GENERAL INSTALLATION GUIDELINES ALARMPATH ECHO AP-4700V WIRELESS SUBSCRIBER UNIT INSTALLATION INSTRUCTIONS The AP-4700V draws a substantial amount of current - approximately 2 AMPS - during transmit. Therefore, follow the instructions for powering the AP-4700V carefully!
IMPORTANT! Failure to Read and Follow These Installation Instructions May Jeopardize Subscriber Security INTRODUCTION: The AP-4700V is a 2-way, fully supervised Wireless Subscriber Unit for use on the nationwide (50 United States plus Puerto Rico and the US Virgin Islands) AlarmPath Network. The AlarmPath Control Center Processors forward these wireless signals to ANY Central Station via standard communicator techniques. The AlarmPath Control Center Processors will generate and report a Communications Failure signal in the event that the network does not receive the expected supervisory test signal from the Wireless Subscriber Unit during the scheduled period. WARNING: To ensure users safety and to satisfy FCC RF exposure requirements, this unit must be installed so that a minimum separation distance of 32 cm is always maintained between the antenna of the transmitting device and nearby persons. Operation closer than this distance is not recommended. Use ONLY the following antenna supplied by AlarmPath to comply with this warning. Colinear Antenna, PN: HG3DB or Wave Rigid Whip Antenna, PN: G0DB, NOTE: FOR FIXED OPERATION ONLY NOTE: This equipment has been tested and found to comply with the limits for a Class B Unintentional Radiator, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction Manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of more of the following measures: 1. Reorient or relocate the receiving antenna, 2. Increase the separation between the equipment and receiver, 3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, 4. Consult the dealer or an experienced radio/TV technician for help. Since the mounting location can ONLY be selected based on RF performance, it is HIGHLY recommended that the installer follow the STEP 1 below BEFORE any wires are run. Generally, high locations are best. DO NOT mount radio in basement or below grade as unpredictable performance may result. Whenever possible, DO NOT mount the AP-4700V in non-climate controlled environments (i.e. attics may become extremely hot in summer, garages may become extremely cold in winter). Avoid mounting locations within 3 feet of large metal objects (air conditioners, metal garage doors, etc.), AC power lines, and fluorescent light fixtures. A fair amount of care may be required to mount the AP-4700V so as to achieve an optimal RF path. Installer should spend as much time as needed to obtain the highest signal level possible. Press the test button (S1), bottom right hand corner; the unit will transmit one long blink. After the unit transmits observe Coverage LED and count the number of blinks. Move the unit as required to achieve the best Coverage (signal strength) possible based on the chart below. As needed, re-
position the unit, transmit and watch the Coverage LED to indicate change. The unit will not transmit if 15 seconds has not passed. There is a 2 second delay between blink cycles. Once a location has been selected based on Coverage, permanently and securely mount the unit using #6 screws (not supplied) Phone 866-ALARMPATH The AP-4700V requires 12VDC. It draws less than 20mA during standby, and almost 2 AMPS during Transmit (for less than 1 second). It is recommended that the AP-4700V be powered directly from the battery
(4AH Minimum) of the alarm control panel, with a 3 AMP fuse in series. As the standby current is very low, the alarm control panel charging circuit will not be affected, and the battery is capable of supplying the 2 AMP current on transmit. DO NOT power theAP-4700V from the aux output of the control panel. 22-gauge wire can be used up to 50 feet in length, and 18-gauge wire can be used up to 100 feet in length. NO NETWORKDO NOT INSTALL, Try Re-positioning Unit VERY WEAK COVERAGEDO NOT INSTALL, Try Re-positioning Unit MARGINAL COVERAGE Try Re-positioning Unit or High-Gain Antenna INSTALL with CAUTION GOOD COVERAGE SIGNAL-OK TO INSTALL VERY GOOD COVERAGE SIGNAL-OK TO INSTALL EXCELLENT COVERAGE-OK TO INSTALL Temporarily connect power to the AP-4700V from a fully charged 12V (4AH minimum) battery. DO NOT mount the AP-4700V at this time. Position the unit in the desired mounting location. SELECT A MOUNTING LOCATION APPLY POWER
# BLINKS 0 BLINKS 1 BLINK 2 BLINKS 3 BLINKS 4 BLINKS 5 BLINKS STEP2 STEP1
screw terminals. DO NOT short wires to metal case. Connect power in at least 2 of the 4 mounting holes. SEE OTHER SIDE FOR STEP 3 Fax 631-696-7943 COVERAGE to
CONNECT INPUTS CHANNEL TRIGGERING NOTE: Use any ONE method to trigger INPUT #1. Use method P or N for INPUT 2 and/or 3. All channels triggered by P or N method have a 1 SEC integration delay. SC (SmartChannel) will analyze Bell or Siren Driver output to determine if trigger is BURG or FIRE, and has a 7 SEC integration delay. After triggering channels, use Signal Verification online at www.alarmpath.com or call AlarmPath Toll-Free (866) 252-7672 and access Automated Operator System (Touch-Tone option 5) STEP3 SC-BP SmartChannel (INPUT Terminal 1) BELL POSITIVE TRIGGER e.g. ADEMCO, NAPCO and others with switched BELL POSITIVE terminals CUT resistor R36 to convert INPUT #1 to SmartChannel
(remove power from unit before cutting any jumpers) Make sure resistor R30 has NOT been cut Run wire from AP-4700V INPUT #1 screw terminal to Alarm Control Panel BELL + terminal Steady Voltage (+4.5 to +14.5VDC) on INPUT #1 sends code 1D (BURG), pulsating Voltage (~800mS 8 SEC/cycle) sends code 1C (FIRE) SC-BN SmartChannel (INPUT Terminal 1) BELL NEGATIVE TRIGGER e.g. DSC and others with switched BELL NEGATIVE terminals CUT resistor R36 to convert INPUT #1 to SmartChannel
(remove power from unit before cutting any jumpers) CUT resistor R30 to convert INPUT #1 to Low/Negative/Pull-to-
ground trigger (remove power from unit before cutting any jumpers) Run wire from AP-4700V INPUT #1 screw terminal to Alarm Control Panel BELL terminal Constant Ground on INPUT #1 sends code 1D (BURG), pulsating Ground (~800mS 8 SEC/cycle) sends code 1C
(FIRE) P POSITIVE TRIGGER (INPUT #1, 2 or 3) e.g. Any POSITIVE voltage (+4.5 to 14.5VDC) trigger To use this method for INPUT #1, make sure resistor R36 has N NEGATIVE TRIGGER (INPUT #1, 2 or 3) e.g. Any NEGATIVE or Pull-to-Ground trigger To use this method for INPUT #1, make sure resistor R36 has NOT been cut Make sure resistor R30, R33, R31 (INPUT #1, 2, 3 respectively) has NOT been cut, as applicable Run wire from AP-4700V INPUT #1, 2, 3 screw terminal (as applicable) to Positive trigger (Positive Voltage on alarm) INPUT # 1, 2, 3 send codes 1, 2, 3, respectively NOT been cut CUT resistor R30, R33, R31 (INPUT #1, 2, 3 respectively), as applicable (remove power from unit before cutting any jumpers) Run wire from AP-4700V INPUT #1, 2, 3 screw terminal (as applicable) to Negative/Pull-to-Ground trigger (Goes Negative /
Pulls-to-Ground on alarm) INPUT # 1, 2, 3 send codes 1, 2, 3, respectively SC-S SmartChannel (INPUT 1) SIREN DRIVER TRIGGER e.g. CADDX and other Alarm Control Panels with built-
in siren drivers USE THIS METHOD ONLY IF METHOD SC-BP OR SC-BN CANNOT BE USED CUT resistor R36 to convert INPUT #1 to SmartChannel (remove power from unit before cutting any jumpers) Run wire from AP-4700V INPUT #1 screw terminal to Alarm Control Panel Built-In Siren Driver terminal. See NOTE below Warble Siren Audio Tone (~500hz to 2khz) on INPUT #1 sends code 2D (BURG), Steady Siren Audio Tone (~1khz) sends code 2C (FIRE) NOTE:
Observe LED D2 to determine correct polarity. D2 will light
(steady or blinking) when connected to the correct SIREN terminal HSO HIGH-SECURITY OPTION The AlarmPath HSO-KIT instructions provides an output if the AP-4700V loses coverage. detailed terminal, which for wiring the HSO includes