Vibration Sensor Node (SD-VSN-3) The SmartDiagnostics family of innovative wireless sensor products enables cost-effective predictive maintenance for industrial equipment. The system provides continuous remote monitoring of key performance indicators to track the operating health of equipment. Optimized for long battery life Full time series data sets up to 5 times per minute Expandable to hundreds of nodes per system Reliable Monitoring Flexible Configuration Cost Effective Vibration Sensor Nodes provide health monitoring in the most hard-to-reach, rugged locations. Each node communicates via a direct wireless link to a Primary Receiver Node, from which the data is imported into SmartDiagnostics Software for viewing and analysis. The system is highly configurable and scalable. A system can have hundreds of sensor points, each of which can be configured to transmit data on a user-selected frequency, and unique indicators can be implemented to warn users of potential machine health issues. Easily installed without the downtime, expense, and labor costs of old-fashioned, hard-wired sensors. Simply place the sensors where you need them and within minutes theyll transmit data. SmartDiagnostics can predict failure before it occurs, saving money spent on unnecessary replacements and extending machine life. At the same time, energy costs are reduced, as properly maintained machines are more efficient. KCF Technologies, Inc. 336 South Fraser Street State College, PA 16801 www.kcftech.com Sales and Support
(814) 867-4097
(814) 690-1579 Fax sales@kcftech.com Learn more at kcftech.com/smartdiagnostics Vibration Sensor Node Specifications Mechanical Weight Enclosure Material Environmental Storage Temperature Min. Operating Temp. 6.6 oz (188 g) 303 Stainless Steel and Radel R 5800
-40 to 238 F (-40 to 120 C)
-4 F (-20 C) 230 F (110 C) surface @ 72 F (22 C) ambient 212 F (100 C) surface @ 105 F (40 C) ambient 167 F (75 C) surface @ 167 F (75 C) ambient IP68, dust-tight and water-tight Survives 5-ft drop onto concrete surface Class I, Division 2, Groups A-D, T5 (model SD-VSN-3N) Max. Operating Temp. IP Rating Impact Resistance Hazardous Certification Wireless Radio Radio Range Antenna Power Power Source Battery Life Accelerometer Range Resolution Noise Floor Transverse Sensitivity Frequency Response Samples per Acquisition Spectral Lines Anti-Aliasing Filter Sampling frequency Temperature Sensor Range Resolution Configurations Part Number SD-VSN-3 SD-VSN-3N SD-VSN-3E KCF DART Wireless 2.4GHz ISM band, FCC ID #Z5ISD2 800ft (240m) in open field 200ft (60m) in congested industrial space
(site survey recommended for installation) Repeater SD-R adds up to 2400ft (730m) of range Internal dipole antenna 3-Volt Lithium Manganese Dioxide (CR123A) Full spectrum acquisition every:
Note: battery life is somewhat reduced at extremely cold temperatures 60 minutes 8 years 15 minutes 6 years 2.5 minutes 2 years
+/- 19 g typical, +/- 16 g nominal 0.866 mg nominal w/ individual NIST-traceable calibration 1.496 mg RMS @ 64 Hz / 13.01 mg RMS @ 8192 Hz 10% Typical
+/- 5% 0-2700 Hz, +/- 3 dB 2700-4000 Hz 4096 (standard) or 1650 (battery saver) 2048 (standard) or 825 (battery saver) 4000 Hz low-pass cut-off, 3rd-order Sallen-Key 64 Hz 8192 Hz configurable (see table)
-4 to 167 F (-20 to 75 C)
+/- 1 F (+/- 0.5 C) Accelerometer Sampling Sampling Frequency (Hz) Sample Duration (s) Spectral Resolution (Hz) Std. (batt. saver) Std. (batt. saver) 8192 4096 2048 1024 512 256 128 64 0.5 (0.2) 1.0 (0.4) 2.0 (0.8) 4.0 (1.6) 8.0 (3.2) 16.0 (6.4) 32.0 (13) 64.0 (26) 2.0 (5.0) 1.0 (2.5) 0.5 (1.24) 0.25 (0.62) 0.13 (0.31) 0.063 (0.16) 0.031 (0.08) 0.016 (0.04) Handling and Care Please consult Application Note on proper use:
https://kcftech.com/smartdiagnostics/resources Description Standard vibration and temperature sensor Class I, Division 2 Certified vibration sensor for use in hazardous locations (US and Canada ETL control number 4008627) Standard vibration and temperature sensor with extended temperature battery This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This equipment complies with the FCC RF radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20cm between the radiator and any part of your body. Changes Or Modifications Not Expressly Approved By The Party Responsible For Compliance Could Void The User's Authority To Operate The Equipment. KCF Technologies, Inc. 336 South Fraser Street State College, PA 16801 www.kcftech.com Sales and Support
(814) 867-4097
(814) 690-1579 Fax sales@kcftech.com