Meazon DinRail 3-Phase Advanced NB Installation Guide 1 Table of Contents Features & Technical Specifications ...................................................................................................................... 2 General Installation instructions ........................................................................................................................... 5 Installation in a three-phase panel ....................................................................................................................... 6 CTs installation .............................................................................................................................................. 6 Power lines L1 L2 L3 installation ................................................................................................................... 7 Installation in a single phase Panel ....................................................................................................................... 8 Installation for loads more of 600A ...................................................................................................................... 9 External Power Relay installation examples ....................................................................................................... 10 3-phase Power Relay installation ................................................................................................................ 10 1-phase Power Relay installation ................................................................................................................ 11 Indication contact installation examples ............................................................................................................ 12 Brief description .......................................................................................................................................... 12 Night tariff indication example ................................................................................................................... 12 Miniature circuit breaker (MCB) indication example.................................................................................. 12 About Meazon ..................................................................................................................................................... 13 Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 2 Features & Technical Specifications Meazon has developed DinRail 3-Phase Advanced NB, a 3-Phase electricity meter capable of remote monitoring and controlling energy consumption of a household and/or an industrial building. It is a wireless metering system based on ZigBee Mesh network technology, featuring a unique design that combines low cost and high accuracy measurements. Every metering device on the ZigBee network is associated with a ZigBee gateway. The role of the gateway is to periodically collect all measurements, gathered by the devices, in order to forward them to the Meazon Cloud for storage and further analysis. Meazon Cloud gives users the ability to monitor the current energy consumption, set alarm rules, control their devices (on/off switching) and schedule them to operate in a desired pattern. Meazon DinRail 3-Phase Advanced NB is a rail-type device with small size (less than 2 din), which can be easily is capable of monitoring, measurement logging and controlling:
installed and up to three separate power lines / loads a three-phased load an entire electrical panel (either single-phase, dual-phase or three-phase) It comes with three current transformers to measure any electrical load without limitations. It can drive a cold junction where a Power Relay could potentially be connected and control (on/off) the power supply to a load. The Relays control logic can be externally driven using On/Off commands or internally using Meazon scheduling. Finally, Meazon DinRail 3-Phase Advanced NB is equipped with a general-purpose indication contact, operating under Neutral detection logic, which can be used as an extra useful information input to your system. Communication Specifications Communication protocol ZigBee NB-IoT (Optional) Frequency band 2.4GHz Data communication interval 1 second (default 5 minutes) Response in case of communication loss Yes (Rerouting through igbee) Security - Communication Encryption Yes (AES encryption 128 bits) Data Storage Up to 25 days Electrical Specifications Operating Voltage (*) /
Frequency Power loss Response 100-285 Vac / 45-65 Hz Automatic resumption of operation after power loss Electrical parameters measured Ranges of measured parameters Electrical measurements Irms, Vrms, Active Power & Energy, Reactive Power & Energy Voltage: 0 to 285 Vac between phase and Neutral (**) Current: up to 600Amps (More Amp available on request) Tolerance
+10% of nominal load (I) Accuracy of measurements
<1% of reading measurement error (***)
(*) Make sure your purchased DinRail 3-Phase Advanced NB meets your appliances Voltage
(**) At least one of the measured phases must have models nominal Voltage
(***) Accuracy refers to Electric Power Measurements Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 3 Mechanical and Environmental Specifications Current Transformers (CT) provided Power Consumption 5VA Dimensions (WxHxD) 29.3 x 86.2 x 62.7 in mm Mass 0.085 Kg Supply wiring requirements Operating Environment 16 or 18AWG Solid/ Stranded, torque 0.6Nm Temperature: -20C to 50C Relative Humidity: 10% to 90% RH CT 5, accuracy +1%
CT 63, accuracy +1%
CT 125, accuracy +1%
CT 300, accuracy +1%
CT 400A, accuracy +1%
CT 600A, accuracy +1%
Id L1 L2 L3 Connector 1 2 3 4 5 6 LED1 LED2 Electrical contacts Description Connector Phase L1 Phase L2 Phase L3 7 8 9 10 11 12 BUTTON Id RN
-
CTN Description Power Relay 100~285Vac Neutral NO Connect Current Transformer N Red Wire
(Optional) CTR1 Current Transformer 1 Red Wire CTR2 Current Transformer 2 Red Wire CTR3 Current Transformer 3 Red Wire Man/Machine interface Button B Neutral External Input N EI CTB Current Transformers Black Wires L1 L2 Relay On/Off Network status Device Status based on led indications L1-LED1 / L2-LED2 LED1 On LED1 Off Relay Switch On Relay Switch Off LED1 Slow Blinking Idle state, not associated with a network, waits for Man/Machine interaction LED1 Fast Blinking Beacon state, not associated with a network, in ready to join mode LED1 On/Off Normal operation, network associated, collecting measurements, Relay Switch On or Off LED2 Device communication status Both LEDS Off Device is not operating Both LEDS Blinking in different frequency Both LEDS Blinking at the same time Identifying state, network associated, collecting measurements, Relay Switch On or Off Operating error, device needs restart Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 4 FCC Information This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Safety Information Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Product may be cleaned with a clean soft towel. Do not use liquids to clean. Product is not water resistant. If the unit gets wet, do not touch it. Power off and allow it to dry thoroughly before further operation. Do not disassemble the product. There are no spare parts for this, it is not repairable. If physical damage to the product occurs, do not use. Replace with a new one. Meazon DinRail 3-Phase Advanced NB Dimensions RF exposure warning :
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment shall be installed and operated with minimum distance 20cm between the radiator & body. Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 5 General Installation instructions INSTALLATION REQUIREMENTS The instructions provided below, should be performed only by licensed electricians. Installation from non-
qualified individuals may lead to electrocution or heavy damage to the devices. Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 6 Wiring requirements: 16 or 18AWG Solid/ Stranded, torque 0.6Nm. Make sure that the maximum amperage to be measured does not exceed the maximum value the provided Meazon DinRail 3-Phase Advanced NB can measure. Meazon DinRail 3-Phase Advanced NB must be protected with a circuit breaker (2A recommended, 10A Max)
(3 pieces for 3-phase electrical panels, 1 piece for single-phase electrical panels). 1) Locate the main electrical panel. 2) Turn the power off for safety reasons. 3) Locate the current conductors to be measured. Current transformers will be added at those conductors WARNING! Current conductors should be between the electrical fuse and the circuit breaker (in case of metering electrical loads separately), or between protection relay and electrical fuse (in case of measuring total consumption). 4) Check inside the electrical panel for the optimal location to place the Meazon DinRail 3-Phase Advanced NB and the 2A protective circuit breaker. 5) Place the protective circuit breaker at the rail. 6) Place the DinRail having the protection clip downwards and lock it at the rail of the electrical panel In this installation guide DinRail 3-Phase Advanced NB will be called DinRail for brevity reasons. Installation in a three-phase panel CTs installation Connect each of the three Current Transformers outputs (black wire) to contact 6 (CTB) of the DinRail. Connect each of the three Current Transformers inputs (red wire) to contact 10 (CTR1), 11 (CRT2) and 12(CRT3) of the DinRail respectively. Locate the current conductors to be measured starting from phase L1 and pass it through the coil of the CT (current transformer) by opening the coil of CT. Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 7 Close the CTs coil again. The red wire of this CT must be connected to contact 10 (CTR1) of the DinRail. WARNING! Make sure the direction of the arrow illustrated at the CT terminals to the load. Reconnect the current conductor. Repeat the process for the other two phases (L2, L3). Power lines L1 L2 L3 installation Power the 2A protective circuit breakers from the main circuit breakers of the electrical panel Connect the output of each of the above circuit breakers with the terminal 1(L1), terminal 2(L2) and terminal 3(L3) respectively of the DinRail. WARNING! Make sure that the sequence of phases 1, 2 and 3 of the DinRail is strictly L1, L2 and L3, otherwise measurements will be incorrect. Connect the neutral conductor of the electrical panel to contact 4(N) of the DinRail. Check the entire procedure again before completing the installation (sequence of the phases of the inputs of the DinRail, sequence of the Current Transformers connection, direction of the arrow of each CT). Upon completion of the electrical installation of DinRail, the electrical panel should appear as below:
Electrical Panel with DinRail 3-Phase Advanced NB in a 3-Phase Panel Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 8 Installation in a single-phase Panel WARNING! You can measure up to three (3) different loads. To do this, follow the instructions of 3-phase installation above. The terminals 1(L1) 2(L2) - 3(L3) must be bridged when the device is installed on single phase panel even if only one CT is used. Electrical Panel with DinRail 3-Phase Advanced NB at Single-Phase Panel Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 9 Installation for loads more than 600A WARNING! The following instructions relate only for DinRail version 5A. Using 5A version you can monitor high current electrical loads using the existing CTs xx/5A of the installation. PRECONDITION! The electrical installation must include current transformers with secondary winding current max output 5 Ampere. Follow the instructions of 3-phase installation above. Connect a wire to the -K- output of the secondary winding of phase L1 current transformer. Pass the wire through the coil of our DinRails current transformer provided (the red wire of this CT must be connected to contact 10 -CTR1- of the DinRail). The arrow illustrated on our CT must have K-
to-L direction. Connect the remaining edge of wire to the -L- input of the secondary winding of phase L1 current transformer. Repeat the process for the other two current transformers. Electrical Panel with DinRail 3-Phase Advanced version 5A in a 3-Phase Panel Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 10 External Power Relay installation examples WARNING! Use Power Relays with coil less than 50 VA. 3-phase Power Relay installation Place Power Relay at the rail. Disconnect the conductors from the loads to be controlled and connect them to the power input connectors of the Power Relay. Connect the power outputs of the Power Relay to the loads with the same order. Connect a conductor from any phase to the Power Relays Coil input connector. Connect a conductor from the Power Relays Coil output connector to the DinRail terminal 7 (RN). Electrical Panel with DinRail 3-Phase Advanced NB at a 3-Phase Panel and external 3-phase power relay Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 1-phase Power Relay installation 11 Electrical Panel with DinRail 3-Phase Advanced NB at a single-Phase Panel and external single-phase power relay Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com 12 Indication contact installation examples Brief description DinRail 3-Phase Advanced NB connector 5 (EI) is a general purpose indication contact that can be used as a useful information input to your system, under certain circumstances. It operates under Neutral detection logic. The usage of this contact is shown on the following examples. Night tariff indication example Connect a conductor from the output of the night tariff indication led to the DinRails connector 5 (EI). The picture in the right shows how to connect night tariff indigation. DinRail would inform your system for the status of night tariff change (enabled or disabled) in your appliance. Miniature circuit breaker (MCB) indication example WARNING! The following connection would have effect only for loads that include Neutral connection. It would not have any effect e.g. for 3-phase loads without neutral. WARNING! The following connection would have effect only for operating loads. If a load has been stopped e.g. by a switch, DinRail would not detect any change of the MCB. Connect a conductor from the output of the MCB to the DinRail connector 5 (EI). The picture in the right shows how to connect MCB indigation. DinRail would inform your system for the status of MCB change (enabled or disabled) in your appliance. Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com Disclaimer 13 The material in this manual is for informational purposes only. The products it describes are subject to change without prior notice, due to the manufacturers continuous development program. Meazon S.A. shall not be liable for any damages, losses, costs or expenses, direct, indirect or incidental, consequential or special, arising out of, or related to the use of this material or the products described herein. About Meazon Meazon acts as a catalyst to the energy efficiency market. We design and manufacture revolutionary small size energy meters and integrate them with cloud technology. We build on open standards and provide insights in energy consumption of commercial and residential buildings. This way we drive significant energy efficiencies. For more information visit www.meazon.com. Contact Information 57 New National Road of Patras Athens, 26442, Patras, Greece Telephone: +30 2610 430000 24 Fokidos Str., 15126, Ampelokipoi, Athens, Greece Telephone: +30 210 8020205 E-mail:info@meazon.com Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com Copyright 2014, MEAZON S.A. 14 Meazon Electronic Systems S.A., 57 N.E.O Patron - Athinon Str. , 26442, Patra, Greece info@meazon.com support@meazon.com +30 2610 430000 www.meazon.com