Single Phase Multi-Tariff ANSI Meter EDMI NC30 Single Phase Multi-Tariff ANSI Meter User Manual PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Content 1. Product Description .................................................................................................................................... 1 2. Total kWh Register ...................................................................................................................................... 2 3. Meter Memory ............................................................................................................................................... 2 4. Event Record ................................................................................................................................................ 2 5. LCD display during power off .................................................................................................................... 2 6. Maxim Demand ............................................................................................................................................. 2 7. Multi-Tariff energy, maximum 4 tariff (TOU) ............................................................................................ 2 8. Programming Password Protected .......................................................................................................... 2 9. LED indicator ................................................................................................................................................ 3 10. LCD display ................................................................................................................................................. 3 10.1.The main symbol explanation: ...................................................................................................... 3 10.2.Normal scroll mode (Table 1) .................................................................................................... 4 10.3. Default Display scroll mode ......................................................................................................... 4 11. Communication Port ................................................................................................................................. 5 12. Dis-connect Relay ...................................................................................................................................... 5 13. Wiring Connect ........................................................................................................................................... 5 14. Component Descriptions ......................................................................................................................... 6 15. Meter Outline Size ...................................................................................................................................... 9 16. Default Parameter Setting ........................................................................................................................ 9 Appendix 1: Specification ............................................................................................................................ 10 Appendix 2: Faceplate .................................................................................................................................. 13 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Single Phase Multi-Tariff ANSI Meter Version 1.0.2 1.0.3 1.0.4 1.0.5 1.0.6 Date Used 2013.01.06 2013.02.21 2013.06.17 2013.08.20 2014.03.21 Description of Revision Add New Details Rename Add Link optional Add maxim demand 1. Product Description Socket type, Outdoor Complied with C12.1 C12.10 C12.18 C12.19 C12.20 LCD 6+1 Energy display way, Display instantaneous item:Voltage,Current, Active Power. Communication port: optical port,RS485,RF,and PLC Optional Max 4 rates can be set, default T1 Max Demand display 2 levels of password 12 months History metering data and 50 events of power on/off and meter reset Dis-connect Relay optional The NC30 meter Figure 1-1 NC30 Meter 1 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter 2. Total kWh Register The total kWh is displayed on the LCD by 6 digits with one decimal. The total kWh register range is 000000.0-999999.9 kWh. 3. Meter Memory The history data can store 12 months . The history data include: Accumulative total and max 4 rates of Wh[abs(Wh+) + abs(Wh-)];
Accumulative total Wh-. 4. Event Record The energy meter can record below events with time stamp;total 50 events. Power on. Power off. Reset Energy data. Reset event log. Reset [energy data+event log]. 5. LCD display during power off Three display modes(can be set):
1. Always display Accumulative Wh[abs(Wh+)+abs(Wh-)]. 2. Displaying Accumulative energy for setting time then no display. 3. No Display. Default LCD display during power off is Mode 1. 6. Maxim Demand 1. Record T1 active (abs(Wh+) + abs(Wh-)maxim demand T2 active maxim demand T3active maxim demandT4 active maxim demandand the time of the corresponding maxim demand. 2. Use the slip mode, demand cycle / slip time <=15 min; demand cycle <=60 min, sliding time < =
demand cycle. 3. Demand decimal use 4 digits, 4. Save one historical demand data,and clear the demand data when power energy save auto. 7. Multi-Tariff energy, maximum 4 tariff (TOU) The meter can be up to 4 tariffs per days. And the time interval can be programmed by software. Default Tariff is Single Tariff, T1. 8. Programming Password Protected Meter must first through the password confirmation, then do the programming or other special operations. There are two meter securities. Level 1, for all permissions. 1122334455;
Level 2, Read only permission, 1111111111. 2 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter 9. LED indicator A high light LED is mounted on the front of the meter, it will blink/pulse at a rate proportional to the measured load if the current through the meter more than starting threshold. The pulse value is identified on the meters nameplate. The pulse can be used for checking the meter accuracy. 10. LCD display The meter LCD shows 6+1 digits power consumption in kWh, without backlight. The big size of the digits
(13mm6mm) and clearly identification of display value make meter reader easily to get the data in distance. View direction: 6 o'clock Polarizer mode: Reflective (long life and UV) Operating temperature :- 40C ~ + 80C Storage temperature:- 45C ~ + 85C Figure 9-1 LCD symbol 10.1. The main symbol explanation:
Symbol Explanation LCD display 7 digits;
The energy display as 6+1 digits.(000000.0~999999.9kWh) Display kWh energy value & date and time. Mode 1: Display instantaneous item:Voltage,Current, Active Power. Mode 2: Display data identification(see table 1) Disconnect Relay Display Export/import energy symbol;
Simulation and percentage of energy accumulated comparison to Kh value Communication symbol (display when comm) Program symbol Current running Tariff indication Unit of Instantaneous Voltage, Unit of Instantaneous Current, Unit of Instantaneous Active Power. Unit of energy 3 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Normal scroll mode 10.2. Normal scroll mode (Table 1) No. Data Identification 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 10.3. Default Display scroll mode No Import Energy (Tariff 1+Tariff Display) Import Energy (Tariff 2+Tariff Display) Import Energy (Tariff 3+Tariff Display) Import Energy (Tariff 4+Tariff Display) Import + Export Energy (Tariff 1+Tariff Display) Import + Export Energy (Tariff 2+Tariff Display) Import + Export Energy (Tariff 3+Tariff Display) Import + Export Energy (Tariff 4+Tariff Display) Import Energy (Total) + Voltage Import Energy (Total) + Current(Total) Import Energy (Total) + Current(I1) Import Energy (Total) + Power Import + Export Energy (Total) + Voltage Import + Export Energy (Total) + Current(Total) Import + Export Energy (Total) + Current(I1) Import + Export Energy (Total) + Power Date Time T1 maxim demand T2 maxim demand T3 maxim demand T4 maxim demand T1 maxim demand Date T2 maxim demand Date T3 maxim demand Date T4 maxim demand Date T1 maxim demand Time T2 maxim demand Time T3 maxim demand Time T4 maxim demand Time 0.1.0 0.2.0 0.3.0 0.4.0 0.5.0 0.6.0 0.7.0 0.8.0 0.9.0 1.0.0 1.1.0 1.2.0 1.3.0 1.4.0 1.5.0 1.6.0 1.7.0 1.8.0 2.0.1 2.0.2 2.0.3 2.0.4 2.1.1 2.1.2 2.1.3 2.1.4 2.2.1 2.2.2 2.2.3 2.2.4 Normal scroll mode Status 1 2 Power on Power off Import + Export Energy (Total) + Voltage Import + Export Energy (Total) + Current (I1) Import + Export Energy (Total) + Power Import + Export Energy (Total) +Voltage 4 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter explanation ANSI type 2 with 9600bps Baud Rate 9600 BPS (Optional) Optional (RF915MHZ) Optional 11. Communication Port No 1 Optical port 2 RS485 port 3 RF port 4 PLC port 12. Dis-connect Relay Dis-connect Relay : Optional. 13. Wiring Connect Figure 12-1 3-wire, 1-phase Figure12-2 Internal connect
(FM2S without Dis-connect Relay) (FM2S with Dis-connect Relay) Figure12-3 Internal connect Figure 12-4 2-wire, 1-phase 5 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Figure12-5 Internal connect
(FM2S without Dis-connect Relay)
(
14. Component Descriptions Figure12-6 Internal connect FM1S with Dis-connect Relay) The components descriptions of the meter are shown in Figure 13-1~Figure 13-8. Figure 13-1: Basic NC30 Meter Components FM2S Figure 13-2:Dis-connect Relay NC30(100A) Meter Components FM2S 6 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Figure 13-3:Dis-connect Relay NC30(200A) Meter Components FM2S Figure 13-4: Basic NC30(100A/200,Current Transformer) Meter Components FM1S Figure 13-5: Basic NC30(100A,Shunt) Meter Components FM1S 7 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Figure 13-6: Dis-connect Relay NC30(100A,Shunt) Meter Components FM1S Figure 13-7: Dis-connect Relay NC30(100A,Current Transformer) Meter Components FM1S Figure 13-8: Dis-connect Relay NC30(200A,Current Transformer) Meter Components FM1S 8 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter 15. Meter Outline Size Figure 14 Meter Outline Size 16. Default Parameter Setting l Default Tariff setting: Single rate; T1;
l Display alternation: 5 seconds. l Default LCD display during power off: Accumulative Wh[abs(Wh+)+abs(Wh-)]. l LCD Display during power on: Accumulative Wh[abs(Wh+)+abs(Wh-)]
+Active power/ Voltage/ Current. l Security password:
Level 1: 1122334455;
Level 2: 1111111111. l Meter RTC:
Philippines Time;
l Communication Port :
Optical port l Dis-connect Relay:
NO. l Meter No.: According to the bar code on the meter. 9 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Item ANSI standards complied with C12.1 C12.10 C12.18 C12.19 C12.20 Accuracy Mounting Parameter Appendix 1: Specification Meter type, form designation and current class Operating Voltage Test Current(TA) Current Current range that guarantees accuracy Test Confidence Temperature Communicat ion Port Starting Current Frequency Kh Kt Power supply type Current sampling mode Power Consumption Immunity to impulse voltage Insulation strength Relative humidity Operating Temperature Storage and Transportation Temperature LCD Operating Temperature Clock accuracy Battery Optical port RS485 port RF port PLC port Security Meter security Meet ANSI C12.10 class 0.5 Socket type FM2S, CL200 FM2S, CL100 FM1S, CL200 FM1S, CL100 80%~120%Un (Un=240V/120V) CL200: 30A CL100: 15A CL200: 0.6~200A (2%TA~Imax) CL100: 0.3~100A (2%TA~Imax) CL200: 0.030A (30mA) CL100: 0.015A (15mA) 60Hz5%
10 1.0 Transformer type Current transformer Voltage circuit: <1W, 5VA Current circuit: <0.25VA/Each Surge >8kV(1.2/50US) 4kV,60Hz for 1 min 0%~95% no condensation
- 40C ~ + 80C
- 45C ~ + 85C
- 40C ~ + 80C
< 0.5 s/d, at 23C Li-SOCI2, 3.6V,1200mAh for clock and LCD display during power off. ANSI type 2 with 9600bps Optional Optional Optional 2 levels of password:
Class 1:All permissions. Default:1122334455 10 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Demand Dis-connect Relay LCD Meter data Material Maxim demand 15(100)A 30(200)A LCD layout and characters &
symbols on LCD's meanings LCD size LCD biggest characters' size LCD biggest characters'
segment width LCD with backlight Number of LCD display digits Energy display way Voltage,Current & Active Power Display way LCD display item ID Display interval Display data update rate Sign 'Yes' at 'meter data'
column can be optional displayed on LCD Default LCD display during power on Default LCD display during power off LED Accumulative total and 4 rates of Wh[abs(Wh+)+abs(Wh-)]
Accumulative total and 4 rates of (Wh+) and (Wh-) Instantaneous frequency Instantaneous Voltage,Current,Active Power Current date & time Energy data reset History metering data Event log Single layer of upper cover Upper cover Class 2: Read only permission. Default:1111111111 Maxim demand ;date; time;
Optional
(Please see 9. LCD Display) 54mm x 34mm 13.0mm x6.0mm 1.7mm No 7 6 integers + 1 decimal 3 digits 3 (No ID when display voltage,current,and power ) 5s 1s Yes Accumulative Wh[abs(Wh+)+abs(Wh-)]+RMS Voltage Accumulative Wh[abs(Wh+)+abs(Wh-)]+RMS Current Accumulative Wh[abs(Wh+)+abs(Wh-)]+RMS Power T1 ( Please see 9. LCD Display) Accumulative Wh[abs(Wh+)+abs(Wh-)]
1 LED (Active Energy Pulse),1000imp/kWh Yes Yes Yes Yes Yes Yes 12 months Record latest 50 events (power on,power off,energy reset events with time stamp) Transparent flat face cover Full Circle; Color White 11 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Tariff Faceplate MCU Link Optical port metal plate Number of sealable position Max 4 rates (each rate's period is programmed by software) Default rate setup Faceplate color Faceplate layout New EDMI logo on faceplate Serial number Bar code Outside, inside 430 grade stainless steel,thickness min 1.2 (inner) 1 Yes T1 (Single rate) Color:White Refer to Appendix 2 to be nominated by EDMI to be nominated by EDMI 39 code NEC 78F0485;
optional 12 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter Appendix 2: Faceplate 1 2 3 4 5 6 7 8 9 18 17 16 15 10 11 12 13 14 1. Windows 2. Meter type 3. Number of wires for the metered service 4. Nominal Voltage 5. Current Class 6. Test amperes 7. Nominal Frequency 8. ANSI C12.10 Form Number 9. Watthour constant 10. Accuracy class 11. Meter Constant 12. Optical port 13. Month and Two digit year of manufacture 14. EDMI logo / Manufacture of meter 15. Wiring connect 16. Utility information and bar code area /Meter serial number 17. Test constant 18. Meter Pulse 13 PDF pdfFactory Pro www.fineprint.cn Single Phase Multi-Tariff ANSI Meter 19. FCC Caution. 15.19 Labelling requirements. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. 15.21 Information to user. Any Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. 15.105 Information to the user. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help. 14 PDF pdfFactory Pro www.fineprint.cn