Trusted KE2 Wireless Sensor for Temperature & Humidity C-DTM-KE2WS - 01 January 2018 KE2 Wireless Sensor for Temperature & Humidity Introduction:
More than waterproof and portable, the KE2 Wireless Sensor is a high-precision digital temperature and humidity indicator
(thermo-hygrometer). The wireless signal and light-weight design mean installation takes just seconds. And, the sensors 3-year bat-
tery life ensures low maintenance and extended performance. The Trusted DTM Edge Manager automatically finds and dash-
boards up to (35) KE2 Wireless Sensors and KE2 Therm con-
trollers. So, local monitoring is almost instantaneous, and IT support is generally not necessary. Remote monitoring is easily achieved by using KE2 Therm's KE2 SmartAccess and/or the KE2 Connect's Trusted DTM Portal. After powering the unit on, the KE2 Connect EDGE Manager will automatically locate the KE2 Wireless Sensor and provide tem-
perature and humidity data. The KE2 Wireless Sensor uses a high-quality, integrated digital temperature and humidity sensor module, ensuring the transmit-
ters superior long-term stability, low latency and resistance to chemical contamination, thus providing an excellent platform to deliver temperature and humidity data. Application:
The KE2 Wireless Sensor can be used to measure environmental temperature and humidity in industrial, commercial, and residen-
tial environments. Common applications are: laboratory, agricul-
tural, communications, storage facilities, warehouses, refrigerated spaces, medical and hospitality. Features & Benefits:
High-accuracy digital temperature and humidity sensor inside Temperature monitoring - tenths of a degree Humidity monitoring - relative humidity +/- .25%
Configurable location name Wireless signal - using BLE 4.1 (Bluetooth Low Energy device) E-mail/Text alerts (see list below) IP66 waterproof level 300ft./100m broadcasting range 3- year battery life (AAA) Low battery indicator 12-month free Trusted DTM portal access Ultra-low power consumption chipset nRF52832 Very fast start-up and measurement time Real-time data converting, storing, & uploading Excellent security mechanism Alarms:
High/low temp alarm with adjustable time delay Disconnect alarm - Edge Manager loses contact with sensor Device loss alarm - KE2 Wireless Sensor loses contact for an extended period (user defined) Portal Disconnect Alarm (optional) 12 Chamber Drive . Washington, Missouri . 63090 ke2connect.io 636.266.0140 2018 KE2 Connect, Washington MO 63090 Trusted KE2 Wireless Sensor for Temperature & Humidity C-DTM-KE2WS - 01 January 2018 Page 2 Physical Properties:
(21632) - KE2 Wireless Sensor for Temperature and Humidity
(21633) - KE2 Wireless Sensor for Temperature and Humidity with External Sensor -
36 sensor wire Waterproof Level Case Material Case Color Product Dimensions Unit Weight Battery Type Voltage Data Access Average Power Consumption Transmission Range Assemble IP66 ABS White 70.6 x 38 x 17.8mm 1.52 oz. / 43g
(2) AAA - FR03 Li-Fe batteries 3V Edge Manager Product Line or KE2 Connect Mobile Client 35uA Max. 300ft/100m in open space 3M adhesive Technical Specifications:
Item Temperature Humidity Sampling Period Range Measure Accuracy Range Measure Accuracy Resolution Value
-40F to 158F
-40C to 70C 50F to 122F 10C to 50C 50F or 122F 10C or 50C 0%RH to 100%RH 0%RH to 90%RH 90%RH 0.05%RH Once per second Error Range Depends on battery working environment 0.9F 0.5C 3.6F 2.0C 2.5% RH 3.5% RH 12 Chamber Drive . Washington, Missouri . 63090 ke2connect.io 636.266.0140 2018 KE2 Connect, Washington MO 63090 Trusted KE2 Wireless Sensor for Temperature & Humidity C-DTM-KE2WS - 01 January 2018 Page 3 Electrical Specifications:
Static Current Peak Current Average Current Battery Type Battery Capacity Lifetime
<3uA (power consumption under power-off status)
<8mA
<35uA
(not including power consumption on data transmission) FR03 1250mAH Over 3 years Environmental Properties:
Working Temperature Long-term Storage Temperature
-40F to 158F
-40C to 70C 50F to 77F, 65%RH 10C to 25C, 65%RH 12 Chamber Drive . Washington, Missouri . 63090 ke2connect.io 636.266.0140 2018 KE2 Connect, Washington MO 63090 FCC Caution This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Any Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help. The device has been evaluated to meet general RF exposure requirement. The device can be used in portable exposure condition without restriction. IC Caution:
This device complies with Industry Canadas licence-exempt RSSs. Operation is subject to the following two conditions:
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause undesi red operation of the device. Le prsent appareil est conforme aux CNR d'Industrie Canada applicables aux apparei ls radio exempts de licence. L'exploitation est autorise aux deux conditions suivantes:
(1)
(2) brouillage est susceptible d'en compromettre le fonctionnement. l'appareil ne doit pas produire de brouillage, et l'utilisateur de l'appareil doit accepter tout brouillage radiolectrique subi, mme si le