Key Features:
Intelligent Electronic swing handle User operations guide PDU Version handle User Operations Guide
. Local Status monitoring via Integrated Multi-colour LED indicator Manual over-ride lock for emergency access (with scalable levels of security) Retro-fittable to existing IT cabinets, industry standard 25x150mmpanel cut-out Compatible with single and multiple point latching External Door contact sensor Complete with Centralised Rack Access Management (RAM) Software for configuration, management, Integrated electronics and environmental sensors (temperature and humidity) Inbuilt Multi-card reader - 125kHz and 13.56MHz Simple one cable connection for power and communication monitoring and reporting Rev.1.0 1 Key dimensions:
Intelligent Electronic swing handle User operations guide MOTOR MODEL ELECTRICAL SPECIFICATION:
-POWER 4.5V TO 5V
- OPERATON CURRENT: LESS THAN 500mA AT 5V DC WITH NO EXTERNAL MECHANICAL LOAD APPLIED TO HANDLE.
- MAX CURENT WITH STALLED ACTUATOR: 1A AT 5V DC.
- STANDBY CURRENT: 300mA, TYPICAL. CONTROL INPUT:
-RJ485 5V DEVICE
-BAUD RATE:19200 BPS Environmental and Performance:
> Operating temperature: -15C to +60C (5F to 140F)
> Survival temperature: -30C to +85C (-10F to +185F)
> Humidity (operating): 95% RH at 50C (122F) Rev.1.0 2 FCC COMPLIANCE / TM / WARRANTY FCC ID:2AYS5DRLCKHIDP Intelligent Electronic swing handle User operations guide To satisfy FCC RF exposure requirements, a separation distance of 20cm or more should be maintained between the antenna of this device and persons during device operation. To ensure compliance, operations at closer than this distance is not recommended. Les antennes installes doivent tre situes de facon ce que la population ne puisse y tre expose une distance de moin de 20 cm. Installer les antennes de facon ce que le personnel ne puisse approcher 20 cm ou moins de la position centrale de l antenne. This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Le prsent appareil est conforme. Lexploitation est autorise aux deux conditions suivantes : (1) lappareil ne doit pas produirede brouillage, et (2) lutilisateur de lappareil doit accepter tout brouillage radiolectrique subi, mme sile brouillage est susceptible den compromettre le fonctionnement. Changes or modifications not expressly approved by the party responsible for compliance could void the users authority to operate the equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Rev.1.0 3 Intelligent Electronic swing handle User operations guide Safety Instructions Please refer to the below instructions before using the Ihandle. Save this manual for future reference. If cleaning The Ihandle is required. Dont use liquid or spray detergent; use a moist cloth. Install and operate the Ihandle Preferably, in an air-conditioned environment with When installing, place the equipment on a sturdy, level surface to prevent it from accidentally falling and temperatures not exceeding 50 Celsius (122 Fahrenheit). causing damage to other equipment or injury to persons nearby. Install the Ihandles Communication and door contact cables in such a way that others wont trip or fall Keep all liquids away from the equipment to minimize the risk of accidental spillage. Liquid spilled on to over it. the Ihandle may cause damage. equipment and invalidate the warranty. service personnel Only qualified service personnel should open the chassis. Opening it yourself could damage the If any part of the equipment becomes damaged or stops functioning, have it checked by qualified Take care when the swing handle is in the open position, to avoid personal injury or damage to the swing handle body. DO NOT use excessive force to open the swing handle and always fully open the swinghandle by gently opening in an upwards position. Once fully in the upwards position turn the handle either left or right based on the position of the rotation limiter. Failure to operate the handle correctly can lead to damage to the handle body. Standard warranty 2 years repair or replace. See exclusions below Damage, deterioration or malfunction resulting from:
Accident, misuse, neglect, fire, water, lightning, or other acts of nature, unauthorized product modification, or failure to follow instructions supplied with the product. Repair or attempted repair by anyone not authorized persons. Any damage of the product due to shipment. Removal or installation of the product. Causes external to the product, such as electric power fluctuations or failure. Use of third-party parts not meeting our specifications. Normal wear and tear. Any other causes which do not relate to a product defect. Rev.1.0 4 Standard supplied Inventory * can be modified to suit specific requirements Intelligent Electronic swing handle User operations guide PDU Version Smart-Handle Kit:
The Smart-Handle Kit comprises the following:
Quantity 1pcs Quantity 1pcs Quantity 1pcs Quantity 1pcs Quantity 2pcs Quantity 5pcs Quantity 1pcs Quantity 1pcs Quantity 1pcs Quantity 1pcs Quantity 2pcs Intelligent swing handle 2m communications cable female rj45 to 4pin JST connector 1.2m Door switch sensors to 5 pin JST connector with 2 magnets 2.5m Cat6 Blue network cable Double sided tape Cable tie Metal bracket back cover and 3 fixing screw Cable protection covers Thin rotation limiter * thick rotation limiter installed on ihandle as standard Spring screws to affix cam to rotation limiter Euro profile lock barrel keys Smart Handle QTY (1) 1.2m door switch sensor kit QTY (1) 2m daisy chain Cable 4 pin JST to RJ45 QTY (1) Rev.1.0 5 Intelligent Electronic swing handle User operations guide Network Cable 2.5m QTY (1) Double-sided tape Cable Tie QTY (2) QTY (5) Key QTY (2) Metal bracket back cover (1) fixing screw (3) Cable Protect Cover (1) Thin Rotation limiter (1) Spring screw
(1) Optional extras. Rev.1.0 6 Installation:
Door cams Multi latching rod system gearbox Intelligent Electronic swing handle User operations guide Check the cut-out dimensions. For retrofit, remove the existing rack handles and check the cut-out dimensions
(see picture below for typical front door and rear door). Keep the cam from the existing handles (used in Step 4). Note: The Smart-Handle can be retrofitted on racks subject to the door having a cut-out dimensions 125mmx50mm. Rev.1.0 7 Intelligent Electronic swing handle User operations guide 1. Typical door Typical door 2. Push the Smart-Handle through the cut-out in the door. Rev.1.0 8 Intelligent Electronic swing handle User operations guide 3. Put the metal back cover on the inside of the handle and insert the 3 screws to secure the handle in place, alternate between the screws while tightening to prevent skewing of the handle. 4. Place the door cam over the handle spindle and then a thick or thin door limiter using the spring screw to secure the mechanism. (For retrofit, re-use the front and rear door cam). Check the cam closes snuggly when the handle is rotated. Swap the door limiters or slightly bend the cam if the cam hits the rack frame. Rev.1.0 9 5. Repeat the procedure for the second door. Intelligent Electronic swing handle User operations guide Network connection:
Front Door 1. Connect the Smart-handle Comms Cable 4 pin to RJ45 150mm cable to the iHandle and attach the Blue Network Cable to the RJ45 connector. 2. Connect the RJ45 coupler and Blue Network Extension Cable to the Blue Network Cable. 3. Route and fix the network cable using cable ties and adhesive pads. Ensure the network cable has slack on the hinge side of the door so that it does not get pinched. Ensure the RJ45 coupler is positioned near the hinge to enable the network cable to be disconnected and allow the easy removal of the door (if required). 4. Install the Cable Protect Cover by placing it over the back of the Smart-handle and sliding the Cable Protect Cover up. 5. Connect the blue Network cable to the RJ45 Sensor Port on either the IPDU, in-line meter or sensor POD. The Smart-handle LED light should now be illuminated. Rev.1.0 10 Intelligent Electronic swing handle User operations guide Rear Door 1. The network connection for the rear door is the same as the front door. 2. Ensure the network cable has slack on the hinge side of the door so that it does not get pinched. 3. Connect the RED Network cable to the RJ45 Sensor Port on either the IPDU or sensor POD Door Switch Sensor 1. The Door Switch Sensor consists of two parts:
1.2m cable to 5pin connector with Door switch sensor Magnet 2. Plug the 5pin connector into the back of the Smart-handle. 3. Route and attach the 1.2m cable to the inside of the door and attach the switch sensor to the door using a dual adhesive pad or screws. In most instances the best location is near the top of the door on the handle side. 4. Close the door and locate the position on the frame inside the rack that corresponds to the location of the switch sensor. pad or M3 tapping screws. 5. Open the door and attach the Magnet to the frame in the location identified using a dual adhesive Rev.1.0 11 6. The magnet and switch sensor must come into contact when the door is closed for the sensor to determine door closed status. Intelligent Electronic swing handle User operations guide Lock:
1. The Euro profile lock barrel can be replaced with an alternate lock barrel either before or after the handle is installed. 2. Removing the lock retaining screw. 4. Re-install the lock retaining screw. 3. Slide the lock cylinder barrel out of the Smart-handle and replace it with the alternate barrel. Note: The lock barrels supplied by Logical Infrastructure are designed specifically for use with the Smart-
handle. Other lock barrels may result in reduced Smart-handle functionality. Environmental Sensors:
1. The Smart-handle has an internal temperature and humidity sensor. 2. One additional environmental sensor (not supplied in the Smart-handle kit) can be attached to the spare port on the Smart-handle. Configuration:
1. The front door of a rack is referred to as the cold aisle and the rear door as the hot aisle. 2. After fitting the Smart-handle ensure that the dip switch is correctly selected for hot aisle or cold aisle appropriate to the rack orientation. Rev.1.0 12 Intelligent Electronic swing handle User operations guide Rev.1.0 13 LED light status:
Intelligent Electronic swing handle User operations guide LATCH & LED colour STATUS definitions SECURED SOLID GREEN ELECTRONICALLY RELEASED BLINKING GREEN UNAUTHORISED CARD SWIPE BLINKING MECHANICALLY RELEASED WITH KEY BLINKING RED ELECTRONICALLY LOCKED/SWINGHANDLE OPEN BLINKING DOOR CONTACT OPEN FOR 5 MINUTES BLINKING RED/BLUE ERROR DETECTED SOLID RED
/RED Rev.1.0 14 Operate with PDU 1.Setup:
Intelligent Electronic swing handle User operations guide The Smart-handle can be connected to PDU before or after PDU power up, it usually take 10 to 50 seconds for the Smart-handle detected by PDU, once the Smart-handle detected, the sensor handle, keyed lock and relevant information can be found from PDUs local display, web GUI or snmp interface. Local Display: Select menu item sensor, use scroll button to view all connected sensors SNMP refer to PDU snmp description Web GUI:
Once the Smart-handle detected, login to PDUs web GUI, handle lock and door switch status will be shown at home page under Security tag:
Handle built-in temperature and humidity sensor will be shown under Environmental tag Setup handle:
Handle related configuration interface can be invoked from setting -> Rack Access Control menu Rev.1.0 15 Intelligent Electronic swing handle User operations guide Rack Access Control page allows PDU user to perform following configuration:
o Authorize an rf id card user o Lock/Unlock the handle o Change the auto lock time o All above configure are under the Action Button as following Authorize rf id card user An ID card user need to be defined given card ID and user name. The card ID is the property of a HID card or Mifare card, which is different as the number printed on the card in most of the cases, to get the card ID, present the card in front of the read area on the handle, the handle led will blink orange, and then Rev.1.0 16 Intelligent Electronic swing handle User operations guide check the event log of the PDU(it takes about 30 seconds for the PDU to pull the latest event from Handle), the log should include item like following:
Take the ID from event log, and put into the new user creation pag ( From Action -> New) The username can be in any test just for memories , select the correct PDU number and Aisle from drop-down selector, click create, the ID card will be authorized to lock/unlock the handle, all authorized card ID and username can be found at the main page of Rack Access Control Rev.1.0 17 Intelligent Electronic swing handle User operations guide Lock/Unlock the handle Lock/Unlock page gives PDU user to performan lock unlock without access the handle with a ID card Rev.1.0 18 Change the auto lock time The handle come with the auto lock function, if the the lock is open for 3 minutes in default, it will automatically close it. The default auto lock time can be changed in the Change the auto lock time page Intelligent Electronic swing handle User operations guide The auto lock time can be configured between 3-30 minitues. Operate with PoE Handle Please refer to PoE handle user manual Rev.1.0 19 FAQ:
Intelligent Electronic swing handle User operations guide What if the smart-Handle fails how do I access my IT cabinet? Use the override key provide to manually open the swing handle. Does the smart-Handle fail safe if power is lost or the communications cable is disconnected? Yes, the smart-Handle will stay in the locked position and when powered up again will automatically check that latch is in the locker position Is the smart-Handle self-latching? Yes, as long as the key barrel is in the 12 oclock lock position and the electronic latch in the lock position once the swinghandle is closed, the latch will allow the key cam to push up the latch and the spring action will drive the latch back down. Can I use my own Euro profile lock barrel? Yes, if the barrel is a standard Euro profile. My current multi point rode systems gear box does not fit the smart-Handle where can I get a gearbox that works with my multi point rod system? We can design a compatible gearbox as an optional extra. Please contact with our sales. Im trying to use my internal companies swipe card and it isnt working why? Your companies swipe cards may be encrypted to your building management system card readers. The smart-Handle requires an open sector on your card in order to read the CSN number. Ive connected my smart-Handle to my building management system but its not working why? The smart-
Handle uses the RS485 protocol and only approved vendor hardware is supported by our Firmware. Please contact with our sales to discuss your requirements. Ive lost some parts, can I buy spares. Yes, please contact with our sales and we will get in contact with you regarding your requirement. Can you integrate with third party access control systems? Yes and No it depends on the communication protocol being used by the third-party system and whether the third party vendor is open to integrating the smart-Handle into their system, please contact with our sales to discuss in more detail. How accurate is the supplied temperature and humidity sensor? The sensors are accurate up to 2 degrees and 5% humidity and have been calibrated to react slowly to changes to avoid large swings in temperature and humidity when the door is opened and closed for short periods of time. This setup is designed to give the user stable readings and avoid unnecessary threshold alarms. Trouble shooting:
The LED light on my smart-Handle has not turned on. Make sure the communications cable is plugged into the correct port on the smart-Handle. My smart-Handle has a flashing blue/red LED. Make sure the supplied door switch sensor is connected to the smart-Handle and that the magnet has been installed correctly. The aisle setting on my smart-Handle is not correct and Ive switched it into the correct position, but the aisle detail has not changed. Power down the smart-Handle by disconnecting the communications cable make sure the dip switch is in the desired position and re-power up the smart-Handle and allow the smart-
Handle to reboot and sync, this should resolve the issue. Rev.1.0 20