X96 K E T R A C O N T R O L L E R Installation Guide Models HW-X96-X-J1 CM-X96-X-J1
! WARNING Shock Hazard. May result in Serious Injury or Death. Turn power OFF at circuit breaker or remove fuse. This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard (s). Operation is subject to the following two conditions:
(1) This device may not cause harmful interference
(2) This device must accept any interference received, including interference that may cause undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user's authority to operate this equipment. This equipment complies with FCC/ISED radiation exposure limits set for an uncontrolled environment. The user should avoid prolonged exposure within 7.9 in (20 cm) of the antenna, which may exceed the FCC/ISED radio frequency exposure limits. 277 V~ NOTE: This equipment has been tested at 277 V~ and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense. 120 V~ NOTE: This equipment has been tested at 120 V~ and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. 2|X96 INSTALLATION GUIDE P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. Cet appareil est conforme la partie 15 des rgles de la FCC. Le fonctionnement doit suivre les deux conditions suivantes :
(1) Cet appareil ne doit pas provoquer dinterfrences nuisibles.
(2) Cet appareil ne doit accepter aucune interfrence reue, y compris des interfrences qui pourraient provoquer un fonctionnement indsirable. Tout changement ou modification sans l'autorisation expresse de Lutron Electronics Co., Inc. pourrait annuler le droit d'utiliser cet quipement. Cet quipement est conforme aux limites dexposition aux rayonnements de la FCC/de lISDE tablies pour un environnement non contrl. Lutilisateur doit viter une exposition prolonge moins de 20 cm (7,9 po) de lantenne, ce qui peut dpasser les limites dexposition aux radiofrquences de la FCC/de lISDE. 277 V~ REMARQUE : Cet quipement a t test 277 V~ et est conforme aux limites dun appareil numrique de Classe A en vertu de la partie 15 des rgles de la FCC. Ces limites sont conues pour fournir une protection raisonnable contre les interfrences nuisibles lorsque lquipement est utilis dans un environnement commercial. Cet quipement gnre, utilise et peut mettre une nergie de frquence radio et, sil nest pas install et utilis conformment au manuel dinstruction, il peut provoquer des interfrences nuisibles aux communications radio. Lutilisation de cet quipement dans une zone rsidentielle est susceptible de provoquer des interfrences nuisibles, auquel cas lutilisateur sera tenu de corriger les interfrences ses frais. 120 V~ REMARQUE : Cet quipement a t test 120 V~ et est conforme aux limites dun appareil numrique de Classe B en vertu de la partie 15 des rgles de la FCC. Ces limites sont conues pour fournir une protection raisonnable face aux interfrences nuisibles dans une installation rsidentielle. Cet quipement gnre, utilise et peut mettre une nergie de frquence radio et, sil nest pas install et utilis conformment aux instructions, il peut provoquer des interfrences nuisibles aux communications radio. Cependant, il ny a aucune garantie que des interfrences ne surviendront dans une installation particulire. Si cet quipement provoque des interfrences nuisibles pour la rception radio et tlvisuelle, ce qui peut tre dtermin en allumant et en teignant lquipement, il est recommand que lutilisateur tente de corriger ces interfrences en utilisant une ou plusieurs des mesures suivantes :
Rorientez ou repositionnez lantenne rceptrice. Augmentez la sparation entre lquipement et le rcepteur. Connectez lquipement une prise lectrique se trouvant sur un circuit diffrent de celui o le rcepteur est connect. Demandez laide du vendeur ou dun technicien radio/TV expriment. 3|X96 INSTALLATION GUIDE P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. Included Components
( 1 ) X96 Ketra Controller Dimensions:
Length: 5 in (127 mm) Width: 5 in (127 mm) Height: 1.3 in (33 mm)
( 1 ) Type A Adapter Used to connect 4-wire cable to input of LS0 luminaire. See install guide P/N 3662562 for more information. Dimensions:
Length: 1.2 in (30.5 mm) Width: 0.7 in (17.8 mm) Height: 0.6 in (15.25 mm)
( 2 ) Mounting Screws Used to mount X96 Ketra controller to 4 in x 4 in
(101.6 mm x 101.6 mm) U.S. junction box. 8 32 X 1.5 in
#2 Phillips Drive Machine Screw Wire Gauge:
Signal Connections:
1824 AWG
(0.750.25 mm2) Power Connections:
1620 AWG
(1.00.5 mm2) Strip Length:
5/16 in (8 mm)
( 3 ) Wire Nuts Suitable for copper wire only. For aluminum wire consult an electrician. Listed as pressure type wire connector on the following solid and/or stranded combinations.
(1-3) 12 AWG (4.0 mm2)
(2-3) 14 AWG (2.5 mm2)
(1-2) 12 AWG (4.0 mm2) and
(1) 14 AWG (2.5 mm2)
( 1 ) X96 Ketra Controller Connector Used to connect 4- wire cable to ouput of X96 Ketra controller Plugged in Dimensions:
Length: 0.53 in (13 mm) Width : 0.6 in (15 mm) Height: 0.31 in (8 mm) Wire Gauge:
24 AWG to 16 AWG
(0.25 mm2 to 1.5 mm2)
(1-2) 12 AWG (4.0 mm2) and Strip Length:
(1) 16 AWG (1.5 mm2)
(1-2) 14 AWG (2.5 mm2) and
(1) 16 AWG (1.5 mm2) 3/8 in (10 mm)
(1-2) 12 AWG (4.0 mm2) and
(1) 18 AWG (1.0 mm2)
(1-2) 14 AWG (2.5 mm2) and
(1) 18 AWG (1.0 mm2) Strip Length:
7/16 in (11 mm) for 18 AWG and 16 AWG
(1.0 mm2 and 1.5mm2) wires 3/8 in (10 mm) for 14 AWG and 12 AWG
(2.5 mm2 and 4.0 mm2) wires X96 INSTALLATION GUIDE|4 INSTALLATIONP/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATION Electrical Specifications Output Input 21 V- Max 96 W to power LS0 luminaire 3.3 V- control signal to control light level and color temperature of LS0 luminaire 120/277 V~ 60 Hz Max 110 W Current 0.92 A/0.40 A 5|X96 INSTALLATION GUIDE P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. Electrical Specifications Pre-Installation Important Notes: Please read before installing. For installation by a qualified electrician in accordance with all local and national electric codes. Damage to this product caused by wiring with power on voids the warranty. Turn power off before installing. Use copper conductors only. For indoor use only. For use only with LS0 luminaires. DO NOT install if the product has any visible damage. If moisture or condensation is evident, allow the product to dry completely before installation. Operate between 32 F and 104 F (0C and 40C) ambient. 0% to 90% humidity, non-condensing. X96 INSTALLATION GUIDE |6 INSTALLATIONP/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATION P R E - I N S TA L L AT I O N Find a suitable mounting location:
Mount within wiring range of the LS0 luminaire. A total of 50 ft (15 m) of cable can be used, from the X96 Ketra controller to the last LS0 luminaire, including cabling in between luminaire segments. The X96 Ketra controller, a Clear Connect Type X device, must be mounted within 71 ft (21.5 m) of its assigned gateway. The X96 must have at least two non-battery-powered Type X devices with 25 ft
(7.5 m). Within a subnet, groups or clusters of Type X devices must not be separated by greater than 25 ft (7.5 m). The gateway and the Type X devices assigned to it must be on the same floor. Mount a minimum of 3 ft (1.0 m) away from interference sources in the 2.4 GHz band, including but not limited to microwaves, wireless access points, hotspots, baby monitors, thermostats, and voice recognizing control devices. Do not install the controller inside a third-party enclosure. Performance of Type X devices can severely degrade if installed inside metal enclosures. For additional guidelines regarding Type X devices, refer to Lutron Application Note #745 (P/N 048745) at www.lutron.com A minimum of 2 in (51 mm) of free space is required all around Figure 1 2 in
(51 mm) the controller. See Figure 1. Mount the controller in a position where it can be easily located and accessed if service or troubleshooting is necessary. Ensure that the reset button and output connector 7 in
(178 mm) 2 in
(51 mm) 4.5 in
(89 mm) can be accessed. See Figure 2. Ensure there is sufficient space above the junction box to drive the mounting screws and attach the top cover. Ensure that the junction box is rotated to allow the output wiring on the controller to route towards the first LS0 luminaire. 7|X96 INSTALLATION GUIDE 2 in
(51 mm) INSTALLATIONP/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATION P R E - I N S TA L L AT I O N Installation S T E P 1 Input Wiring (shown in Figure 2) NOTE: Branch wiring is permitted. 1. Bring mains supply wires through 4 in x 4 in (101.6 mm x 101.6 mm) U.S. junction box. 2. Connect the green ground wire on the controller to the green or bare ground wire in the junction box using the supplied wire nuts. 3. Connect the black wire on the controller to the Line/Hot wire in the junction box using Figure 1 4. Connect the white wire on the controller to the Neutral wire in the junction box using the supplied wire nuts. the supplied wire nuts. Figure 2 Output Connector Reset button:
Hold for 15 seconds to factory reset X96 controller. White Wire Black Wire White or Neutral Wire Black or Line/Hot Wire Green Wire Green or Bare Ground Wire X96 INSTALLATION GUIDE|8 INSTALLATIONP/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATIONINSTALLATION Mounting (shown in Figure 3) 1. Remove top cover to access the mounting holes. 2. Mount the X96 Ketra Controller as shown in Figure 3. 3. Snap top cover back onto controller. S T E P 2 Figure 3 9|X96 INSTALLATION GUIDE P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATION S T E P 3 Output Wiring (shown in Figure 4) 1. Strip the 4 wires in the 4-wire cable (QS-CBL(P)-M or eqv.) to 3/8 in (10 mm) . 2. Push wires into provided plug, positions per diagram below. Pos 1: Red (16 AWG [1.5 mm2]) Pos 2: Purple (22 AWG [0.5 mm2]) Pos 3: White (22 AWG [0.5 mm2]) Pos 4: Black (16 AWG [1.5 mm2]) 3. If needed, push release levers on output connector to remove wires . Figure 4 Wire Input Side Position 3 White | RS485-
Position 4 Black | COM Position 2 Purple | RS485+
Position 1 Red | V+
Release Lever X96 INSTALLATION GUIDE |10 P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATIONINSTALLATION Troubleshooting Ketras LS0 Linear should power on to a default white state. If it powers on to some other color, that means theres a problem in the installation conditions. See the table below for the meaning of each color. T R O U B L E S H O OT I N G TA B L E Color Condition Correction Red or OFF Voltage from X96 Controller is too low Ensure that the controller is the Ketra X96 controller. Check to see if total cable length exceeds 50 ft (15 m), reduce to 50 ft (15 m) of cable from X96 to last LS0 segment. Ensure that power conductors are 16 AWG or 12 AWG (1.5 mm2 or 3.5 mm2) wires, or use the QSH-CBL(P)-M-500 or QSH-CBL(P)-L-500. Ensure that length of LS0 linear does not exceed maximum length requirements i.e., 15 ft (4.5 m) for high output and 24 ft (7.3 m) for long run. Verify power connections (red and black on QSH-CBL-M-500) are wired correctly on the X96 controller and each luminaire adapter Disconnect power, check wiring at adapters and follow wiring directions above, or disconnect luminaire and reverse direction Verify communication (purple and white on QSH-CBL-M-500) are wired correctly on the X96 controller and each luminaire adapter Line voltage must be nominally 120 or 277 V~
60 Hz for X96 Remove excess luminaires and power cycle the X96 controller Magenta LS0 is installed backwards Blue Missing or reversed communication signals Green or OFF Line voltage is too low Yellow Number of luminaires exceeds length limits. Limit for 15 ft
(4.5 m) for high output and diffused lens type and 24 ft
(7.3 m) for long run lens type. 11|X96 INSTALLATION GUIDE P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. Warranty & Tech Support Limited warranty terms can be found at:
www.ketra.com/warranty For questions and technical support, please contact:
(844) 588-6445 ketrasupport@lutron.com Ketra and the Ketra logo are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. X96 INSTALLATION GUIDE|12 INSTALLATIONP/N 3662581 Rev X 2021 Lutron Electronics Co., Inc. INSTALLATION 6231 E. Stassney Ln. Bldg. 13, Suite 400 Austin, TX 78744 www.ketra.com 512.872.4349 P/N 3662581 Rev X 2021 Lutron Electronics Co., Inc.