Vive Sensor Dimmer / Switch Part of the Vive System 032515 Rev. A 06/2018 Please read before installing 010V- RF Sensor Dimmer MRF2S-8SD010 MRF2S-8SDV010 Vacancy Only Occupancy / Vacancy RF Sensor Switch MRF2S-8SS MRF2S-8SSV Vacancy Only Occupancy / Vacancy For set-up, programming, and troubleshooting with a Vive system, please refer to the installation instructions included with the Vive hub or at www.lutron.com h s i l g n E Lighting Electronic fluorescent ballast or LED driver 120 277 V~ 50 / 60 Hz 8 A Canada:
120 V~ 50 / 60 Hz 8 A Compatible Devices Works with all ballasts and drivers that provide a current source compliant to ANSIC137.1-201x 010 V. 010 V- Load Rating One sensor dimmer / switch can sink up to 50 mA of current. Controls up to 25 drivers or ballasts. ANSI C137.1-201x 010 V requires the driver / ballast to limit the current draw to 2.0mA maximum. Motion Coverage Major: 30 ft 30 ft (9 m 9 m) [900 ft2 (81 m2)]
Minor: 20 ft 20 ft (6 m 6 m) [400 ft2 (36 m2)]
Wireless Communication Range of wireless communication is 60ft (18m) line-of-sight or 30ft
(9m) through walls. of the room. Wireless communication is affected by the installation or physical setup Keep all wireless devices visible within the space. Do not place behind large furniture or appliances. Do NOT mount in a metal partition wall or metal power pole. Important Notes:
Neutral is required for product to function. If a neutral wire is not present, consult a licensed electrician. When power is applied, the sensor dimmer / switch can be manually turned on / off after the first 10 seconds and the sensor will automatically control the load after 2 minutes. The sensor requires an unobstructed view of the room and line-of-sight to detect motion. Hot objects or moving air currents can affect the performance of the sensor and may cause it to turn on unexpectedly or not function as desired. CAUTION: To reduce the risk of overheating and possible damage to other equipment, do NOT use to control receptacles. Class 2 / Class 1 wiring: Install in accordance with all national and local electrical codes. For indoor use only. Operate between 32F 104F (0C 40C), ambient. 0% to 90% humidity, non-condensing. Clean only with soft, damp cloth, no chemical cleaners. Start Here Customer Assistance | 1.844.LUTRON1 U.S.A. / Canada | +1.888.235.2910 Mexico | +1.610.282.3800 Others | www.lutron.com/support Wiring For more information and additional wiring instructions, visit: www.lutron.com/TechnicalDocumentLibrary/048687.pdf and/or www.lutron.com/TechnicalDocumentLibrary/3691097.pdf 1. Turn off power WARNING: Shock Hazard. May result in serious injury or death. Turn OFF power at circuit breaker or fuse before installing or servicing the unit. Programming with a Vive Hub 1. Use an iOSR or AndroidT compatible 2. Download the Lutron Vive app. 3. Open the app and follow device. the instructions. 2. Connect Wires a. Sensor Dimmer - Single Pole Wiring Line / Hot 120277 V~
50 / 60 Hz Canada:
120277 V~
50 / 60 Hz Black Black m30 15 5 1 Mode Occ Lrn Fixd Vac Alt PIR Hi Med Low Min Gray () Violet (+) Green Ground White Neutral b. Sensor Switch - Single Pole Wiring Line / Hot 120277 V~
50 / 60 Hz Canada:
120277 V~
50 / 60 Hz Black Black m30 15 5 1 Mode Occ Lrn Fixd Vac Alt PIR Hi Med Low Min Green Ground White Gray () Violet (+) Gray () Violet (+) White Black White Black White Black White Black Neutral Note: Program all desired settings before installing the wallplate. 3. Turn on power WARNING: Shock Hazard. Could result in minor or moderate personal injury. Ground connection required before connecting power 4. Wait 2 minutes The sensor dimmer / switch will manually control the load after the first 10 seconds. Once power has been restored, the sensor dimmer / switch will automatically control the load after the first 2 minutes. 5. Set desired settings (optional) See other side of sheet for details on how to select custom settings. FCC / IC - Supplier Declaration of Conformity This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause interference and (2) This device must accept any interference, including interference that may cause undesired operation. Modification not expressly approved by Lutron Electronics Co., Inc. could void the users authority to operate this equipment. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Ce dispositif est conforme la section 15 des rglements du FCC et des standards CNR exempt de licence dIndustrie Canada. L'opration est sous rserve des deux conditions suivantes :
(1) Cet appareil ne peut causer d'interfrence nuisible, et
(2) Cet appareil doit tolrer toute interfrence, mme celle pouvant affecter son fonctionnement. Tout changement ou modification sans l'autorisation expresse de Lutron Electronics Co., Inc. pourrait annuler le droit d'utiliser cet quipement. REMARQUE : Cet quipement a t test et jug conforme aux limites applicables aux dispositifs numriques Classe B, conformment la section 15 des rgles de la FCC. Ces limites sont conues pour procurer une protection raisonnable contre les perturbations nuisibles en application rsidentielle. Cet quipement gnre, utilise et peut radier l'nergie de frquences radiophoniques. S'il n'est pas install et utilis selon les directives, peut causer des interfrences radiophoniques nuisibles. Cependant, il ny a aucune garantie quaucune interfrence ne se produira dans une installation prcise. Si votre quipement produit de l'interfrence la rception radiophonique ou tlvisuelle, ce qui peut tre dtect en coupant et refermant l'alimentation au systme dclairage. Dans le cas dinterfrence, l'utilisateur sera contraint dessayer de corriger la situation par un ou plusieurs des moyens suivants :
Note: For further information on set up, programming, and troubleshooting with a Vive system, please refer to the installation instructions included with the Vive hub or visit www.lutron.com/vive Programming without a Vive Hub or in optional multi-location applications (associating wireless devices to sensor dimmer / switch) 1. Press and hold T for until the lights 2. Press and hold the wireless device button shown below until the lights flash (about 7seconds). flash (about 6seconds). T m30 15 5 1 Mode Occ Lrn Fixd Vac Alt PIR Hi Med Low Min Pico wireless control
(upto10) Radio Powr Savr daylight sensor
(1maximum) Radio Powr Savr occupancy / vacancy sensor
(up to 10) Link Test Note: To associate multiple wireless devices, repeat steps 1 and 2 above for each wireless device. Un-associating a wireless device from a sensor dimmer/switch 1. Rapidly tap the wireless device button three times and hold on the fourth until the lights begins to flash rapidly; release the button. Within 1 second of releasing the button, rapidly tap it three times again. 2. To test that the wireless device has been successfully un-associated, press Test or d and verify that the wireless device no longer controls the load. Link Test Link Test Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA Rorienter ou re-localiser l'antenne de rception Augmenter la distance sparant l'quipement et le rcepteur Brancher lquipement sur un circuit diffrent que celui sur lequel le rcepteur est branch Demander l'aide du distributeur ou d'un technicien expriment en radio et tlvision XViveX Vive Sensor Dimmer / Switch Part of the Vive System ALL PROGRAMMING IS OPTIONAL Programming is not required for default functionality For set-up, programming, and troubleshooting with a Vive system, please refer to the installation instructions included with the Vive hub or at www.lutron.com Default Settings Timeout: 15 minutes Sensor Mode: Occupancy (Auto-On / Auto-Off)1 PIR Sensitivity: High Occupied Level: 100%
Vacancy Level: 0%
Fixed ALD Level: Low (when in Fixed ALD mode) Check Current Settings2 To display the current settings, tap the Timeout (
), Sensor Mode ( M ), or PIR Sensitivity ( P ) button. The indicator LED ( IL ) that corresponds to the current setting will illuminate. Tapswitch
(on / off) T IL Indicator LEDs 2 Timeout 4 M Sensor mode 4, 7 Sensor LED
(behind lens) See Test Mode section. Maestro LEDs ML Raise 3 R L Lower 3 Alt Alt 2 P PIR sensitivity 4 PIR lens m30 15 5 1 Mode Occ Lrn Fixd Vac Alt PIR Hi Med Low Min Sensor dimmer shown 1 Sensor Mode is locked as Vacancy in vacancy only models (MRF2S-8SDV010 and MRF2S-8SSV). 2 Available in standalone. Not available when used in a Vive system. 3 Only available with the sensor dimmer. Not available with sensor switch. 4 Available in standalone. When the device is used in a Vive system, these adjustments are only available via the Vive software. 5 Learning ALD (Ambient Light Detection): Lights remain off if enough natural light is present. If the lights turn on and the user does not want that much light, they can tap T within 5seconds of entering the space. Similarly, if the lights do not turn on when entering a space and the user wants more light, they can tap T within 5seconds of entering the space. Over time, the sensor will learn the preferred light level. 6 Fixed ALD: Lights turn on only when there is less than a set (locked) amount of natural light available. The level can be adjusted in Fixed ALD Level settings. 7 This setting will override the sensor mode of the Radio Powr Savr occupancy / vacancy sensor. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA Default settings in bold Change Basic Settings Customer Assistance | 1.844.LUTRON1 U.S.A. / Canada | +1.888.235.2910 Mexico | +1.610.282.3800 Others | www.lutron.com/support 1. Press and hold the desired programming button (
2. Tap the same programming button to cycle to your desired setting. 3. Press and hold the same programming button until the IL turns solid (about 3seconds). The setting has been saved.
, M , or P ) until an IL flashes (about 3seconds). Timeout 4 30 minutes 15 minutes 5 minutes 1 minute M Sensor Mode 1
(determines when lights turn on) Occupancy (Auto-ON / Auto-OFF)4 Occupancy with Learning ALD 2, 5 Occupancy with Fixed ALD 2, 6 Vacancy (Manual-ON / Auto-OFF)4 P PIR Sensitivity 4 High Medium Low Minimum Test Mode Test mode has a short timeout (< 15 seconds) that will test the coverage of the sensor with the current settings. 1. Wait at least 2 minutes after power is turned on. 2. Press and hold T until the PIR lens flashes (about 3 seconds). 3. The device will exit test mode after 5 minutes of inactivity or when any button is pressed. The sensor LED behind the lens will turn on while occupied and turn off while vacant. Change Advanced Settings For complete programming options and additional information, visit www.lutron.com/TechnicalDocumentLibrary/048687.pdf High-End Trim 3, 4 100%
55%
Alt 1. Press and hold T and R until a ML flashes (about 6 seconds). 2. Press and hold R until the top ML is lit and the lights stop brightening. 3. Tap L until the desired level is achieved. Press and hold T until the ML stops flashing (about 6 seconds). Low-End Trim 3, 4 PIR Hi Med Low Min 1. Press and hold T and L until a ML flashes (about 6 seconds). 2. Press and hold L until the bottom ML is lit and the lights stop dimming. 3. Tap R until the lights are on and stable (no flickering) and the desired level is achieved. Press and hold T until the ML stops flashing (about 6 seconds). 45%
Alt 1%
PIR Hi Med Low Min Occupancy Level 3, 4 The level which the sensor dimmer turns on when motion is detected. This level is adjustable from 1% to 100% within the range of the low-end and high-end trims. 100%
1%
1. Press and hold M and R until a ML flashes (about 6 seconds). 2. Tap R or L until desired level is achieved. 3. Press and hold M until the ML stops flashing (about 6 seconds). Alt PIR Hi Med Low Min Vacancy Level 3, 4 The level which the sensor dimmer dims or turns off when motion has not been detected for the timeout period. This level is adjustable from 1% to 100% within the range of the low-end and high-end trims. 100%
0%
1. Press and hold M and L until a ML flashes (about 6 seconds). 2. Tap R or L until desired level is achieved. 3. Press and hold M until the ML stops flashing (about 6 seconds). Alt PIR Hi Med Low Min Fixed ALD Level 2 (MRF2S-8SD010 and MRF2S-8SS only) The light level that determines when a sensor will turn lights on or keep lights off when detecting occupancy. This setting only affects sensors set to Fixed ALD mode. m30 15 5 1 Mode Occ Lrn Fixd Vac m30 15 5 1 Mode Occ Lrn Fixd Vac m30 15 5 1 Mode Occ Lrn Fixd Vac m30 15 5 1 Mode Occ Lrn Fixd Vac 1. Press and hold M and Alt until an IL flashes (about 3 seconds). 2. The Fixed ALD light level will now be displayed by the IL . Tap M to cycle to the desired setting. 3. Press and hold M until the IL turns solid (about 3 seconds). High (turn ON lights unless area has a lot of light) Medium Low Minimum (turn ON lights only when room is dark) Walk-through Mode 2 Allows the lights to turn off before the Timeout has expired if occupancy is detected only briefly. m30 15 5 1 1. Press and hold 2. The walk-through setting will now be displayed by the IL . Tap Alt to cycle to the desired setting. 3. Press and hold Alt until the IL turns solid (about 3 seconds). and Alt until an IL flashes (about 3 seconds).
(unused)
(unused) Disabled Enabled Alt Electronic Off 2 Mode Affects how the lights are turned off. If enabled, the driver will still have power but the lights will be turned off. If disabled, the driver will Occ m30 Lrn not have power and the lights will be turned off. 15 Fixd 5 Vac 1 1. Press and hold 2. The electronic off setting will now be displayed by the IL . Tap M to cycle to the desired setting. 3. Press and hold M until the IL turns solid (about 3 seconds). and M until an IL flashes (about 3 seconds).
(unused)
(unused) Enabled Disabled PIR Alt Hi Med Low Min Mode Occ Lrn m30 Fixd 15 Vac 5 1 Lutron, Pico, Maestro, and Vive are trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. App Store is a service mark of Apple, Inc. Android and Google Play are trademarks of Google LLC. iOS is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license. Mode 2018 Lutron Electronics Co., Inc. Occ Lrn PIR Hi Alt Med Low Min PIR Hi Med Low Reset Factory Defaults Note: It may be necessary to reset the device to factory default settings. Before beginning, ensure the device is connected and powered. Note: Any associations or programming previously set up with the sensor dimmer / switch will be erased and will need to be re-programmed after resetting to factory defaults. 1. Rapidly tap T three times and hold on the fourth until the lights begins to flash rapidly; release T . 2. Within 1 second of releasing T , rapidly tap T three times again and the lights will flash slowly indicating that the device has been reset to factory defaults. Troubleshooting www.lutron.com/support Symptom Possible Causes and Solutions Lights can not be manually turned ON or OFF with the newly installed sensor dimmer / switch. Verify proper wiring. Neutral must be connected for product to function properly. Wait 10 seconds and try to turn ON or OFF again. Wireless device will not associate to a sensor dimmer / switch. Wireless device is out of range. Wireless performance is being affected by the physical setup of the space. See Wireless Communication section for more information. Not all of the sensor modes are available when programming. Lights do not automatically turn ON when space is occupied. Driver / ballast cannot be dimmed up or down. Lens flashes when trying to dim the lights. Sensor modes are limited for vacancy only models
(MRF2S-8SDV010 and MRF2S-8SSV). Device may be part of a Vive system. Sensor Mode is set to Vacancy (Manual-ON / Auto-OFF). The sensor dimmer / switch may be a vacancy only model
(MRF2S-8SDV010 and MRF2S-8SSV). The room may be too bright for the current light level setting for Fixed ALD Level. Verify proper connection of gray and purple wires. Driver / ballast does not comply with ANSIC137.1-201x 010V. See www.lutron.com/TechnicalDocumentLibrary/048687.pdf