EVOGate 2.0 with RTU+Server2 Installation Manual Serial Number Document Code EMNL000057_01_EN EVOGate 2.0 Copyright EnergyICT n.v. Copyright 2011 by EnergyICT n.v. All rights reserved. The information in this document is subject to change without notice and does not represent a commitment on the part of EnergyICT. The software described in this document is furnished under a license agreement, and may be used or copied only in accordance with the terms of that agreement. No part of this document may be reproduced, transmitted, transcribed, stored in any retrieval system, or translated into any language by any means, electronic or mechanical, including photocopying and recording, for any purpose other than the licensee's personal use without the express written permission of EnergyICT. In no event will EnergyICT be responsible for any damages, including any lost profits, lost savings or other incidental or consequential damages arising out of the use of this product. Disclaimer The information contained in this message (including any attachments) is confidential and intended solely for the attention and use of the named addressee(s). It must not be disclosed to any person without our authority. If you are not the intended recipient, please delete it from your system immediately - any disclosure, copying or distribution thereof or any action taken or omitted to be taken in reliance thereon is prohibited and may be unlawful. 2 / 29 Table of contents Safety Precautions ........................................................................................................................................4 Notice on Interference ..................................................................................................................................5 Chapter 1: Introduction ........................................................................................................ 6 About the EVOGate 2.0 .................................................................................................................................7 EVOGate 2.0 Component Overview ...............................................................................................................8 Technical Specifications ..............................................................................................................................10 RTU+Server2 Casing...................................................................................................................................11 IP Enclosure Casing ....................................................................................................................................12 RTU+Server2 Labels ...................................................................................................................................14 IP Enclosure Labels.....................................................................................................................................16 LED Indications...........................................................................................................................................19 Chapter 2: Mounting and Wiring......................................................................................... 20 Mounting Instructions IP Enclosure .............................................................................................................21 Power Supply Wiring Safety Guidelines........................................................................................................21 Power Supply Wiring Instructions EVOGate 2.0............................................................................................22 Power Supply Wiring RTU+Server2 .............................................................................................................23 Chapter 3: Communication Interfaces................................................................................ 24 Overview Communication Interfaces............................................................................................................25 Double Ethernet Connection........................................................................................................................26 Double USB 2.0 Host Connection.................................................................................................................26 GSM/GPRS Modem......................................................................................................................................27 Wavenis RF Modem ....................................................................................................................................28 Appendix ............................................................................................................................. 29 3 / 29 Safety Precautions Precautions The EVOGate 2.0 with RTU+ Server2 has been designed and tested with US norms and has left the factory in a safe condition. The present installation manual contains important information and warnings which have to be followed by the user to ensure safe operation and to retain the unit in safe condition. Interventions Any interventions to the EVOGate 2.0 with RTU+ Server2 must be done by technical service staff only. Note
+ Changes or modifications not expressly approved by the responsible party for compliance (EnergyICT) could void the user's authority to operate the equipment. Clock The device contains a real-time clock with 6 day autonomy in case of absence of power. WARNING!
When activating the Wavenis modem, an RF antenna must already be connected to the EVOGate 2.0! The absence of an antenna during activation will cause irreparable damage to the modem. Consult Wavenis RF Modem on page 27 for more information. 4 / 29 Notice on Interference FCC Class B digital device The EVOGate 2.0 complies with Part 15 of the FCC Rules / Industry Canada license-
exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class B digital apparatus complies with Canadian ICES-003. Use of radio frequency energy This device generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. Preventing interference If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
+ Reorient or relocate the receiving antenna
+ Increase the distance between the equipment and the receiver
+ Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
+ Consult the dealer or an experienced radio/TV technician for help. Notice on Industry Canada (IC) certification Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication. This radio transmitter (IC: 9864A-RTUS2WC) has been approved by Industry Canada to operate with the antenna types listed below with the maximum permissible gain and required antenna impedance for each antenna type indicated. Antenna types not included in this list, having a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with this device Antenna type used for certification measurements : Antenex FG9026 Antenna specs:
Frequency range : 902 928 MHz
VSWR : < 1.5:1 Max
- Nominal Gain : 6 dBd
- Nominal impedance : 50 Ohm
Polarization : vertical 5 / 29 Chapter 1: Introduction Introduction Chapter description This chapter provides the user with an introduction to the EVOGate 2.0, its main internal components (including EnergyICTs RTU+ Server2 data concentrator) and its main functions. This chapter describes the following topics:
Topic About the EVOGate 2.0 EVOGate 2.0 Component Overview Technical Specifications RTU+Server2 Casing IP Enclosure Casing RTU+Server2 Labels IP Enclosure Labels LED Indications Page
[7]
[8]
[10]
[11]
[12]
[14]
[16]
[18]
6 / 29 About the EVOGate 2.0 Description The EVOGate 2.0 is positioned as the generic ODM Water solution for utility applications in the United States. EVOGate 2.0s main component is the RTU+ Server2 concentrator; which is built around a core feature set and is provided with a robust casing. The RTU+ Server2 is installed inside the EVOGate 2.0s IP enclosure resisting easily to any industrial environment. The RTU+ Server2 also offers unprecedented upstream and downstream flexibility and splits expensive communication over multiple endpoints, allowing utilities to optimize the implementation of various AMI technologies. Main functions The table below lists the main functions of the RTU+ Server2:
Function Description Data is collected and stored per definable interval period; the device is able to store a virtually unlimited amount of data, depending on its memory capacity. For more information on memory capacity, see Technical Specifications on page 10. Pulse data is collected via the digital inputs and meter data is collected via the standard serial interface or via an optional communication interface. The RTU+ Server2 can transfer data to EnergyICTs advanced EIServer meter data management solution using the EIWebp+ push protocol, via its Ethernet ports, or via an optional communication interface. has Server2 capability and embedded network The RTU+
management serves as master concentrator in a Wavenis RF network, with multiple Wavenis endpoints acting as slaves. For more information, see Wavenis RF Modem on page 27. Data collection Data transfer Fixed network management and remote monitoring 7 / 29 EVOGate 2.0 Component Overview Overview Listed below are EVOGate 2.0s main components. The EVOGate 2.0 entails all components described here at purchase, except for the Wavenis antenna (and coax cable) which need to be purchased separately. Consult the Appendix for more information. 8 / 29 Description Component Type 1. GSM Antenna CANT000021 2. IP Polyester enclosure Schneider Electric NSYPLM43 3. N-to-N Surge protection Phoenix contact 2818148 4. Data concentrator 5. Net Filter 6. Surge Protector 7. Automatic Fuse 8. Battery DIN Rail mounted RTU+Server2 DIN Rail mounted Phoenix contact 2788977 DIN Rail mounted Phoenix contact 2856812 DIN Rail mounted Phoenix contact 0916608 CBAT000003 Important!
Battery may need to be installed by the customer (application dependent). 9 / 29 Technical Specifications Feature HOUSING Implementation IP Enclosure Housing Protection:
IP 66 POWER BATTERY Type NSYPLM43 (See p. 12 for more technical characteristics) Internal RTU+Server2 Housing:
Plastic enclosure 183 * 174 * 62 mm. (including optional connector cover) Material: PC ABS (UL94 5VA compliant) Fixation: DIN Rail connection Universal Power Supply: 100 VAC - 230 VAC Internal Lithium ion battery pack, based on GP Battery Swing 4400 Cells Usage: UPS functionality. o When main power is cut, unit survives for maximum 6 days. Discharge temp: -40 C - +65C Charge temp: -10C - +60C Voltage: 7,4V / 12Ah Fuel Gauge circuit with I2C communication 5V signaling Configuration: 2S3P Recharging time: 24 to 48 hours Certification: UN3480 CONSUMPTION Max. 6 VA FUSE 6 A MEMORY RTU+SERVER2 OPERATING SYSTEM SOFTWARE 128 MByte SDRAM (32-bit wide) 256 MByte Managed NAND Flash (up to 2GByte on request). Memory extension is not possible. Linux Plug and Play configured software cooperating with EIServer Data collection software with extended protocol library SOFTWARE UPGRADES via Ethernet via USB via GPRS (possible but not recommended) TEMPERATURE Extended temperature range from -20 C to +60 C TAMPER DETECTION Tamper contact via a cover-removed alarm: when the internal cover is removed, an alarm signal is sent to the meter data management platform. CERTIFICATIONS CCSAUS certified Emission: FCC Part 15, FCC ID : VS7RTUS2-WC / IC : 9864A-RTUS2WC 10 / 29 RTU+Server2 Casing Overview The RTU+ Server2 resides in a PC ABS UL94 5VA-compliant plastic enclosure. This cover shields the motherboard and all internal components from the outside. 3 screws are used to fasten this cover to the mounting plate. Dimensions Plastic enclosure 183 * 174 * 62 mm. 11 / 29 IP Enclosure Casing Overview The RTU+ Server2 and all EVOGate 2.0 components are mounted into a Polyester wall-mounting enclosure IP 66 Type NSYPLM43:
Technical specifications Monobloc wall-mounting enclosure made from polyester reinforced with fiberglass, molded by hot compression, RAL 7032 grey color. Degree of protection IP 66 according to IEC 60529. Resistance to external mechanical impacts:
Plain door enclosures IK 10 (20 joules). Locking device outside the sealed area, guaranteeing the tightness of IP 66 over time. Locking system:
2 locks with double-bar insert Door opening angle: 180. 12 / 29 Dimensions 13 / 29 RTU+Server2 Labels Overview The RTU+ Server2 has the following 2 labels located on its casing:
Label B Max. 50 mA Label A This label contains the RTU+Server2s article code and unique serial number:
Label A 1 2 3 4 1. Article code The code of the product. Consult the Appendix for a full overview of available product types, their article codes and spare parts. 2. Production Time XXYY:
XX: Production Year (last two digits of the year) YY: Production Week 3. Description The description of the data concentrator 4. Serial number XXX YYYYYYYYYYYY XXX: Family Type YYYYYYYYYYYY: Unique Serial Number 14 / 29 Label B This label depicts the power input specifications and warning content:
15 / 29 IP Enclosure Labels Overview The IP enclosure has:
2 labels located on its front panel:
Label C Label D 2 labels located on its bottom panel:
Label E Label F 1 label located on the inside of its door:
Label G 16 / 29 Label C Warning label:
Label D EnergyICT logo:
Label E Identical as Label A:
Label F The FCC and IC Label; also depicts the article number of the EVOGate 2.0:
17 / 29 Label G The WaveCard Radio address label:
18 / 29 LED Indications Introduction The RTU+Server2 data concentrator has 6 LEDs located on the top cover of the enclosure. Power Power LED ON when the unit is powered. 1st Ethernet port LED. ETH1 ETH2 2nd Ethernet port LED.
- When OFF: no link integrity
(no cable connected)
- When ON: link integrity
(link with HUB)
- When blinking:
receiving data GPRS GPRS LED ON when transmitting data Application Dependent
- When blinking at 0.5Hz:
receiving data Reserved Reserved A B 19 / 29 Chapter 2: Mounting and Wiring Introduction This chapter provides information on the physical installation of the polyester enclosure, including mounting and wiring instructions. Chapter description This chapter describes the following topics:
Topic Mounting Instructions IP Enclosure Power Supply Wiring Safety Guidelines Power Supply Wiring Instructions EVOGate 2.0 Power Supply Wiring RTU+Server2 Page
[20]
[20]
[21]
[22]
20 / 29 Mounting Instructions IP Enclosure Mounting the IP Enclosure The IP enclosure can be mounted directly on the walls. The seals and caps supplied as standard with the enclosure guarantee that it maintains its degree of protection and insulation. There are 3 options:
Wall-fixing lugs Post-fixing device Blanking Plates Important!
Included in the EVOGate 2.0 package is a document which describes these options. However, none of these options are part of the EVOGate package and need to be purchased from Schneider. Please refer to the Schneider website to purchase these options. Power Supply Wiring Safety Guidelines Securing the device The RTU+Server2 concentrator is internally protected by fuse resistors. Power rating: 2W. Fuse type : Welwyn Components ULW2-100RJA25 Wiring The following additional guidelines must be taken into account:
+ The unit must have a permanent connection to fixed wiring
+ The power supply must be connected to the power connector of the RTU+
Server2 by means of solid wiring. Cables The concentrator was designed and tested to operate safely in an industrial and residential environment. However, you must take care to use one of two options:
+ Shielded network cables (FTP cables)
+ Unshielded network cables (UTP cables) Power specifications Power specifications are located on label B and label F, as mentioned under the labels section on page 14 and 16. 21 / 29 Power Supply Wiring Instructions EVOGate 2.0 Power connector The power supply cable gland is located to the right on the bottom panel of the EVOGate 2.0s enclosure. The cable gland only accepts AC input signals. Power supply wiring connections Connect the electrical wire to the cable gland carefully. Power Supply Cable Gland G L1 L2 22 / 29 Power Supply Wiring RTU+Server2 Power connector The power supply connector is located at the bottom left corner of the RTU+
Server2. The connector only accepts AC input signals. Single wire or two wires Power supply wiring connections The connector accepts single wires of 0,2 to 2,5 mm (24 to 14 AWG) or two wires of 0,2 to 1,0 mm (24 to 18 AWG). Important!
The RTU+Server2 is already fully connected at EVOGate 2.0 purchase. L1 L2 Circuit Physical Connection 2F 115V x x L1 L2 23 / 29 Chapter 3: Communication Interfaces Introduction The EnergyICT RTU+ Server2 is configured with a number of communication interfaces for downstream communication to the meters as well as upstream communication to a central data management system. Chapter description This chapter contains RTU+Server2. Important!
information on the communication cards of the All communication interfaces are already in place at purchase; installation and maintenance may only be carried out by qualified personnel. Topic Overview Communication Interfaces Upstream Double Ethernet Connection Double USB 2.0 Interface GSM/GPRS Modem Downstream Wavenis RF Modem Page
[24]
[25]
[25]
[26]
[27]
24 / 29 Overview Communication Interfaces Description The overview of the RTU+ Server2 standard communication interfaces is shown below:
A. Double USB connectors F. Power input connector B. Double Ethernet connectors G. RF Wavenis antenna connector C. Wired M-Bus connector
(Not Applicable) D. SIM-card interface E. GSM/GPRS antenna connector H. Digital inputs
(Not Applicable) I. Digital outputs
(Not Applicable) J. RS-485 connector
(Not Applicable) 25 / 29 Double Ethernet Connection Description The RTU+ Server2 uses the Ethernet 10/100 Base-T standard. Every unit features 2 standard Ethernet ports, as depicted below, and can be connected to a LAN network using standard straight-through LAN RJ-45 connectors. Link Integrity and Rx indication LEDs are located on the connector. To make a direct connection to a PC, a crossover LAN cable should be used. Double USB 2.0 Host Connection Description The RTU+ Server2 uses the USB 2.0 standard. Every unit features 2 standard USB interfaces, as depicted below, next to the Ethernet ports. Both connections can, for example, be used to connect keyboards and memory sticks for software updates. IMPORTANT USB ports may exclusively be used for service purposes. A maximum of 50 mA is allowed. USB devices must be removed during normal operation. 26 / 29 GSM/GPRS Modem Description This card equips the RTU+ Server2 with a high tech GSM/GPRS modem. This allows collected data to be transmitted over the Internet without a need for a fixed connection. Installation Note
+ The advanced GSM/GPRS EDGE modem is available on request: this technology offers increased data transmission speeds and is supported by all major providers. In order to function, the GSM/GPRS modem requires a SIM-card. C B A D This SIM-card has to be placed inside a SIM-card holder A and placed inside B on the modem itself, before switching on the RTU+ Server2. Next, the GSM-antenna has to be screwed into C. Press D to eject the SIM-card holder. Technical specifications Feature Frequency Bands Implementation Quad-band module includes support for GSM 850 and PCS 1900 Compliant to GSM Phase 2/2+
Transmit Power Class 1 (1W) at GSM 850 and PCS 1900 GPRS GPRS multi-slot class 10 Connectivity GPRS mobile station class B Temperature Normal operation: -20C to +60C Range GPRS data downlink transfer: max. 85.6 kbps GPRS GPRS data uplink transfer: max. 42.8 kbps Coding scheme: CS-1, CS-2, CS-3 and CS-4 SIM Interface Supported SIM card: 1V8, 3V 27 / 29 Wavenis RF Modem Description This module empowers the RTU+ Server2 to serve as master in a Wavenis RF network. Wavenis is an integrated wireless communication application capable of high performance network management and 2-way endpoint monitoring, remote data collection and scheduled polling. Communication management for extended networks is achieved via smart gateways, repeaters and end-points. Stored data is uploaded to EIServer via EnergyICTs proprietary EIWeb+ protocol. The RF module is embedded at the factory. Important!:
The Wavenis RF antenna and coax cable need to be ordered separately!
EnergyICT recommends the Antenex FG9026 as this was used for the FCC / IC tests. When activating the Wavenis modem, an RF antenna must already be connected to the EVOGate 2.0! The absence of an antenna during activation will cause irreparable damage to the modem. Consult the Appendix for more information. Antenna connection Wavenis Antenna Connector Technical specifications Feature Implementation Frequency range 915 MHz Output power Maximum +27 dBm (500 mW) Receiver sensitivity Channels Data rate Range
(-110)dBm @ 19.2 kbps
(-113)dBm @ 4.8 kbps 16 channels (hopping) Maximum: up tot 100 kbps Outdoor: up to 1000 meters (line-of-sight) 28 / 29 Appendix Article numbers This number represents the code for the concentrator type. If you experience problems with your concentrator or wish to purchase spare parts, please refer to the specific article number:
Article Number Description EVOGate 2.0 ELGR900008 RTU+Server2 + IP Enclosure + Wavenis 915Mhz 500mW US + Battery + Protection GPRS/GSM +
Protection Wavenis + Breaker + Filter + GPRS Antenna + NO Wavenis Antenna Antenex FG9026 Wavenis Antenna
(Needs to be purchased separately) CCBL000033 Spare Parts Low loss coax cable, 10meter. Nmale both sides
(Needs to be purchased separately) CBAT000003 Battery CANT000021 GSM Antenna 29 / 29