EkkoAir Installation guide Version 1.1 14th August 2019 Critical Things EkkoAir installation guide Copyright Notice All rights reserved. No part of this publication may be reproduced without the expressed written permission of EkkoSense Ltd. EkkoSense Ltd shall not be liable to the purchaser of this product or third parties for damages, losses, costs, or expenses incurred by the purchaser or third parties as a result of accident, misuse or abuse of this product or unauthorised modifications, repairs, or alterations to this product, or failure to strictly comply with EkkoSense Ltd operating and installation instructions. Disclaimer This document is for informational purposes only and is provided as is with no warranties whatsoever. This includes any warranty of merchantability, non-infringement, fitness for any particular purpose, or any warranty arising out of any proposal, specification, or sample. EkkoSense disclaims all liability, including liability for infringement of any proprietary rights, relating to the use of information in this specification. No license, express or implied, to any intellectual property rights is granted herein. Revision history Version Notes V1.0 V1.1 New Add regulatory information EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 2 Critical Things EkkoAir installation guide Contents 1. About this installation guide ...................................................................... 4 2. 3. 4. 5. Fit or replace the battery ........................................................................... 4 Change the EkkoAir settings ...................................................................... 5 Connect the sensors, antenna, CTs and power supply ............................. 8 Install the EkkoAir, sensors, and CTs ....................................................... 10 EkkoAir ............................................................................................................................. 10 Current transformers (CTs) ............................................................................................ 10 Antenna ........................................................................................................................... 11 Sensors ............................................................................................................................ 11 6. Regulatory information ........................................................................... 11 7. Add EkkoAir to EkkoSoft .......................................................................... 12 8. Troubleshooting checklist........................................................................ 15 EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 3 Critical Things EkkoAir installation guide 1. About this installation guide This guide is aimed at EkkoSense installers and explains how to fit and configure the EkkoAir cooling duty sensor. 2. Fit or replace the battery To fit or replace the battery in an EkkoAir you need to remove the front cover. You will also need to remove to configure the EkkoAir. front cover the To remove the cover, use a screwdriver to press in the tabs on the side and gently slide the front off. The battery connection is in the front and is wired to the circuit board in the back of the EkkoAir, so take care when removing front. the The EkkoAir uses a Lithium Thionyl Chloride AA 3.6V battery that fits into the rear of the cover. Only use Tadiran SL760/S or SAFT LS14500 batteries. Make sure that the polarity of the battery matches the + and symbols shown next to the battery clips for the battery connection. The cables that connect the battery panel to the circuit board should be connected so that black
(negative) is the top connection and red (positive) is the bottom connection, as shown in the image here. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 4 Critical Things EkkoAir installation guide 3. Change the EkkoAir settings This part of the installation only applies if you need to change the settings of the EkkoAir. It is designed to work with the default settings in place, but you may need to change settings to meet the requirements for the site. 1. Remove the cover of the EkkoAir unit. For instructions on removing the cover, see Fit or replace the battery on page 4. 2. Connect the USB TTL serial cable to the UART connection in the EkkoAir. It is the 6 pin connection on the left side of the circuit board. Note: Connect the cable so that the green wire at the top, then yellow, orange, red, brown, with black at the bottom. Please check the text on the PCB if you are unsure. The EkkoAir will be unable to connect to a computer if the USB TTL cable is connected in any other way. 3. Connect the USB TTL serial cable to your computer. If this is the first time you have connected an EkkoAir to your computer, Windows will detect the USB TTL serial cable and set it up automatically. This can take a few minutes. Windows provides a notification when the setup is complete. 4. Run the EkkoAirConfiguration.exe file. If Windows Defender protects your PC, select the More info link and then select Run anyway. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 5 Critical Things EkkoAir installation guide 5. When the EkkoAir Configuration Tool app runs, select the:
Communication port that is used for the USB TTL serial connection. Typically, there is only one port shown. Record configuration option if you want the app to record a log of the configuration changes you make. If you enable this feature, a File field appears, which you can use to choose the location for the log file. Connect button to connect to the EkkoAir. When you select Connect, the EkkoAir Configuration Tool should connect to the EkkoAir. At this point, the settings in the bottom section of the window will become available and you will see connected in the bottom right. If the EkkoAir Configuration Tool cannot connect, the bottom section will remain unavailable for use. In this situation, try:
Selecting a different COM port. If there are multiple COM ports available, you may have selected the wrong one. Checking that the USB TTL serial cable is connected correctly (see step 3 on page 5). If you are unable to get the EkkoAir to connect, try using a different EkkoAir unit. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 6 Critical Things EkkoAir installation guide 6. Use the EkkoAir Configuration Tool to change the settings to meet the site requirements. Setting Description Serial number The serial number of the device. This cannot be changed. Key Leave blank to use the default key or enter a new key of exactly 32 hexadecimal characters (0 to F). You can also Load a .txt file that contains a key. If you add a new key manually, we recommend that you Save the key as a .txt file. You can then load the key file on to the other EkkoSense devices in your network. They can only communicate if they all use the same key. Average Count Use to define how many measurements the EkkoAir will use to calculate the average. For example, if you set the Average Count to 2, the EkkoAir will use two measurements to calculate the average. It then reports the average at the Transmit Interval time. Set this to match the rating of the current transformers (CT) that are going to be used to monitor the power supply (10A is standard for EkkoAir). Use to control how often the EkkoAir transmits data to the EkkoHub. You can choose 1, 2, or 5 minute intervals. Check this box if you want the EkkoAir to monitor humidity as well as temperature. Clear the box for temperature monitoring only. Check this box if you are going to install multiple CTs for the EkkoAir. Clear the box if you are only installing one CT. CT Rating Transmit Interval Measure Humidity Phase 3 Current Measurement Note: Standard mode is the default. An Installer mode is available by checking the box next to Standard Version and entering a password. You should only use this setting under the guidance of EkkoSense technical support. 7. Select Update configuration to apply the changes. 8. Select Disconnect, and then disconnect the USB TTL serial cable and refit the EkkoAir cover. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 7 Critical Things EkkoAir installation guide 4. Connect the sensors, antenna, CTs and power supply Connect the sensors, antenna, CT(s), and any external power supply and inputs as shown below:
Diagram Description 1 Return sensor 2 Supply sensor Connections DA Yellow
-
+
Green Brown CL White DA Yellow
-
+
Green Brown CL White EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 8 Diagram Description Connections Critical Things EkkoAir installation guide 3 4, 5, 6 External input 12V-24V (optional). Can be any binary input, typically a status input. 0.333V Current 10A Typically one CT, but can be 2 or 3. Transformers
(CTs). Plain Black Dot White 7 External antenna. Use a wired Siretta ALPHA14/2.5M/SMAM/S/S/26 antenna If EkkoAir is to be installed inside an AHU. Use a stubby Siretta DELTA2A/X/SMAM/S/RA/11 antenna if the EkkoAir is to be installed in a separate box. Serial number and QR code for EkkoAir unit. External power source (optional). The EkkoAir can be powered by its internal battery or can be wired to an external power source. 8 9 G
+12 to +24V DC or 12 to 24V AC (50Hz or 60Hz) G0 0V For the optional external power source, connect as shown below:
The current drawn by the EkkoAir is less than 0.1A. Any external power source must include a current limiting device to limit available power to less than 100W. For example, on a 12V supply a fuse rated 8A or less, on a 24V supply a fuse rated 4A or less. The AC supply can be 50Hz or 60Hz. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 9 5. Install the EkkoAir, sensors, and CTs Critical Things EkkoAir installation guide Note: Do not extend the sensor cables. EkkoAir Fit the EkkoAir to a DIN rail in AHU. If there is not enough space in the AHU, fit a box with DIN rail next to the AHU, and then fit the EkkoAir in the box. Where possible, fit the EkkoAir so that it is possible to remove the front cover without having to remove the EkkoAir from the DIN rail. Current transformers (CTs) Fit the CT(s) around the power supply cable to the fan being monitored. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 10 Critical Things EkkoAir installation guide Antenna If you are installing a wired Siretta ALPHA14/2.5M/SMAM/S/S/26 antenna, you should fix it in place outside the AHU. It has a self-adhesive pad that you can fix to metal or non-metal surfaces. Sensors On the front of each EkkoAir sensor is a label that shows whether the sensor is a supply sensor or a return sensor. Fit the supply sensor so that the front of the sensor is in the supply (intake) airflow. Fit the return sensor so that the front of the sensor is in the return (exhaust) airflow. Use self-tapping screws or loop cable ties to secure the sensors to the strut. 6. Regulatory information The EkkoAir must be professionally installed. The EkkoAir is only approved for use with a wired Siretta ALPHA14/2.5M/SMAM/S/S/26 antenna (2.5m cable) or directly connected Siretta DELTA2A/X/SMAM/S/RA/11 antenna. Use of other antennas is not permitted and invalidates the radio regulatory approval. Any changes or modifications not expressly approved by the party responsible for compliance could void the users authority to operate the equipment. This FS-EA-10 device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) this device must accept any interference received, including interference that may cause undesired operation. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 11 Critical Things EkkoAir installation guide 7. Add EkkoAir to EkkoSoft When you have installed a sensor, you need to add it to the Ekkosoft software so that it can be monitored. There are two ways to add a sensor to EkkoSoft. You can either use a 2D barcode scanner to scan the sensors QR code or you can enter the scanners ID manually. 1. Login to EkkoSoft on a laptop (internet connection required). 2. Select the data centre. 3. Select Visit Room. 4. Select Editor mode. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 12 Critical Things EkkoAir installation guide 5. Select the ACU that the EkkoAir is fitted to. 6. Expand the EkkoAir settings. 7. Select the Sensor ID field. 8. Connect a 2D barcode scanner to your laptop (via USB) and scan the EkkoAirs QR code. The QR code is on the label next to the antenna connection at the bottom of the EkkoAir. If you do not have a 2D barcode scanner, you can enter the EkkoAirs ID manually. When you scan the QR code, the EkkoAirs ID code is automatically copied from the 2D barcode reader into the Sensor ID field (as long as the Sensor ID field is selected). 9. Add the configuration details:
Setting Voltage Description Set to match the voltage of the fan, as defined in the fan specification. Total Fans Set to match the total number of supply fans in the ACU. Fans Monitored Set to the number of fans that have their power supply monitored by the EkkoAirs CTs. Phases Per Fan Set this to match the phases that are defined in the fan specification. Nominal Power Fan Set to match the total amount of power required by the fan when running at 100%. This in the fan specification. information included is EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 13 Critical Things EkkoAir installation guide 10. When the you have configured the EkkoAir, check that it is set up correctly. In EkkoSoft, view the room in Viewer mode and look at the values for the ACU. The EkkoAir entry should show an airflow reading. Note: There may be a delay of several minutes before the readings from the EkkoAir are shown in EkkoSoft for the first time. This is because EkkoAir is designed to send data every 2 minutes (default) and EkkoSoft acquires data periodically. 11. Repeat this process for each EkkoAir. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 14 Critical Things EkkoAir installation guide 8. Troubleshooting checklist In the unlikely event that you experience problems with the EkkoAir, please check:
The battery is fitted correctly or the external power supply is present If the battery is used then check that the connection from the battery board to the main circuit board is fitted correctly The supply and return sensors are wired to the appropriate terminals and with the correct colours to each terminal The front side (the side with the label) of the sensors is in the airflow The CTs are connected to the appropriate terminals and are installed around the cables. power AC You should also use the EkkoAir Configuration Tool to check:
The EkkoAir is used the same key as the other EkkoSense products in the network The CT rating is correct, and the 3 Phase Current Measurement setting is enabled if there is more than one CT Measure Humidity is enabled if humidity monitoring is required. If these conditions and settings are all in place, contact EkkoSense support. You may need to install a different EkkoAir unit. EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW 15 EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln, LN1 1XW