C-site User Manual Version 1.1 Ex-CWTD-WRM-00009 Page 2 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 Version history Version Date Description Author Approver 1.0 1.1 23.2.2015 Approved version KL TV 13.3.2015 IC certification numbers p. 9 TSo PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 3 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 Contents 1.1 2.1 2.2 Contents .................................................................................................................................................. 3 Introduction ....................................................................................................................................... 4 1 C-site units at a glance .............................................................................................................4 1.1.1 C-site S7 .............................................................................................................................. 4 1.1.2 C-site R7 .............................................................................................................................. 7 2 Notes and wireless conditions .......................................................................................................... 9 All units (S7001, S7002, R7-001, R7-101) ...............................................................................9 C-site R7-001......................................................................................................................... 10 3 Getting started ................................................................................................................................ 12 Before R7 configuration ......................................................................................................... 13 R7 WLAN configuration ......................................................................................................... 15 R7 3G configuration ............................................................................................................... 18 4 Setting up the sensor network ........................................................................................................ 19 5 Troubleshooting .............................................................................................................................. 24 6 Maintenance ................................................................................................................................... 25 Security passwords ............................................................................................................... 26 7 Support ........................................................................................................................................... 27 3.1 3.2 3.3 6.1 PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 4 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 1 Introduction This user manual describes the practices to take the C-site remote monitoring system into use. Also guidance on how to operate and maintain the system is given. C-site remote monitoring system consists of C-site S7 sensor units as well as C-site R7 remote terminal units. 1.1 C-site units at a glance 1.1.1 C-site S7 C-site S7 is the sensor unit of the C-site Remote monitoring system. It reads data from the transducers and transfers the data wirelessly to the C-site R7 units. C-site S7 has two different model options, C-site S7001 and C-site S7002. C-site S7001 is a sensor unit with integrated Keller pressure transducer. C-site S7002 is equipped with a connector that enables different type of sensors to be used with the sensor unit. 1. Ex batteries 2. 2.4GHz antenna 3. Battery cap Figure 1. C-site S7001 top view and back view.
(Note! Batteries ordered and delivered separately) PRINTED 13.3.2015 1. Rotation adapter SW 27 mm 2. Rotation lock nut SW 36 mm CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 5 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 1. Connector cap 2. Binder connector 1. Ex batteries 2. 2.4GHz antenna 3. Battery cap 4. Binder connector 1. Connector cap 2. Binder connector Figure 2. C-site S7002 top view and back view.
(Note! Cables and transmitters for Binder connector ordered separately) PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 6 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 1.1.1.1 C-site S7 screens This section describes the different screen views the S7 unit can display during operation. After power up, the S7 unit starts automatic scanning of available R7 units. Normally the scanning phase takes about 30 seconds. In normal operation, the screen shows the pressure (1), temperature (2), received signal strength (3) and battery levels (4 and 5). 1. Pressure 2. Temperature 3. Signal level 4. Battery level 5. Battery level from the In case the alarm sign is on, please check the alarm status and details alarm log on the R7 display. In case of a low battery level, please replace the batteries in safe area. Only batteries delivered by Creowave is permitted. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com 1.1.2 C-site R7 Page 7 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 C-site R7 is remote terminal unit of the C-site Remote monitoring system. C-site R7 collects data and information from multiple C-site S7 units and sends the information onwards to the system. C-site R7 has three different model options, C-site R7-001, R7-101 and R7-201. Only difference between the models is the technology it uses WLAN, GSM or TETRA. Figure 3 C-site R7 unit view with accessories.
(Note! Accessories ordered and delivered separately. Standard package includes plugs as well as one armored gland in the package, but not installed) PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 8 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 1.1.2.1 C-site R7 screens This section describes the different screen views the R7 unit can display during operation. When powering up, the R7 unit asks the user to enter a password (default 2580). After password has been entered the normal screen view appears. Process measurements click to see the process measurement readings from S7 unit. Field device network click to see the connected devices. Device information click to see the R7 device information. Notifications & alarms click to see the notifications and alarms PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 9 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 2 Notes and wireless conditions Before getting started, make sure you read this chapter thoroughly. The use of units is not permitted without going through the notes and wireless conditions for the specific unit. 2.1 All units (S7001, S7002, R7-001, R7-101) The following notes and conditions concerns the following units: S7001, S7002, R7-001, R7-101. This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation. These radio transmitters (S7001, S7002, R7-001, R7-002, R7-101, R7-102) have been approved by Industry Canada to operate with the antenna types listed below with the maximum permissible gain indicated. Antenna types not included in this list, having a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with this device. C-site S7001, S7002 (IC: 12318A-S7) antenna: Bulgin PX407, gain 4.8 dBi C-site R7-001, R7-002 (IC: 12318A-R7WLAN) antenna:
2.4GHz: Extronics iANT200-24-S-1, Gain 5 dBi 5GHz: Extronics iANT200-58-S-1, Gain 8 dBi. When operating within 5180-5220MHz the antenna cable shall be at least 1.5m (RG58) Dual band WiFi: Extronics iANT216, Gain 5 dBi @ 2.4-2.5GHz, 7 dBi @ 4.94-5.925GHz. When operating within 5180-5220MHz the antenna cable shall be at least 1m (RG58). C-site R7-101, R7-102 (IC: 12318A-R73G) antenna:
2.4 GHz wireless:
o Extronics iANT200-24-S-1, Gain 5 dBi o Aerial AV1433-24501, gain 2dBi GSM / 3G: Extronics iANT213QB, Gain 4 dBi @806-960MHz, 5 dBi @ 1710-2170MHz __________________________________________________________________ Ces metteurs radio (S7001, S7002, R7-001, R7-002, R7-101, R7-102) ont t autoriss par Industry Canada tre utiliss avec les types dantennes numrs ci-dessous, avec le gain maximum autoris indiqu. Il est strictement interdit dutiliser des types dantennes qui ne sont pas inclus dans cette liste, avec un gain suprieur au gain maximum autoris indiqu pour ce type, avec cet appareil. Antenne C-site S7001, S7002 (IC : 12318A-S7): Bulgin PX407, gain 4,8 dBi Antenne C-site R7-001, R7-002 (IC : 12318A-R7WLAN):
2,4 GHz : Extronics iANT200-24-S-1, gain 5 dBi 5 GHz : Extronics iANT200-58-S-1, gain 8 dBi. En cas de fonctionnement dans la bande 5180-5220 MHz, le cble de lantenne doit mesurer au moins 1,5 m (RG58). WiFi bi-bande : Extronics iANT216, gain 5 dBi 2,4 - 2,5 GHz, 7 dBi 4,94-5,925 GHz. En cas de fonctionnement dans la bande 5180-5220MHz, le cble de lantenne doit mesurer au moins 1 m (RG58). Antenne C-site R7-101, R7-102 (IC : 12318A-R73G):
2,4 GHz sans fil :
Extronics iANT200-24-S-1, gain 5 dBi o o Aerial AV1433-24501, gain 2 dBi GSM / 3G : Extronics iANT213QB, gain 4 dBi 806-960MHz, 5 dBi 1710-2170MHz __________________________________________________________________ This device complies with Industry Canadas licence-exempt RSSs. Operation is subject to the following two conditions:
PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 10 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause undesired operation of the device. ______________________________________________________________________________________________ Le prsent appareil est conforme aux CNR dIndustrie Canada applicables aux appareils radio exempts de licence. Lexploitation est autorise aux deux conditions suivantes:
(1) lappareil ne doit pas produire de brouillage;
(2) lutilisateur de lappareil doit accepter tout brouillage radiolectrique subi, mme si le brouillage est susceptible den compromettre le fonctionnement. _________________________________________________________________________________________________ Note! The grantee is not responsible for any changes or modifications not expressly approved by the party responsible for compliance. Such modifications could void the users authority to operate the equipment. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Absolute minimum distance between the antennas is always 20 cm. Minimum distance between the antennas and people is 50 cm for C-site R7 models and 20 cm for C-
site S7 models. Always install the antennas pointing upwards. __________________________________________________________________________________________________ La distance minimale absolue entre les antennes est de 20 cm. La distance minimale entre les antennes et les personnes est de 50 cm pour les modles C-site R7 et de 20 cm pour les modles C-site S7. Toujours installer les antennes pointe vers le haut. ___________________________________________________________________________________________________ 2.2 C-site R7-001 In addition to the notes in chapter 2.1, the following notes and conditions concerns the unit C-site R7-
001.
(i) the device for operation in the band 5150-5250 MHz is only for indoor use to reduce the potential for harmful interference to co-channel mobile satellite systems. _____________________________________________________________________________________________________
(i) lappareil destin fonctionner dans la bande 5150-5250 MHz est uniquement destin une utilisation intrieure afin de rduire les potentielles interfrences nuisibles avec les systmes satellites mobiles du mme canal. __________________________________________________________________________________________ Operating WLAN frequency bands of the R7-001:
2412-2462 MHz 5180-5220 MHz (indoor use) 5745-5825 MHz DFS channes (ch 52-64, 5260-5320 MHz and ch 100-140, 5500-5700MHz) have been disabled by the firmware. The firmware of the WLAN transceiver is factory installed and cannot be modified by the PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 11 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 installer or end user by any means. In addition, ch 48 (5240 MHz) has been disabled to prevent disturbance within DFS channels. The RF parameters of the WLAN connection are controlled by the FW. The only parameter that shall be modified by the installer is the channel list. By selecting country of operation the installer can select channels to be used from the channels that are allowed. Access to modify the WLAN settings is password protected. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 12 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 3 Getting started This chapter describes how to configure the R7 and S7 and how to take the system into use. Before getting started, make sure you have read thoroughly the paragraph 2 Notes and Wireless conditions. The use of units is not permitted without going through the notes and wireless conditions for the specific unit. What you need to get started:
From Creowave:
o C-site Configuration toolkit (ordered separately)
PC with Ethernet port and Windows 7 or later operating system
Engineering tool software and license file from Creowave
1 pc R7-001 for configuration use only
+12VDC/2A power supply with open-ended power cable 0,5-1,5 mm2
(AWG20-14) o C-site Installation toolkit with installation hand tools (ordered separately) o C-site Spare part kit with spares for S7 and R7 (ordered separately) o Installation manuals
Ex-CWIM-WRM-00001_Installation_Manual_S7
Ex-CWIM-WRM-00002_Installation_Manual_R7 From the network administrator:
o WLAN network name (SSID) o WLAN security mode o WLAN Pre-Shared key o 3G APN (Access Point Name) o 3G SIM card PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 13 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 3.1 Before R7 configuration WARNING! Before getting started please read Installation Manual for R7 (Ex-CWIM-WRM-
00002_Installation_Manual_R7) The following configuration procedures need to be done on safe zone. 1. Open connector cover 2. Connect power cable to Ex terminals (see R7 Installation manual for detailed instructions) 3. Connect Ethernet cable to Ex terminals (see R7 Installation manual for detailed instructions) 4. Connect antennas to R7 (see R7 Installation manual for detailed instructions) 1. Antenna cables 2. Connector cover 3. Power cable 4. RS485 cables
(optional) 5. Ethernet cable Install SIM-card (3G option) (see R7 Installation manual for detailed instructions) 5. 6. Power up R7 7. On the R7 LCD screen type the password (default 2580) 8. On the screen tab Device info to check the R7 status. In case of alarms, please see Troubleshooting section no. 5. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 14 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 9. On PC, click Windows and on the search field type: Network and sharing center 10. Select Network and Sharing Center 11. In Network and Sharing Centre go to Change adapter settings 12. Select Local Area Connection and right mouse click Properties 13. On Item list select Internet Protocol Version 4 (TCP/IPv4) and click Properties PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 15 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 14. Select Use the following IP address and type:
IP Address: 192.168.200.1 a. b. Subnet mask: 255.255.255.0 c. Leave default gateway empty 15. Now the connection between the R7 and the PC is ready. 3.2 R7 WLAN configuration This section describes only the configuration for C-site R7 unit with WLAN option, model R7-001. Please note, that you can login to configuration site as an admin or as a user. As an admin you can configure the R7 WLAN, as a user you can only view the settings. See more details from chapter 6.1. Please also note, that the firmware updates needs to be done by Creowave or assigned representative of Creowave. 1. Open web browser 2. Enter web address: 192.168.200.102 3. Enter Username: admin. Leave password blank. NOTE! Remember to change the username and password after configuration. Keep good care of your username and password, you are not able to recover those afterwards. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 16 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 4. Click Basic and then Wireless 5. Under Wireless configure following:
a. Wireless Network Name (the network you want to connect R7) b. Region/Country: change the country or region c. Check that Auto channel select is enabled d. Wireless Security Mode (according to network setup) e. Type the Pre-Shared Key (according to network setup) f. Click Save settings from the top of the page and then click Continue 6. Go to LAN settings a. Modify LAN settings according to the network if needed. Ask more information from the network administrator b. Click Save settings from the top of the page and then click Reboot the Device PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 17 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 7. Wait for 60 seconds WLAN to reboot and open web browser 8. Re-enter web address 192.168.200.102 9. Login and check from the front page the connection status:
a. Network name b. RSSI level 10. Click Tools and under Admin to change the passwords
WLAN/LAN connection to the site network is now ready PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 18 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 3.3 R7 3G configuration This section describes only the configuration for C-site R7 unit with GSM option, model R7-101. More detailed guidance is given in the User Manual for Engineering Tool (document creation in process). In case needed, contact Creowave for support at service@creowave.com. 1. Make sure that the Ethernet cable is connected to the R7 and to the PC. 2. Launch Engineering tool software. 3. On the device list select R7 4. Modify APN settings according to the 3G network operator 5. Define a. User name and Password (optional) b. Define Proxy address (optional) c. Define Proxy port (optional) d. Define Authentication type: PAP/CHAP/None (optional) PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 19 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 4 Setting up the sensor network This section describes how to set up the sensor unit network. This needs to be done on the safe zone, outside the hazardous area. More detailed guidance is given in the User Manual for Engineering Tool (document creation in process). In case needed, contact Creowave for support at service@creowave.com. 1. Make sure that the Ethernet cable is connected to the R7 and to the PC 2. Power up the R7 3. Launch the Engineering tool 4. On the Session click Connect. 5. Type Remote IP address 192.168.200.101. The remote port has default port determined and dont need to be changed. The security key is default. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 20 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 6. Select R7 from the Devices list and configure:
a. TAG b. Location c. Measurement interval for the diagnostics d. LCD screen password (default 2580) e. Network key f. APN (3G option) 7. Insert batteries to the S7 units. Battery level indicators on the S7s LCD may show low battery levels at the start-up which is a normal situation. Battery level will normalize after few hours of operation. 8. S7s will appear on the Devices list after the connection is ready. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 21 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 9. Select S7 from the Devices list and configure:
a. TAG b. Location c. Heartbeat interval d. Measuring interval 10. On the Devices list under S7 select transducer and configure:
a. TAG b. Low and High Alarm limits c. Deadband for the alarm limits d. From the Display drop-down select the value unit (sets also the value unit for the S7 LCD screen) 11. Click S7 on the Devices list set the Network key a. NOTE! After the Network key is changed the S7 will disconnect from the R7 b. Make sure that all configurations are done before changing the Network key c. Keep the Network key in secure place. Note! After the key is set, the S7 unit can only connect to R7 unit with this key. 12. After all S7 are configured select R7 from the Devices list 13. Change the Network key PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 22 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 14. Now all S7s should appear on the Devices list after 2 minutes 15. Configure measurement intervals of the S7 units according the requirement 16. Select R7 and define the Fixed IP address or activate DHCP (R7 Ethernet port) a. If DHCP is used the new IP address can be seen on the R7s display PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 23 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 17. Units are now ready for the field installation a. NOTE: If the measurement interval is < 10 seconds it is recommended to remove batteries from the S7 units to save battery life b. WARNING: Batteries must be inserted outside the hazardous area!
c. It is recommended to install R7 units first to the field 18. After the installation contact the system administrator to verify that all units are connected to the SCADA/DCS system. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 24 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 5 Troubleshooting If you are facing problems in configuration or use of the products, please have a look at this troubleshooting section. If more assistance is needed, contact your sales representative or Creowave at service@creowave.com. C-site S7 Alarm sign is active on the S7 screen Check the alarm limit settings and process values from Engineering Tool Check the battery levels on the S7 display S7 doesnt connect to the R7 Check that the antenna is properly installed to the S7 Check the battery levels on the S7 display Check that the R7 is powered on Check the sensor network antenna connection on the R7 Check the alarm log from the R7 display Check that there is no big metal obstacles between the S7 and R7 S7 doesnt get data from the transducer Check the configuration of S7 from R7 or Engineering Tool that the right type of transducer has been installed Check the transducer connection C-site R7 R7 doesnt power up Check the power switch Check the power cable connection CAUTION!
BEFORE OPENING THE UNIT LID MAKE SURE THE EXTERNAL POWER SWITCH IS OFF. R7 doesnt find S7 units Check that the S7 is not already connected to another R7 Check the alarm log from the R7 screen Check the antenna connections Check that the network ID is correct Check that there are no big obstacles between the R7 and S7 Check that the S7 units have been powered up R7 doesnt connect to the monitoring system Check the network connection password Check the WLAN antenna connection Check that the monitoring system IP address is correct Check that a valid SIM card has been installed (3G) R7 cannot be reached by Ethernet Check wiring Check the IP address of R7 from the R7 screen Check that your computer is in the same subnet as R7 PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 25 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 6 Maintenance Some special conditions of safe use for these Ex approved equipment has been set. Read these carefully before taking the equipment into use. C-site S7 Special conditions of safe use 1. The batteries shall not be removed or replaced in hazardous area. 2. The equipment shall not be opened in hazardous area. 3. Only batteries delivered by Creowave are permitted to be used in conjunction with this apparatus. 4. The RF output power of the sensor unit is set by the manufacturer and shall not be modified by the user by any means. 5. The end user shall ensure that the length of cable used to connect the transducer to the sensor unit determined by ensuring Ci+Cc < Co and Li + Lo, where Ci = capacitance of transducer, Cc = capacitance of cable for required length, Li = inductance of transducer, Lc =
inductance of cable for required length, Co and Lo see Table of entity parameters. C-site R7 Special conditions of safe use 1. The LCD screen shall be routinely inspected and replaced immediately if broken. 2. The battery pack or cells used to supply the RTU C-site R7 must be IECEx / ATEX approved and have a 12Vdc nominal voltage and a peak open circuit voltage that does not exceed 15 Vdc. 3. The Ethernet connection shall be made only through ATEX/IECEx certified Ethernet isolator e.g. MTL 9468-ET, part no. INM9468 or equivalent. 4. The RF output power of the RTU C-site R7 is set by the manufacturer and shall not be modified by the user by any means. 5. Do not open equipment while energized. Connection / disconnection to the input terminal J1 shall only be made while the supply is de-energized. PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 26 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 6.1 Security passwords There are three role-based user accounts for the R7 configuration. Table 1 below describes the levels of access. Role User name Access User for read-only access for R7 WLAN configuration user For WLAN read-only access Maintenance - for R7 and sensor network configuration maint Administrator for R7 WLAN configuration admin Configure communications between R7 and S7. No RF output power control. Configure RS485 baud rate Configure Ethernet of R7 All maintenance privileges Configure WLAN Configure Ethernet of the WLAN transceiver Set passwords Table 1. Role Based User Accounts Usernames and default passwords for the different user accounts are as follows:
Username: user Leave password field blank Username: maint Password: default Username: admin Leave password field blank PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com Page 27 / 27 Ex-CWTD-WRM-00009 C-site User Manual Version 1.1 7 Support In case more support, please contact Creowave service at service@creowave.com PRINTED 13.3.2015 CREOWAVE OY | Creowave Oy, Yrttipellontie 10 H, 90230 Oulu, Finland | T: +358 10 8326 300 | www.creowave.com