ZigbeePIR,Photo&LightingControl ON/OFF&010VDimming Product Features Environmental Zigbee Wireless Control of Luminaries Zigbee Occupancy Sensor, & Photo Sensor 2.4GHz, +20dBm Zigbee transmit power 0-10V Analog Dimming Control, 50mA Sink Compatible with Electronic Ballasts & LED Drivers that comply with IEC60929 Annex E2, 0-10V Dimming. Best when used with Dim to Zero (Dim to OFF) Ballasts & LED Drivers 1. Operating temperature: 0 to +60C 2. Storage temperature range: -10C to +70C 3. Humidity (non-condensing): 5% - 95%RH 4. Cooling: Convection 5. Vibration Frequency: 5-55Hz/2g, 30 minutes 6. Impact resistance: 1g/s Safety and Compliance Electrical Specifications at 25OC I P R
L i g h t
P h o t o
T e m p S 8 3 0 P L D Z B Z i g b e e W l i r e e s s 1. UL244A Listed 2. FCC ID: 2AJ2N-S830-PL-DZB, FCC Class B 3. Zigbee 3.0 compatible 4. Mount 1/2 Inch Trade Size Knockout, Dust Proof Design IP50 Part Numbers E513483 Input: UL Class 2 DC voltage 12VDC (10 to 14VDC) Input Current Draw: 60mA, 200mA Peak during transmit. 0-10V Dimming intended for use with Dim to Zero/Dim to OFF Ballasts and LED Drivers. IP50 S830-DZB Part Number Dimming US & CN Class 2 Control S830-PL-DZB YES Zigbee 3.0 S830-DZB YES Zigbee 3.0 ON/
OFF Control YES via Dim YES via Dim Dimming 0-10V Analog Photo Sensor PIR Occupancy Sensor YES YES YES NO YES NO Typical Application Circuit S830 S830-ACC-CNR1M Accessory 1M Cable S830 +12VDC S830 12VDC GND S830 DIM-
S830 DIM+
S830-PL-DZB 12VDC UL Class 2 Power Source AUX +12VDC AUX Common AC Line (BLACK) AC Neutral (WHITE) Dimming LED Driver or Dimming Ballast
(0-10V) VIOLET (0-10V) Dim+ Control PINK (0-10V) Dim Control Legacy Dim- = GRAY FCC ID 2AJ2N-S830-PL-DZB: Channel 11 to 25 See warnings on page 4. EuControlContact:Info@EuControls.comlLosAngeles,CA90248l8885359580 Specifications subject to change without notice EuControls, Inc. Los Angeles, California T: 888 535-9580 E: Sales@EuControls.com www.EuControls.com Rev B - 08/05/2022 U.S. Patent Pending 1 I P R
L i g h t
P h o t o
T e m p S 8 3 0 P L D Z B ZigbeePIR,Photo&LightingControl ON/OFF&010VDimming FCC ID 2AJ2N-S830-PL-DZB: Channel 11 to 25 See warnings on page 4. Mechanical Dimensions: Inches [mm]
Labeling Example Material: 5VA PC Plastic Case Weight: TBD Grams (TBD oz.) Typical Notes:
RED Occupancy LED Visible through PIR Lens. GREEN Zigbee LED Visible through PIR Lens. S830-DZB GREEN Zigbee LED Visible through Flat Cover Reset switch is located on flat side of case near connector. Z i g b e e W l i r e e s s S830-ACC-CNR1M, 1 Meter Cable, mm (Scale ~5:1) S830-DZB EuControlContact:Info@EuControls.comlLosAngeles,CA90248l8885359580 Specifications subject to change without notice EuControls, Inc. Los Angeles, California T: 888 535-9580 E: Sales@EuControls.com www.EuControls.com Rev B - 08/05/2022 U.S. Patent Pending 2 Z i g b e e W l i r e e s s ZigbeePIR,Photo&LightingControl ON/OFF&010VDimming I P R
L i g h t
P h o t o
T e m p S 8 3 0 P L D Z B Input Specifications Parameter Min. Typ. Max. Notes/Conditions Input Voltage Input Current Zigbee Control Transmit Power Zigbee Control Receive Photo Sensor Range 10 1 12 14 V DC, UL Class 2 Power Source 60mA 200mA Peak mA DC, Peak occurs during transmit
+20dBm ON/OFF, 0-10V dimming & Photo Sensor, Standard Zigbee
-95dBm 300fc Zigbee Radio Receive Sensitivity Precision Optical Filtering Matches the Human Eye Output Specifications Parameter Min. Typ. Max. Notes/Conditions Sink Current on 0-10V (+) Violet Wire 0mA 50mA IEC60929 Annex E2 Absolute Voltage Range on 0-10V (+) Violet Wire
-20.0V
+20V IEC60929 Annex E2 Dimming Range 0.2V
+10V Ballast or Led Driver provides Dim Voltage & Current per IEC60929 Annex E2, 0(1)-10V Analog Dimming Environmental Specifications Parameter Min. Typ. Max. Notes/Conditions Operating Temperature (Ta) Storage Temperature (Ts) Operating Humidity Vibration 0 OC
-10 OC 5 Hz
+60 OC
+70 OC Operating temperature range. Non operating temperature range. 95% RH Relative Humidity, non-condensing. 55 Hz 2G, 10 minutes/1 cycle, period 30 minutes, each along X, Y, Z axis. Safety & EMC Compliance Safety Notes/Standards UL/CUL Listed UL910, CSA22.2 NO. 205 CE 0-10V Class 2 Dimming Circuit FCC EN61347-1, EN61347-2-13 UL & cUL Class 2, Dim+ Violet/Dim Pink. (Using a 12VDC UL Class 2 Power Source) FCC ID 2AJ2N-S830-PL-DZB CH11 to CH25, Also Certified to FCC Class B, See Warnings on page 4. EuControlContact:Info@EuControls.comlLosAngeles,CA90248l8885359580 Specifications subject to change without notice EuControls, Inc. Los Angeles, California T: 888 535-9580 E: Sales@EuControls.com www.EuControls.com Rev B - 08/05/2022 U.S. Patent Pending 3 ZigbeePIR,Photo&LightingControl ON/OFF&010VDimming Standard Lens Coverage I P R
L i g h t
P h o t o
T e m p S 8 3 0 P L D Z B Z i g b e e W l i r e e s s FCC ID 2AJ2N-S830-PL-DZB: Channel 11 to 25 Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the users authority to operate the equipment. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-- Reorient or relocate the receiving antenna.
-- Increase the separation between the equipment and receiver.
-- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-- Consult the dealer or an experienced radio/TV technician for help. To maintain compliance with FCC's RF exposure guidelines, the distance must be at least 20cm between the radiator and your body, and fully supported by the operating and installation configurations of the transmitter and its antenna(s). EuControlContact:Info@EuControls.comlLosAngeles,CA90248l8885359580 Specifications subject to change without notice EuControls, Inc. Los Angeles, California T: 888 535-9580 E: Sales@EuControls.com www.EuControls.com Rev B - 08/05/2022 U.S. Patent Pending 4