Litenode wireless node Single load RME-GEN Installation instructions IL42-5047A Description Part of the DimOnOff wireless control technology, Litenode relays are suitable for general purpose lighting control applications that add intelligent functions and networkability to any light fixture. The relay provides continuous retroactive 0 V to 10 V (sink/source) for all types of ballasts and drivers and provide power to external sensors (optional).
intelligent distributed control, metering, and monitoring
NEMA C136-41
5- and 7-pin with continuous retroactive 0 V to 10 V dimming Operation Unless otherwise programmed, the relay will turn on the fixture approximately 10 seconds after power is restored to the relay. The yellow LED will blink when power is properly applied. Using DimOnOff software, test the communications link with the relay. Before you install
This device is to be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult a qualified electrician.
Use this device only with NEMA C136-41 or C136-10 certified receptacles. Use authorized utility procedures to install or service this device. Dangerous voltages are present. Disconnect power at the circuit breaker or fuse when servicing, installing, or removing the light fixture. Equipment damage, personal injury, or death may result if safety precautions are not followed. DRAFT Litenode wireless node 2 Installation Use authorized utility procedures to install or service this device. Dangerous voltages are present. Disconnect power at the circuit breaker or fuse when servicing, installing, or removing the light fixture. Equipment damage, personal injury, or death may result if safety precautions are not followed. If you are uncertain about any part of these instructions, consult a qualified electrician. The node input and output are low voltage (24 VDC). Consult local building codes and regulations for information regarding low-voltage installation. 1 To avoid fire, shock, or death, be sure to turn off power at the circuit breaker or fuse. Verify that power is off before proceeding. 2 Connect lead wires according to the wiring diagram as follows:
- Line voltage wiring: Remove 5/8-inch (1.6 cm) of insulation from each circuit conductor. Make sure that the ends of the conductors are straight. Connect lead wires from relay to line per the appropriate wiring diagram as follows. Twist strands of each lead tightly and, with circuit conductors, push firmly into the appropriate wire connector. Screw connectors on clockwise making sure that no bare conductor shows below the wiring connectors. Secure each connector with electrical tape.
- Class II warning: Connect low-voltage wires from relay to fixture per appropriate wiring diagram as follows. Twist strands of each lead tightly, and with circuit conductors, push firmly into appropriate wire connector. Screw connectors on clockwise, making sure that no bare conductor shows below the wire connectors. Make sure to cap-off unused low-voltage wires. Secure each connector with electrical tape. 3 Restore power at circuit breaker or fuse. RME-GEN wiring Line wires on C-136 socket supplied by others Line in Neutral/line 2 Line out Color Black White Red DC control wires on C-136 socket supplied by others 0 V to 10 V+ out 0 V to 10 V- ground out Digital in 13 VDC to 30 VDC VCC 24 VDC 50 mA Purple Gray Orange Brown Gauge 14 14 14 18 18 18 18 DRAFT Litenode wireless node 3 Antenna location and installation The antenna for the model ELIR1 Lightnode relay is integral to the unit and is contained wholly within the device itself. It is not accessible to the user and may not be modified in any way. To satisfy FCC RF exposure requirements for mobile transmitting devices, a separation of 20 cm or more should be maintained between the antenna of this device and persons during device operation. To ensure compliance, operations at closer distance than 20 cm is not recommended. Troubleshooting General
Make sure the wires are connected according to the wiring diagram.
Make sure the wires have proper contact and are securely connected.
If no LEDs are lit, then check the power. Lights wont turn on when relay is being powered:
Make sure the wires are properly connected.
Make sure the yellow LED is blinking. Light wont turn off after command has been sent:
Make sure that relay is receiving communication (red LED blinks) Relay doesnt respond to commands:
Make sure no obstacle (concrete, metal, etc.) is present between relay antenna and the emitter. LED indicators:
Yellow: blinks every 3 seconds to indicate that relay is powered and functioning normally
Red: flashes to indicate message reception
Green: flashes to indicate message transmission by the relay. If there is no message reception/transmission, then possible causes are antenna positioning and distance from another relay or the gateway. Specifications
Model: ELIR1
IC: 4557A-ELIR1
FCC ID: QZC-ELIR1
Operating range: 110 VAC to 480 VAC 50 Hz or 60 Hz
Max output: 8 A (2 A at 480 V)
Inputs: 1 digital (0 VDC to 30 VDC), optional
Output: 24 VDC 50 mA max
Continuous retroactive 0 V to 10 V dimming See the product data sheet for complete details DRAFT Litenode wireless node 4 WARNING (PART 15.21) Changes or modifications not expressly approved by Elster could void the user's authority to operate the equipment. This device complies with Part 15 of FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. COMPLIANCE STATEMENT (FCC PART 15.19 AND INDUSTRY CANADA) This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. NONC DE CONFORMIT Le prsent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorise aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radiolectrique subi, mme si le brouillage est susceptible d'en compromettre le fonctionnement. LiteNode is a trademark and/or registered trademark of DimOnOff Installation information obtained from DimOnOff and is used by permission of DimOnOff. DISCLAIMER OF WARRANTIES AND LIMITATIONS OF LIABILITY There are no understandings, agreements, representations, or warranties either express or implied, including warranties of merchantability or fitness for a particular purpose, other than those specifically set out by any existing contract between the parties. Any such contract states the entire obligation of the seller. The contents of this document shall not become part of or modify any prior existing agreement, commitment, or relationship. The information, recommendations, descriptions, and safety notices in this document are based on Elster Solutions, LLC experience and judgment with respect to operation and maintenance of the described product. This information should not be considered as all-inclusive or covering all contingencies. If further information is required, Elster Solutions, LLC should be consulted. No warranties, either expressed or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising from the course of dealing or usage of trade, are made regarding the information, recommendations, descriptions, warnings, and cautions contained herein. In no event will Elster Solutions, LLC be responsible to the user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to: damage or loss of use of equipment, cost of capital, loss of profits or revenues, or claims against the user by its customers resulting from the use of the information, recommendations, descriptions, and safety notices contained herein. 2016 by Elster. All rights reserved. Produced in the United States. Elster Solutions Raleigh, North Carolina Technical support: 800 338 5251 DRAFT