Occupancy Sensor - Wall Mounted 2.5 64mm 1.1 28mm Specifications Installation Guide Model: EOSW Solar Cell Lens Button Interface Package Contents Occupancy Sensor 2 screws, 2 wall anchors 1 wide angle lens
(installed) 1 long range lens 5.8 148mm 1.8 45.7mm Tools Required Power drill, 3/16 bit Screwdriver Leveling tool Light meter Battery (CR2032) for testing Product Description The wall-mounted Occupancy Sensor saves energy and adds convenience by accurately detecting when an area is occupied or vacant. It is wireless, solar-powered, and uses a passive infrared (PIR) sensor to detect motion. The occupancy sensor transmits RF sig-
nals that control lighting, HVAC, and outlets to manage building energy consumption more efficiently. Features Include:
Sends wireless signals to receiving devices whenever motion is detected Harvests indoor light to power the sensor and wireless communications Mounts flush on the wall or in a corner; adjustable ceiling corner bracket sold separately Works with other sensors for enhanced occupancy tracking Interchangeable lenses for tailored sensor coverage Built-in tests to confirm operation at installed location Supplemental battery or alternative power supply options for extreme low-light conditions Power Supply Transmission Range Radio Frequency Light Required to Sustain Operation Charge Time before Linking Charge Time for Full Charge Operating Life in Dark-
ness (after full charge) EEP (EnOcean Equipment Profile) Indoor light energy harvesting
(Optional) Supplemental battery or 2-wire connector for external power or remote solar cell (3-5VDC) 80 ft. (25 m) EnOcean 315 MHz, ISO/IEC 14545-3-10 standard 50 lux for 30 transmissions/hour 100 lux for 60 transmissions/hour 2 minutes @ 50 lux 3 hours @ 200 lux (after startup) 6 hours @ 200 lux (cold start) 48 hours A05-07-01 Dimensions Weight Environment Heartbeat 2 - 12 mins., randomized 5.83 L x 2.52 W x 1.8 D
(148 mm x 64 mm x 45.7 mm) 4.09 oz. (116 g) Indoor use only 14 to 104F (-10 to 40C) 20% to 95% relative humidity
(non-condensing) FCC, IC Agency Compliance Functional Description If occupation is detected by the permanently active PIR sensor, a radio telegram indicating the occupied status will transmit immediately. An internal timer starts to run with a variable timer length. The timer value may vary between 60 and 300 seconds, depending on the light level. No radio telegrams will be sent out when the timer is counting down. After the timer has finished the countdown, the unit will trans-
mit again if occupancy was detected during the countdown time period. If occupancy was not detected, the unit will transmit a heartbeat signal - sending the unoccupied status with a ran-
dom timing of 2 to 12 minutes. There are two buttons which allow entrance to a Walk or Light-level test mode. These test modes are for installation purposes only and will be exited automatically after 3 minutes. Page 1 Occupancy Sensor Wall Mounted Installation Guide Planning Take a moment to plan for the sensors successful operation and optimal communication with other system components. Remove the sensor from its packaging and place it under a bright light to provide the required startup charge. To quickly ensure the sensor energy storage is fully charged, insert a CR2032 battery for 30 seconds. Ensure the location provides consistent and adequate light Install with the appropriate lens for the required coverage Locate the sensor between 8 and 10 ft (2.4 to 3 m) high with an unobstructed view of the space For wide angle coverage, locate the sensor where traffic moves across the detection pattern, not in and out Consider the areas traffic patterns and principal use, for example, walking, lounging or sleeping Provide a minimum clearance of 4 ft. (1.2 m) away from heat sources, light bulbs, forced air, or ventilation systems Consider the construction materials (such as metal) in the space and obstacles that may interfere with RF signals Sensor Range A single occupancy sensor provides sufficient coverage for most applications. For some applications, multiple sensors may be required to provide complete coverage. Wide Angle Coverage 33 ft (10 m) 16 ft (5 m) 0 16 ft (5 m) 33 ft (10 m) 6.8 ft
(2.1 m) Top View Side View 6 ft 15 ft 25 ft 50 ft Long Range Coverage 77 27 16 ft 8 ft 0 8 ft 16 ft 6.8 ft
(2.1 m) Top View 21.5 14 6.5 center line Side View 3 ft
(1 m) 7 ft
(2.2 m) 10 ft
(3 m) 35 ft
(10.7 m) 60 ft
(18.3 m) 100 ft
(30.5 m) Installing estimated time: 20 minutes The mounting plate can be installed flush to the wall or angled in a corner. NOTE: It may be easier to link the sensor before it is mounted on the wall. See the Linking section. 1. Remove the mounting plate from the sensor assembly by pressing the release tab located on the top of the sensor. 2. Using a level and a pencil, lightly mark two small dots to align the upper edge of the mounting plate. 3. Decide which of the two installation options is appropriate:
A. Flush to the Wall i. Orient the mounting plate using the pencil marks. Mark the two mounting screw drill points. ii. Drill two holes with a 3/16 drill bit and insert the wall anchors. iii. Insert the first screw loosely and level the mounting plate. iv. Insert the second screw then hand-tighten the first screw. B. Angled in a Corner i. Orient the mounting plate using the pencil marks. ii. Carefully drill through two of the four blind holes on the angled sides of the mounting plate (one on each side). iii. Mark the two mounting screw drill points and drill two pilot holes with a 3/16 drill bit and insert the wall anchors. iv. Insert the two screws and hand-tighten them. 4. Fit the sensor into the groove at the bottom of the mounting plate and close the top. Page 2 Occupancy Sensor Wall Mounted Installation Guide The sensor snaps into the tab at the top. 5. Confirm the sensor is properly positioned to detect motion and has sufficient light to operate, see the See Walk Test and See Light Test sections. Linking Two or more compatible devices can be linked and configured to provide the desired control. There are two basic types of devices in the system; transmitters and transceivers. Transmit-only: Transmitters are simple energy-harvesting devices that send RF messages to communicate a condition, level, or state. Transmitters can only be linked to transceivers. Examples > Self-powered Light Switches, Occupancy Sensors Transmit & Receive: Transceivers are controlling devices that send as well as receive RF messages. They also process relevant control logic, and actuate the appropriate outputs
(switching a light on or off for example). Transceivers can be linked with transmitters as well as other transceivers. A trans-
ceiver can have up to 30 devices linked to it. Examples > Relays, Gateways The Occupancy Sensor is a Transmit-only Device. To link the occupancy sensor to a transceiver; the transceiver must first be powered, within wireless range, and set to accepts links. Next, the desired transmitter, or another transceiver, is triggered to send a special link message. The awaiting transceiver receives and stores the link permanently so the devices can interact to provide a variety of intelligent control options. To Link or Unlink an Occupancy Sensor 1. Set the desired transceiver to Accept a Link (refer to that devices installation guide). 2. Click the Menu button on the bottom of the sensor once. This sends a link/unlink radio telegram. NOTE: The button interface on the sensor is used for linking and testing only. The occupancy timer settings are configured on the transceiver to which the sensor is linked. Refer to the Linking section of the transceiver/controller installation guides to complete the linking process. Testing the Sensor Before starting a test, ensure the sensors energy storage is fully charged by placing it under bright light (at least 200 lux) for 20 minutes, or insert a battery for 5 minutes. If a battery is used to charge the sensor for a light test, ensure it is removed to get an accurate light measurement. A test mode will stay active for 3 minutes. To exit a test and resume normal operation, press and hold the Menu button for 5 seconds. Walk Test Use the walk test to confirm that motion is within the sensors range. 1. Press and hold the Set button for 5 seconds.
> Red LED will blink to confirm that a walk test is active. 2. Move in and out of the sensors range to determine its cov-
erage area.
> Sensor will blink when it detects motion. 3. Make small hand movements just inside the limit of the sen-
sors range to see if the motion triggers a response. Light Test Use the light test to measure real-time light levels and confirm whether the occupancy sensor has sufficient light. 1. Create a realistic lighting condition (the test measures the real-time light level). 2. Press and hold the Set button for 10 seconds.
> Red & green LEDs will blink to confirm light test is active. 3. Watch the LED blink rate to determine the light strength.
> The highest is 5 blinks which indicates very good light
(200 lux or more). 1 blink indicates minimum light (15 lux). NOTE: If there is no blink rate, consider relocating the sensor or installing a battery to provide supplemental power. If the sensor does not have a sufficient charge, it cannot enter the test modes. No LED light or 1 red blink when the test button is pressed indicates insufficient charge. Changing the Lens The Occupancy Sensor package contains two lenses: a wide angle lens and a long range lens. The wide angle lens is installed by default and can be distinguished from the long range lens by the pattern. Lens Patterns Wide Angle Lens Long Range Lens Page 3 Occupancy Sensor Wall Mounted Installation Guide To change the lens:
1. If the sensor is mounted, press the top tab and remove it from the mounting plate. 2. Unscrew the front cover screw on the back at the bottom and remove the front cover. 3. Remove the installed lens by gently squeezing it to ease one side out of its groove, and then the other. 4. Insert the lens you want to use by aligning the notch with the top on the front cover. Orient the smooth side facing out, and the textured side facing the sensor. 5. Hold both edges of the lens, flex it gently and push until it pops into the grooves. Make sure the edges are flush. NOTE: If the lens is out of position, the sensor will not detect activity properly. 6. Replace the top edge of the front cover and then close it on the sensor. 7. Replace the bottom screw and remount sensor on the plate. Installing Supplemental Battery (optional) If light levels are very low where the sensor is installed, auxiliary battery power (CR2032) can be used to supplement the solar energy harvester. 1. Remove the sensor from the mounting plate. 2. Unsnap sensor cover and identify the battery holder on the circuit board. 3. Insert the battery under the clip with the positive pole (+) up and press it in place. 4. Replace cover and remount the sensor on the wall. Troubleshooting Problem Sensor does not generate a wireless message Sensor is activated when there is noth-
ing to detect during a walk test Solution Checklist Verify the LED blinks when motion is detected Verify the solar cell is charged properly Verify there is 4 ft. (1.2 m) clearance from heat Reduce sensitivity setting by moving the PIR sensitivity switch on the back to low (the left-
hand position) sources that may disturb sensing Linked device does not respond to wireless messages Check for environment or range issues Verify the device is linked Check the transceiver connection and the wir-
Check if appropriate devices are linked accord-
ing for errors ing to good system planning FCC SZV-EOSW01 IC 5713A-EOSW01 This device complies with part 15 of the FCC rules and Industry Canada ICES-003. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. IMPORTANT! Any changes or modifications not expressly approved by the party responsible for compliance could void the users authority to operate this equipment. Le prsent appareil est conforme aux CNR dIndustrie Canada applicables aux appareils radio exempts de licence. Lexploitation est autorise aux deux conditions suivantes: (1) lappareil ne doit pas produire de brouillage, et (2) lutilisateur de lappareil doit accepter tout brouillage radiolectrique subi, meme si le brouillage est susceptible den compromettre le fonc-
tionnement. IMPORTANT! Tous les changements ou modifications pas expressment approuvs par la partie responsable de la conformit ont pu vider lautorit de lutilisateur pour actioner cet quipment. Limited Warranty Subject to the other terms of this warranty, the manufacturer warrants you the original purchaser that this product will be free from defects in material and workmanship for one year from the date of your purchase of the product. During that period, if the product does not comply with this limited warranty, the manufacturer will, at its discretion, repair or replace the product. Repair or replacement is your sole remedy under this or any other warranty of the product, whether express or implied. Coverage Limitations. This limited warranty extends only to the original purchaser and is not transferable. This limited warranty expressly excludes any defects or damages resulting from any product installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner. To obtain warranty service - return the product, a description of the problem, together with your proof of purchase, securely packaged and with postage prepaid, to the manufacturer. You may be required to provide other information or evidence of the defect. Any returned product that is replaced becomes the property of thye manufacturer. Implied Warranties. TO THE EXTENT PERMITTED BY LAW, ANY IMPLIED WARRANTIES, IN-
CLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO THE SAME DURATION AS THIS EXPRESS WARRANTY. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. NO OTHER EXPRESS WARRANTY HAS BEEN MADE OR WILL BE MADE BY THE MANU-
FACTURER WITH RESPECT TO THIS PRODUCT. Limitation of Liability. THE MANUFACTURER SHALL NOT BE RESPONSIBLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES SUCH AS THE COST OF LABOR FOR REMOVAL OR REINSTALLATION OF THE PRODUCT, WHETHER ARISING OUT OF BREACH OF WARRANTY, BREACH OF CONTRACT, TORT, OR OTHERWISE. Some states do not allow the exclusion of inci-
dental or consequential damages, so the above exclusion and limitation may not apply to you. This limited warranty gives you specific legal rights, and you also may have other rights which vary from state to state. In Canada, the above provisions are not intended to operate where prohibited by law and do not preclude the operation of any applicable provisional consumer protection statute which in certain circumstances may extend the express warranties herein. Page 4