED is flashing, the associated zone is tripped,
and the 2-minute communication timer delay is in effect. All
additional triggers from that sensor are ignored for 2 minutes.
Testing the module
Verify that the module and zones are working correctly.
To test the module/zones:
1. Set the panel to the sensor test mode.
2. Trip each zone on the module one at a time. Monitor the
system after tripping the zones.
Refer to the ClareOne Wireless Security and Smart Home
Panel User Manual (DOC ID 1871) for specific test
information.
DOC ID - 1987 • Rev 03
3 / 6
Wiring
The graphic below details the module wiring.
Figure 1: Wiring diagram
(1) 12 VDC Backup battery connection
(4) 12VDC Auxiliary Power Output 2
(2) 16 VDC Power supply connection
(3) 12VDC Auxiliary Power Output 1
(1.a) Negative wire (-)
(1.b) Positive wire (+)
(2.a) Positive wire (+)
(2.b) Negative wire (-)
(3.a) Positive wire (+)
(3.b) Negative wire (-)
(4.a) Positive wire (+)
(4.b) Negative wire (-)
(5) Tamper input
(6) Wired zone N/O loop
(7) Wired zone N/C loop
Note: When wiring a sensor that also has a tamper output, the alarm output and tamper output should be wired in series so that
the zone will trigger on either a motion or tamper event.
4 / 6
DOC ID – 1987 • Rev 03
Specifications
Compatible panel
ClareOne (CLR-C1-PNL1)
Input voltage
16 VDC Plug-in transformer
Auxiliary voltage output 12 VDC @ 500 mA
EOL supervision
4.7K (resistors included)
Battery backup
12 VDC 5Ah (optional)
Input zones
Zone type
16
N/O or N/C compatible
Tamper zone
Use external switch or wire to short
Dimensions
5.5 × 3.5 in. (139.7 × 88.9 mm)
Operating environment
Temperature
Relative humidity
32 to 122°F (0 to 50°C)
95%
Regulatory information
Manufacturer
Clare Controls, Llc.
7519 Pennsylvania Ave, Suite 104
Sarasota, FL 34243
North American
standards
FCC: 15.109 Class B 15.231, Industry Canada:
ICES-003, RSS-210
FCC compliance
FCC / IC Statement
This equipment has been tested and found to
comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable
protection against harmful interference in a
residential installation.
Per FCC 15.19 (a) (3) and (a) (4), This device
complies with part 15 of the FCC Rules.
Operation is subject to the following conditions:
(1) this device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesirable operation.
Per FCC 15.21, The user manual or instruction
manual for an intentional or unintentional radiator
shall caution the user that changes or
modifications not expressly approved by the party
responsible for compliance could void the user's
authority to operate the equipment. This
equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in
accordance with the instructions, may cause
harmful interference to radio communications.
However, there is no guarantee that interference
will not occur in a particular installation.
If this equipment does cause harmful interference
to radio or television reception, which can be
determined by turning the equipment off and on,
the user is encouraged to try to correct the
interference by one or more of the following
measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment
and receiver.
•Connect the equipment into an outlet on a circuit
different from that to which the receiver is
connected.
•Consult the dealer or an experienced radio/TV
technician
for help. This device complies with Industry
Canada license-exempt RSS standard(s).
Operation is subject to the following two
conditions: (1) this device may not cause
interference, and (2) this device must accept any
interference, including interference that may
cause undesired operation of the device.Cet
appareil est conforme avec Industrie Canada
exempts de licence standard RSS (s). Son
fonctionnement est soumis aux deux conditions
suivantes: (1) cet appareil ne doit pas provoquer
d'interférences et (2) cet appareil doit accepter
toute interférence, y compris celles pouvant
causer un mauvais fonctionnement de l'appareil.
In accordance with FCC requirements of human
exposure to radio frequency fields, the radiating
element shall be installed such that a minimum
separation distance of 20 cm is maintained from
the general population.
FCCID: 2ABBZ-RF-CHW16-433
IC: 11817A-CHW16433
This device complies with Part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation. Changes or
modifications not expressly approved by the party
responsible for compliance could void the user's
authority to operate the equipment. This Class B
digital apparatus complies with Canadian ICES-
3B. Cet appareil numérique de la classe B est
conforme à la norme NMB-003 du Canada.
MANUFACTURER HEREBY DISCLAIMS ALL
WARRANTIES AND REPRESENTATIONS,
WHETHER EXPRESS, IMPLIED, STATUTORY
OR OTHERWISE INCLUDING (BUT NOT
LIMITED TO) ANY WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE WITH RESPECT TO
THESE PRODUCTS AND ANY RELATED
SOFTWARE. MANUFACTURER FURTHER
DISCLAIMS ANY OTHER IMPLIED WARRANTY
UNDER THE UNIFORM COMPUTER
INFORMATION TRANSACTIONS ACT OR
SIMILAR LAW AS ENACTED BY ANY STATE.
(USA only) SOME STATES DO NOT ALLOW
THE EXCLUSION OF IMPLIED WARRANTIES,
SO THE ABOVE EXCLUSION MAY NOT APPLY
TO YOU. THIS WARRANTY GIVES YOU
SPECIFIC LEGAL RIGHTS AND YOU MAY
ALSO HAVE OTHER LEGAL RIGHTS THAT
VARY FROM STATE TO STATE.
DOC ID - 1987 • Rev 03
5 / 6
Environmental
class
UL: Indoor dry
IEC: 3K5
EU compliance
EN 54
EN 54-00:0000
European Union
directives
MANUFACTURER MAKES NO
REPRESENTATION, WARRANTY, COVENANT
OR PROMISE THAT ITS ALARM PRODUCTS
AND/OR RELATED SOFTWARE (I) WILL NOT
BE HACKED, COMPROMISED AND/OR
CIRCUMVENTED; (II) WILL PREVENT, OR
PROVIDE ADEQUATE WARNING OR
PROTECTION FROM, BREAK-INS,
BURGLARY, ROBBERY, FIRE; OR (III) WILL
WORK PROPERLY IN ALL ENVIRONMENTS
AND APPLICATIONS.
1999/5/EC (R&TTE directive): Hereby, Clare
Controls declares that this device is in
compliance with the essential requirements and
other relevant provisions of Directive 1999/5/EC.
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
2006/66/EC (battery directive): This product
contains a battery that cannot be disposed of as
unsorted municipal waste in the European Union.
See the product documentation for specific
battery information. The battery is marked with
this symbol, which may include lettering to
indicate cadmium (Cd), lead (Pb), or mercury
(Hg). For proper recycling, return the battery to
your supplier or to a designated collection point.
For more information see: www.recyclethis.info.
Warranty information
Clare Controls offers a two (2) year limited warranty on original
Clare Controls components, from the date of shipment from
Clare Controls.
Contact information
Clare Controls, LLC.
7519 Pennsylvania Ave, Suite 104
Sarasota, FL 34243
General: 941.328.3991
Fax: 941.870.9646
www.clarecontrols.com
Integrator/Dealer Support: 941.404.1072
claresupport@clarecontrols.com
Homeowner Support (ClareCare): 941.315.2273 (CARE)
help@clarecontrols.com
6 / 6
DOC ID – 1987 • Rev 03