all | frequencies |
|
|
|
|
|
exhibits | applications |
---|---|---|---|---|---|---|---|---|
manual | photos | labels |
app s | submitted / available | |||||||
---|---|---|---|---|---|---|---|---|
1 |
|
Manual | Users Manual | 895.86 KiB | March 02 2015 | |||
1 |
|
Internal Photos | Internal Photos | 2.27 MiB | March 02 2015 | |||
1 |
|
External Photos | External Photos | 372.01 KiB | March 02 2015 | |||
1 |
|
Label | ID Label/Location Info | 213.92 KiB | March 02 2015 | |||
1 |
|
Label and Location | ID Label/Location Info | 216.23 KiB | March 02 2015 | |||
1 |
|
Agent Auth | Cover Letter(s) | 133.81 KiB | March 02 2015 | |||
1 |
|
Antenna Spec | Cover Letter(s) | 71.52 KiB | March 02 2015 | |||
1 |
|
Correspondence | Cover Letter(s) | 106.11 KiB | March 02 2015 | |||
1 |
|
Family Channel Dwell Time | Cover Letter(s) | 220.27 KiB | March 02 2015 | |||
1 |
|
Long Term Confidentiality | Cover Letter(s) | 110.09 KiB | March 02 2015 | |||
1 | RF Exposure Info | June 02 2015 / March 02 2015 | ||||||
1 |
|
Short Term Confidentiality | Cover Letter(s) | 125.35 KiB | March 02 2015 | |||
1 | Test Report | March 02 2015 | ||||||
1 | Test Report | March 02 2015 | ||||||
1 | Test Setup Photos | March 02 2015 |
1 | Manual | Users Manual | 895.86 KiB | March 02 2015 |
Packet Power Smart Power Cable Users Manual Version 1.5 Packet Power, LLC 233 Park Avenue, Suite 203 Minneapolis, MN 55415 1-877-560-8770 Email: info@packetpower.com www.packetpower.com Indicates a POTENTIAL HAZARD. Consult documentation carefully. CAUTION Read all instructions carefully prior to installation. Smart Power Cables should only be connected to the type of power source indicated on the label. protector. Adhere to voltage and amperage guidelines and utilize a proper branch circuit No field-serviceable parts. Do not attempt to disassemble the product as potentially severe electrical shock may result. Installation and maintenance must be performed by qualified personnel. Follow basic safety precautions to reduce the risk of electrical shock and damage to equipment. Store in a clean, dry location. Clean with a dry cloth. Intended for indoor use only, do not install in a wet location. Adhere to all local electrical codes and guidelines. Failure to use the product in the specified manner may lead to injury or death and damage to equipment. REGULATORY INFORMATION This product has been certified to meet the following requirements:
UL / ANSI standards 61010-1,Second Edition, Dated July 12, 2004 with revisions through and including October 28, 2008 CAN/CSA-C22.2 No. 61010-1, second edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements. Council Directive 2006/95/EC (December 12, 2006) on Low Voltage Equipment Safety; IEC 61010-1:2001 (Second Edition) and EN 61010-1:2001 (Second Edition) Council Directive 1999/05/EC - European Union (EU) Radio & Telecommunications Terminal Equipment Directive
(R&TTE) ETSI EN 300 220-2, Issued:2006/04/01 and ETSI EN 301 489-3, Issued:2002/08/01 V1.4.1 Council Directive 2004/108/EC (December 15, 2004) on Electromagnetic Compatibility CENELEC EN 61326-1 Issued:2006/05/01; IEC 61326-1:2005;:1997 AS/NZS 4268: 2008 Class B Device Statement / FCC Regulations:
Section 15.105(a) of the FCC Rules: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Section 15.19 of the FCC Rules: This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Pursuant to Part 15.21 of the FCC Rules, any changes or modifications to this product not expressly approved by Packet Power LLC might cause harmful interference and void the FCC authorization to operate this product. Pursuant to part 2.1091c of the FCC rules device is categorically excluded from routine RF Exposure regulations. Industry Canada (IC) Compliance Statement This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication. Per section RSS-102, 2.5 of Industry Canada regulations, this device is categorically excluded from Routine Evaluation Limits. Industrie Canada (IC) Dclaration de conformit Le prsent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorise aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radiolectrique subi, mme si le brouillage est susceptible d'en compromettre le fonctionnement. Conformment la rglementation d'Industrie Canada, le prsent metteur radio peut fonctionner avec une antenne d'un type et d'un gain maximal (ou infrieur) approuv pour l'metteur par Industrie Canada. Dans le but de rduire les risques de brouillage radiolectrique l'intention des autres utilisateurs, il faut choisir le type d'antenne et son gain de sorte que la puissance ipoosotrope rayonne quivalente (p.i.r.e.) ne dpasse pas l'intensit ncessaire l'tablissement d'une communication satisfaisante. Packet Power Smart Power Cable Users Manual Safety summary and specifications This manual is intended for use by personnel responsible for installing or removing the Smart Power Cables. Packet Power LLC assumes no liability for users failure to comply with these safety guidelines. Please read this manual carefully before proceeding. This symbol is used throughout this manual to indicate critical safety information. Failure to observe the information following this symbol may result in injury or death. Smart Power Cables should only be connected to the type of power source indicated on the label. Do not overload a Smart Power Cables as this can result in a risk of fire or electrical shock. circuit protector. Cables shall be connected according to their amperage ratings to a proper branch Cables must be connected to a terminal that is compatible with the connector on the cable and has the appropriate electrical rating. Cables must be connected to a grounded (earthed) outlet. Adhere to all local and national electrical codes and guidelines. Prior to installation, check to make sure the Smart Power Cable has not been damaged. Store in a clean, dry location. Intended for indoor use only. Do not install in a wet location. No field-serviceable parts. Do not attempt to disassemble the product as potentially severe electrical shock may result. Installation and maintenance must be performed by qualified personnel. Failure to use the product in the specified manner may lead to injury or death and damage to equipment. The R Model Smart Power Cables will support three-phase or single-phase power. Please note carefully the type of power your cable is designed to support as indicated on the cables label. Use only with the indicated type of power. Copyright 2012 Packet Power, LLC. 1 Packet Power Smart Power Cable Users Manual Contents Safety summary and specifications ......................................................................................... 1 Contents .................................................................................................................................. 2 Chapter 1: Introduction ............................................................................................................ 3 Smart Power Cable Overview ............................................................................................. 3 Service types ................................................................................................................... 3 Communication ............................................................................................................... 4 Packet Power Monitoring Solution Overview ...................................................................... 4 Wireless Monitoring Nodes ............................................................................................. 4 Software .......................................................................................................................... 4 Chapter 2: Installation ............................................................................................................. 7 Installing the Cables ............................................................................................................ 7 Smart Power Cable Indicator Lights and LED Display .................................................... 9 Installing the Wireless Ethernet Gateway ........................................................................... 9 Gateway Placement ........................................................................................................ 9 Gateway Types ............................................................................................................. 10 Gateway Node Capacity ............................................................................................... 10 Updates ......................................................................................................................... 10 Security ......................................................................................................................... 10 Ethernet Gateway Setup ............................................................................................... 10 Menu Access and Navigation ........................................................................................ 11 Gateway Menu Tree ...................................................................................................... 11 Setting an IP Address ................................................................................................... 12 The Ethernet Gateway Console .................................................................................... 12 Chapter 3: Technical Specifications ...................................................................................... 14 Communications ........................................................................................................... 14 Environmental ............................................................................................................... 14 Outputs .......................................................................................................................... 14 Outputs .......................................................................................................................... 14 Size and Weight ............................................................................................................ 14 Models ........................................................................................................................... 15 Connector Types ........................................................................................................... 15 Communication ................................................................................................................... 5 Copyright 2012 Packet Power, LLC. 2 Packet Power Smart Power Cable Users Manual Chapter 1: Introduction Smart Power Cable Overview Service types Smart Power Cables are power cables with embedded wireless power monitors that transmit real time power and energy usage data wirelessly to a central Gateway module. The Smart Power Cable is a monitoring-only device and it cannot disconnect, switch or otherwise interfere with the electrical current flowing through the cable and is inherently failsafe with a no risk of interrupting the circuit in the event of failure to the monitoring device. The monitoring mechanism is powered from the cable itself and consumes less than 0.6W of power. The cables are provided in an S (single phase) and R (three phase and high current single phase) form. Panel-mounted P models (independent power monitors with no cable assembly) are covered in a separate manual. The appropriate Smart Power Cable is selected based on the appropriate voltage, current and connector type shown in the chart below. Smart Power Cables are available in just about any connector type and are universally operational at 50/60 Hz. Figure 1: R Cable Figure 2: S Cable S Model Cables Voltage 1 120VAC 1 120VAC 1 200 to 240VAC 1 200 to 240VAC 1 120VAC 1 200 to 240VAC 1 200 to 240VAC 1 120VAC 1 208VAC 1 200 to 240VAC Amperage 10 amps or under 15 amps or under 15 amps or under 16 amps or under 20 amps 20 amps 20 amps 30 amps 30 amps 32 amps R Model Cables Voltage 1 120VAC 1 208 to 240VAC 1 200 to 240VAC 1 240VAC 3 Wye 120V/208V 3 Wye 120V/208V 3 Wye 120V/208V 3 Wye 120V/208V 3 Delta 120/208VAC 3 Delta 120/208VAC 3 Wye either 240/415VAC or 200/346VAC 3 Wye either 240/415VAC or 200/346VAC Amperage 50 amps 50 amps 60 amps 63 amps 20 amps 30 amps 50 amps 60 amps 30 amps 60 amps 16 amps 32 amps Copyright 2012 Packet Power, LLC. 3 Packet Power Smart Power Cable Users Manual 3 Wye either 240/415VAC or 200/346VAC 63 amps Cables should only be connected to the type of power source indicated on the label. If you are unsure of the type of power supply, consult an electrician or the power company. Refer to the highlighted section on the label to confirm the current and voltage rating. Communication The Smart Power Cables incorporate Packet Powers advanced zero-configuration wireless mesh networking technology to transmit power measurement data. Data is sent across the wireless network to the Packet Power Ethernet Gateway which connects using a standard Ethernet port to the customers wired network infrastructure. Packet Power Monitoring Solution Overview The overall Packet Power system consists of the following components:
Wireless Monitoring Nodes Wireless Power and Environmental Monitors including:
o Smart Power Cables that can record true power usage and monitor temperature readings in real time integrated in a cable format o Environmental Monitors that record up to 12 temperature channels, humidity and differential pressure o Current Monitors that record up to six channels of current o Power Monitors that can record true power usage and monitor temperature readings in real time One or more of the Packet Power Ethernet Gateways that can gather data from hundreds of monitoring devices via a wireless mesh radio network. The Ethernet Gateways form the bridge between the wireless monitoring network and the facilitys LAN. Software Customers can choose either to use Packet Powers monitoring applications or connect the wireless monitoring system to an existing monitoring system:
Figure 3: Ethernet Gateway Copyright 2012 Packet Power, LLC. 4 Packet Power Smart Power Cable Users Manual o Packet Powers EMX monitoring portal provides access to real-time information on power, energy and environmental usage along with data analysis and reporting tools that can be easily customized. The Power Manager product compliments the portal and adds tools specific to advanced data center monitoring. Packet Powers applications can be accessed from a cloud-based service or installed at a customer site. Figure 4: The EMX portal provides detailed energy use reporting and energy and power usage data along with alarm capabilities. o Certain models of the Ethernet Gateway provide protocol conversion and management capabilities allowing applications that can accept data in the SNMP or Modbus TCPIP protocols to access data from the wireless monitoring devices. A Smart Power Cable communicates with other cables and a Gateway using Packet Powers wireless mesh network. As soon as a Smart Power Cable is plugged in, it automatically tries to join the wireless network. If you already have an operating Packet Power network within your facility, information from a newly installed Smart Power Cable will become available shortly after it is plugged in. If you do not yet have a Packet Power network operating within your facility, please refer to the gateway section of the manual for additional information regarding wireless gateway and software setup. Communications Information gathered by a power cable is transmitted via a Packet Power radio network operating at either 900 MHz or 2.4 GHz (the exact frequencies vary with region please contact Packet Power for details). The network operates in a mesh topology. Each device in the network must be within range of at least one other device (either another monitoring node or the Gateway) in the network. The effective range of the radio in the Smart Power Cables varies depending on several factors, including the environment in which the product is used. Typically, each device has an effective range of 20 to 50 meters. The Smart Copyright 2012 Packet Power, LLC. 5 Packet Power Smart Power Cable Users Manual Power Cable will not transmit effectively if it is installed in an enclosure that entirely blocks radio signals such as fully enclosed metallic enclosures. Every site where a Smart Power Cable is deployed must have installed at least one compatible Packet Power Gateway device and associated software to collect data and prepare it for transmission to approved monitoring and analysis applications. It is not necessary for all cables to communicate directly with the Gateway. As long as each cable can communicate with at least one other cable, and one cable can also communicate with the Gateway, information from all cables will reach the Gateway. The rate at which power monitoring information is gathered from a cable depends primarily on the ratio of the number of cables to the number of gateways. As an example, at a ratio of 100 cables per Gateway, a Gateway should read from each cable every 5 to 15 seconds. The system will automatically reallocate network traffic across Gateways when new Gateways or devices are added. Note: In the event of a loss of power to a power cable, energy consumption information (Wh) is retained in non-volatile memory and will be transmitted when power is restored. Figure 6: Packet Power Communications Architecture Copyright 2012 Packet Power, LLC. 6 Packet Power Smart Power Cable Users Manual Chapter 2: Installation Installing the Cables 1 Confirm that the cable is correctly rated for the power and voltage. 2 3 4 5 Make sure that any devices that may be interrupted by the process are safely powered down. While Smart Power Cables can be plugged into an energized source, It is recommended for that if possible, the power source energizing the Smart Power Cable be turn-off during installation. Remove any existing power cables Plug-in the supply-side (plug or male) connector of the Smart Power Cable into to the power source. (1) Connect the load side (receptacle or female) connector of the Smart Power Cable to the load device or power strip. (2) 6 If the source power was disconnected, reconnect the source power. Copyright 2012 Packet Power, LLC. 7 7 Packet Power Smart Power Cable Users Manual The cable should now be energized and the indicator lights and LED display will be active. The Smart Power Cable will immediately attempt to join the wireless network (if available) and transmit power data. 8 Power up any devices. DISCLAIMER Installation of Packet Power monitoring cables involves the disruption of power flow to your devices. Disconnecting power supply cables on running computing equipment and other electrical devices may lead to interruption of service, data loss, equipment damage and other potential losses. Packet Power is not responsible for any losses incurred due to power interruptions during the installation process. The customer is responsible for understanding and mitigating any consequences of interrupting and re-starting power flow to any equipment during the installation process. Installation should only be performed by personnel otherwise authorized to manage power connections to the equipment to be monitored. Dual-powered (A & B) devices can in some cases be connected live, with one side (e.g. A) being replaced first, followed by the other side (e.g. B). However, any time one of the power supplies is disconnected, the redundancy of a dual power supply and all of the protections it provides against failure are compromised. You are responsible for completely understand-ing this risk and taking responsibility for any consequences of a power loss while connecting power cables. Copyright 2012 Packet Power, LLC. 8 Packet Power Smart Power Cable Users Manual Smart Power Cable Indicator Lights and LED Display All Smart Power Cables have three large alpha-numeric LEDs that provide for local display of monitoring data and three small lights adjacent to the LEDs that provide operating status information.
`
Installing the Wireless Ethernet Gateway Each location in which Smart Power Cables are deployed must have one or more Packet Power Ethernet Gateway(s) to gather data from the Smart Power Cables. The Ethernet Gateway version 3 is the central Gateway by which all Packet Power monitoring nodes (environmental and power) communicate. The following instructions are intended to provide a high level overview of how to commission a Gateway module. Refer to the support section of www.packetpower.com for additional support. Gateway Placement Gateway placement is critical. Gateway module(s) should be located 10-30 meters / 30-100 feet from one or more monitoring nodes (ideally line of site). The network is designed as a mesh network which means that the signal for distant nodes can be relayed through adjacent nodes until reaching Copyright 2012 Packet Power, LLC. 9 Packet Power Smart Power Cable Users Manual nodes in good radio proximity to the Gateway. Refer to the Gateway Placement manual on the support section of the website for additional details. Locate the gateway at a height above monitoring nodes when possible in a location with the best line of sight view of monitoring nodes. Do not locate inside metallic cabinets or directly on metal surfaces Use the Gateway mounting bracket for optimal placement and signal strength. Redundant Gateways are advised for any critical environment; additional Gateways should be placed in midway or in the opposite end of the device constellation when possible. Gateway Types There are various Gateway models. These include the standard Gateway designed to communicate exclusively with the Packet Power EMX portal, Modbus TCP/IP output versions (enterprise and solo), and SMNP output versions (solo and enterprise). All Gateway versions can communicate with the EMX portal simultaneously (i.e. a Modbus version can provide ModBus TCP/IP output as well as communicate with the EMX portal simultaneously). Gateway Node Capacity One Gateway can support up to 300 nodes (node count will affect polling time). The network is self-
configuring and will auto recognize new nodes added. Multiple Gateways can be used within a network for capacity or redundancy and will automatically load balance the nodes. Updates The Gateway and Smart Cable firmware is capable of being remotely updated over the network. Consult the support section of the website for additional details. Security The Packet Power network is designed to be the most secure monitoring system available with many inherent security features exclusive to the architecture that limit any possibility of penetration through the wireless nodes onto the host network. Additionally the Gateway can be equipped with 128 bit encryption. Refer to www.packetpower.com for additional explanations on security architecture. Ethernet Gateway Setup Connect the Gateway to a router (using a standard network cable) with network access using the Ethernet port on the back of the Gateway. Connect the power supply provided or any 5 VDC source to the DC input of the Gateway. The Gateway can be powered using PoE (Power over Ethernet) using a splitter and 5VDC PoE source. Copyright 2012 Packet Power, LLC. 10 Packet Power Smart Power Cable Users Manual Once energized the Gateway will indicate its firmware version, then device ID number (also found on the top label of the Gateway) followed the IP address (may be blank if operating DHCP mode); note that the IP address may take up to two minutes to display. POWER UP DISPLAY SEQUENCE FIRMWARE Menu Access and Navigation To access the menu for the Gateway, press and hold the selector button on the back of the device for three seconds. To navigate the menu, use short clicks of the selection button; to change a setting or advance into a menu item press and hold the button. The menu tree is shown in the table below. IP ADDRESS DEVICE ID Gateway Menu Tree SET IP ADDRESS DHCP [ON]
DHCP [OFF]
UPDATE IP NETMASK GATEWAY TFTP DOWNLOAD RESTORE FACTORY SETTINGS RESET TEST PIN IP NETMASK GATEWAY DNS REBOOT EXIT - HOLD BUTTON TO EXIT WILL INDICATE DEVICE IS REBOOTING Copyright 2012 Packet Power, LLC. 11 Packet Power Smart Power Cable Users Manual Setting an IP Address To configure the IP address of the Gateway, enter the setup menu by pressing and holding the selection button for three seconds. Use short clicks of the button to advance through the menu until the [-> Set IP] option appears. Click and hold [-> Set IP]. The LCD will show DHCP:On -or- DHCP:Off. Click and hold the button to toggle between DHCP on and off. To set a static IP address click and hold DHCP:Off. The display will then show CP: Off <- . Click and hold the button and the IP address will appear. Use short clicks to scroll through specific digits of the IP address. Click and hold the button to change the underlined number of the IP address. Once the correct IP address is entered you can exit the IP address console by advancing to the end of the screen and holding the selector button when the back arrow character <- is highlighted. To properly configure the IP address, the Gateway, Netmask and DNS server address must also be entered. To change these parameters use the same menu navigation style as described above. After the DNS Server address is set you will need to reboot to have implement your changes. Do this by pressing HOLD when Reboot is displayed. Booting will show on the display while the unit reboots and implements your changes. To leave the configuration menu without having changes take effect, click and HOLD the Exit. You can find additional information, including details on the SNMP MIB and Modbus register map, at www.packetpower.com/support. Please see www.packetpower.com/support for detailed information on SNMP and Modbus connectivity. Contact support@packetpower.com for additional assistance. The Ethernet Gateway Console In about the technical status of an Ethernet Gateway is accessible from the Gateway Console. This can be accessed by entering the Gateways IP address in any web browser. Copyright 2012 Packet Power, LLC. 12 Packet Power Smart Power Cable Users Manual Note: the MAC address of the Gateway will be the last 12 digits of the 16-digit ID number indicated on the Gateways label. The information available from the Console includes:
Information on the status of the device, including its name and IP address and whether it is set to communicate to the Packet Power cloud service or transmit data in SNMP format locally. Data on which monitoring devices the Gateway is communicating with and the amount of time that has elapsed since it last communicated with each device. Configuration options for the Gateway and information used by Packet Power technical support to help in problem determination. Detailed information on the Ethernet Gateway, including initial configuration instructions, can be found at www.packetpower.com/support. Please contact support@packetpower.com with any questions and include a snapshot of the information listed under the debug tab when requesting technical support. Copyright 2012 Packet Power, LLC. 13 Packet Power Smart Power Cable Users Manual Chapter 3: Technical Specifications Communications Operating frequency Wireless protocol Wired network protocol From 860, 930MHz and 2.4 GHz. Specific frequency used varies by region. Proprietary frequency hopping, self-configuring, load-balancing mesh network TCP/IP (one IP address needed per Gateway), support for Modbus TCP/IP and SNMP protocols Wireless 10 to 50 meters indoors from any one device to any other transmission Firmware updates Typical range Antenna Cable to Gateway ratio Multi-site support Encryption Environmental Operating temperature Operating humidity Water and dust resistance Max. operating altitude Power usage Outputs LED status indicators Local display Monitored points Outputs LED status indicators Local display Monitored points Size and Weight S Models under 16A S Models 16A and above R Models P Models Enclosure material Power cords Fully enclosed, fixed configuration Up to 300 cables per gateway (unlimited Gateways per system) Yes Optional 128-bit
-7 to +45C (+20 to +113F) 5% to 95% non-condensing Indoor applications 3,300 meters (10,000 feet) Smart power cable: 0.6W Ethernet Gateway: 0.7W Power (Red / Orange), Status (Red/Orange), Communications (Green) 3 Digit LED (cycles Amps, Volts, Watts by phase); user definable Voltage (V), Current (A), Power (W), Energy (Wh), Apparent Power (VA), Power Factor (PF), Frequency (Hz), Internal Temperature; all measurements +/- 1%, Temperature (+/-2C) Power (Red / Orange), Status (Red/Orange), Communications (Green) 3 Digit LED (cycles Amps, Volts, Watts by phase); user definable Voltage (V), Current (A), Power (W), Energy (Wh), Apparent Power (VA), Power Factor (PF), Frequency (Hz), Internal Temperature; all measurements +/- 1%, Temperature (+/-2C) 150 cm (60 in), 0.45kg (1 lbs) 120 cm (48 in), 0.75 1.0kg (1.5 to 2 lbs) Approximately 120 cm (48 in), 1.5 to 3 kg (3.5 to 7 lbs) Varies see product manual High-impact resistant Lexan, V0 flammability rating Each cord carries standard industry markings that describe its intended operating environment and power type Copyright 2012 Packet Power, LLC. 14 Packet Power Smart Power Cable Users Manual Models Model S and R Wireless PDU Connector Types Model S (all single phase) Voltage (V) 120, 208-240 120 / 208, 240 / 415 120, 208, 120 / 208 NEMA 5-15 / L5-15 5-20 / L5-20 L5-30 6-15 / L6-15 6-20 / L6-20/L6-30 R single phase IEC 60320 C13 / C14 60320 C19 / C20 60309 2P+E 6h R 3-phase Wye L21-20, L21-30 60309 3P+N+E 6h R 3-phase Delta Amperage (A) 10, 15, 16, 20, 30, 32 16, 20, 30, 32, 50, 63, 100 Three-phase L-L and L-N 20,30, 60 phase, Three-
Type Single phase Single phase L-L and L-N Other Schuko CEE7-7, AS/NZA 3112 2000, BS 1363A
(UK), BS 546A (India, S Africa), Whip, others on request CS6361/6360, CS8264/8265 360_6W, 3720/3913, 3750/3933, 3720U-1/
3913U-1, 3720U-2/3913U-
2, 9_23U2, 9_23U0, 9_33U0, 9_53U2, 9_63U2 516_6W, 532_6W, 530_6W, 560_6W, 563_6W 420_9W, 430_9W, 460_9W, 9_54U2, IBM D/3760, 3934, CS8365/8364, 7428, and others on request Copyright 2012 Packet Power, LLC. 15
1 | Agent Auth | Cover Letter(s) | 133.81 KiB | March 02 2015 |
December 1, 2014 ComplianceTestingLLC 1724S.NevadaWay Mesa,AZ85204 To whom it may concern:
I, the undersigned, hereby authorize Diana Williams at Compliance Testing, LLC, to act on our behalf in all manners relating to application for equipment authorization, including signing of all documents relating to these matters. Any and all acts carried out by Compliance Testing, LLC on our behalf shall have the same effect as acts of our own. I, the undersigned, hereby certify that we are not subject to a denial of federal benefits, that includes FCC benefits, pursuant to Section 5301 of the Anti-Drug Abuse Act of 1988, 21 U.S.C. 853(a). In authorizing Compliance Testing, LLC as our agent, we still recognize that we are responsible to:
a) comply with the relevant provisions of the certification program;
b) c) d) make all necessary arrangements for the conduct of the evaluation, including provision for examining documentation and access to all areas, records (including internal audit reports) and personnel for the purposes of evaluation (e.g. testing, inspection, assessment, surveillance, reassessment) and resolution of complaints;
make claims regarding certification only in respect of the scope for which certification has been granted;
do not use our product certification in such a manner as to bring the Certification Division into disrepute and not make any statement regarding our product Packet Power, LLC Phone +1(877)560-8770 Fax +1(866)324-2511 www.packetpower.com 2716 Summer St NE, Minneapolis, MN 55413 USA certification which the Certification Division may consider misleading or unauthorized;
upon suspension or cancellation of certification, discontinue use of all advertising matter that contains any reference thereto and return any certification documents as required by the Certification Division;
use certification only to indicate the products are certified as being in conformity with specified standards;
endeavor to ensure that no certificate or report nor any part thereof is used in a misleading manner;
ensure that any reference to our product certification in communication media such as documents, brochures or advertising, complies with the requirements of the Certification Division;
keep a record of all complaints made known to the us relating to the products compliance with requirements of the relevant standard and to make these records available to the Certification Division when requested;
take appropriate action with respect to such complaints and any deficiencies found in products or services that affect compliance with the requirements for certification;
e) f) g) h) i) j) k) document the actions taken. This authorization is valid until further written notice from the applicant. Sincerely Yours, Steve VanTassel CEO Packet Power LLC Packet Power, LLC Phone 1(877)560-8770 Fax 1(866)324-2511 www.packetpower.com 201 6th St. SE, Suite #1, Minneapolis, MN 55414 USA 2 3 REMARK:
1. This authorization letter will be sent along with your application when filing with the Certification Division. 2. Please follow the format and type it on company letterhead and send original to us. 3. Authorized signature must be in agreement with grantee code contact in FCC database. Packet Power, LLC Phone 1(877)560-8770 Fax 1(866)324-2511 www.packetpower.com 201 6th St. SE, Suite #1, Minneapolis, MN 55414 USA
1 | Antenna Spec | Cover Letter(s) | 71.52 KiB | March 02 2015 |
P5T1 Antenna Specification Wire InsulatedAWG20(0.81mmdiameter)solidcopperwire Blackforantenna1 Redforantenna2 Antenna 1 (BLACK) (ANT1) InsulatedAWG20BLACKsolidwire 82mm(+/2mm)totallength,3mmstrippedforsoldering Antenna 2 (RED) (ANT2) InsulatedAWG20REDsolidwire 35mm(+/2mm)totallength,3mmstrippedforsoldering
1 | Correspondence | Cover Letter(s) | 106.11 KiB | March 02 2015 |
CB-7.2.1 Technical Review RT Form FCC ID: WCGP5T1 IC ID: 8751A-P5T1 CT Project: P14b0018 From: From: Shawn McMillen Date: 1/16/15 1n/a 2n/a 3--The block diagram and theory of operation files refer to several other model numbers that are not associated with this filing. This filing needs to be a standalone and only address the radios with this filing. Alan 1/19/15 - I can only see this in the radio communications section. I will amend this and re post today. (Still waiting for this revision-DW) 4--The FCC statement in the users manual is confusing. It reads that it complies with both Class A and class B. The manual should only reflect the product as tested. DW Revised manual saved. 5--The users manual is missing the necessary RF exposure statements. DW Revised manual saved. 6--The 2.4GHz radio was tested to a maximum power level of 0.246mW radiated however the specifications in the operational description list it at a maximum power of 0.398mW. The antenna data sheet does not include a gain value. The power level limit per 15.247 is a conducted value. Please include the antenna gain value in order to determine what the actual conducted power is. Alan 1/19/15 - The antenna gain value was previously measured at 9 dBi. CT - The gain value has been included. 7--The radiated restricted band measurements were performed using a 100kHz RBW however the 15.209 requirement is based on 1MHz RBW @ 3m. CT Updated test report 8--Please include the occupied bandwidth plot in the test report for the 2.4GHz radio. CT The report has been updated. Issue Date: 9/22/2011 Form: CB-7.2.1 Revised Date: 6/23/2014 L:\Project\2014\p14b0018-Packet Po\TCB Folder\RT's\CB-7.2.1 - Technical Review RT Form.docx Issued by: QM Revised by: QM-JS Page 1 of 3 9--The dwell time for the 2.4GHz requires more information to determine that it meets the 0.4s limit. Also the timing plots should show the actual on time in the spectrum window. CT Due to the nature of the duty cycle of this device it is impractical to capture this data on a spectrum analyzer. A document has been supplied by the manufacturer detailing the timing of the radio 10--The test report should also address RF exposure if necessary. If the EUT is exempt from routine RF exposure this should be stated in the report. CT Completed. 11--The power level recorded for the 900MHz radio was 195uW radiated however the radio is rated up to -2dBm conducted. The antenna data sheet does not include a gain value. The power level limit per 15.247 is a conducted value. Please include the antenna gain value in order to determine what the actual conducted power is. CT The gain value has been included. 12--Please note that in both 900MHz and 2.4GHz test reports the 15.209 radiated emissions data includes a statement that No other emissions were detectable. All emission were greater than -
20dBc. Emissions >960MHz are based on an absolute value of 54dBuV average at 3m distance and not a -20dBc requirement. -20dBc is a 15.247 requirement for emission not falling into restricted bands and is based on a 100kHz RBW. You may want to consider revising that statement. CT Updated test report 13--There is insufficient information in the 900MHz test report to demonstrate that the EUT meets the dwell time requirements. CT Due to the nature of the duty cycle of this device it is impractical to capture this data on a spectrum analyzer. A document has been supplied by the manufacturer detailing the timing of the radio 14--If any simultaneous operation with the two radios exists this needs to be addressed. If not then this should be stated in the material provided. Alan: These devices are intended to operate in constellations of many, even hundreds of units. Date:
Issue Date: 9/22/2011 Form: CB-7.2.1 Revised Date: 6/23/2014 L:\Project\2014\p14b0018-Packet Po\TCB Folder\RT's\CB-7.2.1 - Technical Review RT Form.docx Issued by: QM Revised by: QM-JS Page 2 of 3 CT -
Response by:
Submitted by:
Date:
Issue Date: 9/22/2011 Form: CB-7.2.1 Revised Date: 6/23/2014 L:\Project\2014\p14b0018-Packet Po\TCB Folder\RT's\CB-7.2.1 - Technical Review RT Form.docx Issued by: QM Revised by: QM-JS Page 3 of 3
1 | Family Channel Dwell Time | Cover Letter(s) | 220.27 KiB | March 02 2015 |
P5 Device Family R/F Channel Dwell Time Overview AllPacketPowerP5familydevices(P5T3,P5T1,P5J6etc.)useidenticalhardareand softwareR/Fcommunicationsystems.Thesystemusesapseudorandomfrequencyhopping scheme,withpacketstransmissiontimesof7ms(in2.4GHzband)or10ms(in860/920MHz bands). Minimumtimebetweenanytwotransmissions(alwaysondifferentchannels)is:
2^9*22.5ms=11.52s, Maximumtimebetweenbetweensuchtransmissionsis:
2^12*22.5ms=92.16s. Minimumtimebetweenconsecutivetransmissionsonthesamechannel(outof64)is:
64*2^9*22.5ms=737s. PacketPowerL.L.C.StrictlyProprietary&Confidential
1 | Long Term Confidentiality | Cover Letter(s) | 110.09 KiB | March 02 2015 |
December1,2014 ComplianceTestingLLC 1724S.NevadaWay Mesa,AZ85204 RE:CONFIDENTIALITYREQUESTFORSMARTPOWERCABLE/P5T1FCCID:WCGP5T1 ToWhomItMayConcern:
Thisletterservesasanofficialrequestforconfidentialityundersections0.457and0.459ofCFR 47. We have requested that the following documents required to be submitted with this applicationbepermanentlywithheldfrompublicreview. PartsList BlockDiagram Schematics TheoryofOperation Thesedocumentscontain detailed systemandequipmentdescriptions andrelated information abouttheproduct,whichmanufacturer/applicantconsiderstobeproprietary,confidential,anda customdesignandotherwise,wouldnotreleasetothegeneralpublic.Sincethisdesignisabasis from which future technological products will evolve, manufacturer/applicant feels that this informationwouldbeofbenefittoitscompetitors,andthatthedisclosureoftheinformationin thesedocumentswouldgiveourcompetitorsanunfairadvantageinthemarket. Pleasecontactmeifthereisanyinformationyoumayneed. SincerelyYours, SteveVanTassel CEO PacketPowerLLC Packet Power, LLC Phone +1(877)560-8770 Fax +1(866)324-2511 www.packetpower.com 2716 Summer St NE, Minneapolis, MN 55413 USA
1 | Short Term Confidentiality | Cover Letter(s) | 125.35 KiB | March 02 2015 |
December1,2014 ComplianceTestingLLC 1724S.NevadaWay Mesa,AZ85204 ToWhomItMayConcern:
1. Testsetupphotos 2. Externalphotos 3. Internalphotos 4. Usersmanual RE:ShortTermConfidentialityRequestForSmartPowerCable,FCCID:WCGP5T1 Inaccordancewithsections0.457and0.459ofCFR47,PacketPowerLLC.requestsshortterm Confidentialityoffollowingsectionsofthisapplicationforaperiodof45daysaftergrantisissued. Thesedocumentscontaindetailedsystemandequipmentdescriptionsandrelatedinformationabout theproduct,whichmanufacturer/applicantconsiderstobeproprietary,confidential,andacustom designandotherwise,wouldnotreleasetothegeneralpublic.Sincethisdesignisabasisfromwhich futuretechnologicalproductswillevolve,manufacturer/applicantfeelsthatthisinformationwouldbe ofbenefittoitscompetitors,andthatthedisclosureoftheinformationinthesedocumentswouldgive ourcompetitorsanunfairadvantageinthemarket. Granteewillnotmarketordistributeproductduringtheperiodrequested.Onceproductisavailablefor marketing,GranteewillnotifyFCCorTCB. Pleasecontactmeifthereisanyinformationyoumayneed. Sincerely, SteveVanTassel CEO PacketPowerLLC 2716SummerSt.NE,Minneapolis,MN,55413
(877) 560-8770 Steve@Packetpower.com Packet Power, LLC Phone +1(877)560-8770 Fax +1(866)324-2511 www.packetpower.com 2716 Summer St NE, Minneapolis, MN 55413 USA
frequency | equipment class | purpose | ||
---|---|---|---|---|
1 | 2015-02-03 | 2401 ~ 2464 | DSS - Part 15 Spread Spectrum Transmitter | Original Equipment |
app s | Applicant Information | |||||
---|---|---|---|---|---|---|
1 | Effective |
2015-02-03
|
||||
1 | Applicant's complete, legal business name |
Packet Power
|
||||
1 | FCC Registration Number (FRN) |
0017809211
|
||||
1 | Physical Address |
2095 Salem Ct.
|
||||
1 |
Orono, 55356
|
|||||
1 |
United States
|
|||||
app s | TCB Information | |||||
1 | TCB Application Email Address |
d******@compliancetesting.com
|
||||
1 | TCB Scope |
A4: UNII devices & low power transmitters using spread spectrum techniques
|
||||
app s | FCC ID | |||||
1 | Grantee Code |
WCG
|
||||
1 | Equipment Product Code |
P5T1
|
||||
app s | Person at the applicant's address to receive grant or for contact | |||||
1 | Name |
P**** B******
|
||||
1 | Telephone Number |
952-2********
|
||||
1 | Fax Number |
952-5********
|
||||
1 |
p******@packet-power.com
|
|||||
app s | Technical Contact | |||||
n/a | ||||||
app s | Non Technical Contact | |||||
n/a | ||||||
app s | Confidentiality (long or short term) | |||||
1 | Does this application include a request for confidentiality for any portion(s) of the data contained in this application pursuant to 47 CFR § 0.459 of the Commission Rules?: | Yes | ||||
1 | Long-Term Confidentiality Does this application include a request for confidentiality for any portion(s) of the data contained in this application pursuant to 47 CFR § 0.459 of the Commission Rules?: | Yes | ||||
1 | If so, specify the short-term confidentiality release date (MM/DD/YYYY format) | 03/28/2015 | ||||
if no date is supplied, the release date will be set to 45 calendar days past the date of grant. | ||||||
app s | Cognitive Radio & Software Defined Radio, Class, etc | |||||
1 | Is this application for software defined/cognitive radio authorization? | No | ||||
1 | Equipment Class | DSS - Part 15 Spread Spectrum Transmitter | ||||
1 | Description of product as it is marketed: (NOTE: This text will appear below the equipment class on the grant) | Ethernet Gateway | ||||
1 | Related OET KnowledgeDataBase Inquiry: Is there a KDB inquiry associated with this application? | No | ||||
1 | Modular Equipment Type | Does not apply | ||||
1 | Purpose / Application is for | Original Equipment | ||||
1 | Composite Equipment: Is the equipment in this application a composite device subject to an additional equipment authorization? | No | ||||
1 | Related Equipment: Is the equipment in this application part of a system that operates with, or is marketed with, another device that requires an equipment authorization? | No | ||||
1 | Grant Comments | Power is listed as radiated. The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operated in conjunction with any other antenna or transmitter. | ||||
1 | Is there an equipment authorization waiver associated with this application? | No | ||||
1 | If there is an equipment authorization waiver associated with this application, has the associated waiver been approved and all information uploaded? | No | ||||
app s | Test Firm Name and Contact Information | |||||
1 | Firm Name |
Compliance Testing, LLC
|
||||
1 | Name |
M******** S********
|
||||
1 | Telephone Number |
480-9********
|
||||
1 | Fax Number |
480 9********
|
||||
1 |
m******@compliancetesting.com
|
|||||
Equipment Specifications | |||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Line | Rule Parts | Grant Notes | Lower Frequency | Upper Frequency | Power Output | Tolerance | Emission Designator | Microprocessor Number | |||||||||||||||||||||||||||||||||
1 | 1 | 15C | 2401 | 2464 | 0.002 | ||||||||||||||||||||||||||||||||||||
1 | 2 | 15C | 902.4 | 927.6 | 0.0002 |
some individual PII (Personally Identifiable Information) available on the public forms may be redacted, original source may include additional details
This product uses the FCC Data API but is not endorsed or certified by the FCC