all | frequencies |
|
exhibits | applications |
---|---|---|---|---|
manual |
app s | submitted / available | |||||||
---|---|---|---|---|---|---|---|---|
1 |
|
Users Manual | Users Manual | 2.16 MiB | ||||
1 | Block Diagram | |||||||
1 | External Photos | |||||||
1 | Internal Photos | |||||||
1 | ID Label/Location Info | |||||||
1 | ID Label/Location Info | |||||||
1 | Operational Description | |||||||
1 | Cover Letter(s) | |||||||
1 | Schematics | |||||||
1 | Test Report | |||||||
1 | Test Setup Photos |
1 | Users Manual | Users Manual | 2.16 MiB |
2012 March AYC-E/Q60 Family Vandal Resistant Convertible Reader/Controllers Instruction Manual Copyright 2012 by Rosslare. All rights reserved. This manual and the information contained herein are proprietary to REL, RSP Inc. and/or their related companies and/or subsidiaries (hereafter:ROSSLARE). Only ROSSLARE and its customers have the right to use the information. No part of this manual may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of ROSSLARE. ROSSLARE owns patents and patent applications, trademarks, copyrights, or other intellectual property rights covering the subject matter in this manual. TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION MAY RESULT IN LEGAL PROCEEDINGS. The furnishing of this manual to any party does not give that party or any third party any license to these patents, trademarks, copyrights or other intellectual property rights, except as expressly provided in any written agreement of ROSSLARE. ROSSLARE reserves the right to revise and change this document at any time, without being obliged to announce such revisions or changes beforehand or after the fact. Table of Contents Table of Contents Introduction .............................................................. 9 1. Reader/Controller Types......................................................... 9 1.1 Box Content ....................................................................... 10 1.2 1.3 Ancillary Equipment ............................................................ 10 2. Technical Specifications .......................................... 11 Key Features ....................................................................... 12 2.1 2.1.1 Reader ....................................................................................... 13 2.1.2 Controller .................................................................................. 13 Installation .............................................................. 14 3. 3.1 Mounting the AYC-E60 ....................................................... 14 3.2 Mounting the AYC-Q60 ...................................................... 15 4. Wiring Instructions ................................................. 17 5. Reader Functionality ............................................... 21 Transmit Mode ................................................................... 21 5.1 5.2 Programming the AYC-E/Q60 Series ..................................... 21 Entering Programming Mode ..................................................... 23 5.2.1 Exiting Programming Mode ....................................................... 23 5.2.2 Selecting Keypad Transmission Format ...................................... 24 5.2.3 5.2.4 Keypad Transmission Format Option Number ............................ 25 Selecting HID Prox Card Transmission Format ............................ 30 5.2.5 Selecting Rosslare PROX Card Transmission Format ................... 30 5.2.6 Changing the Programming Code ............................................. 33 5.2.7 5.2.8 Changing the Facility Code ........................................................ 33 Setting the Backlight Behavior ................................................... 34 5.2.9 AYC-E/Q60 Family Instruction Manual iii Table of Contents Setting the Reader Format ......................................................... 35 5.2.10 Return to Factory Default Settings ............................................. 35 5.2.11 5.2.12 Replacing a Lost Programming Code ......................................... 36 6. Controller Functionality.......................................... 37 Normal, Secure, and Master Users ........................................ 37 6.1 6.2 Modes of Operation ............................................................ 38 Normal Mode ............................................................................ 38 6.2.1 Bypass Mode ............................................................................. 38 6.2.2 Secure Mode ............................................................................. 39 6.2.3 6.3 Changing the Modes of Operation ....................................... 39 Changing from Normal Mode to Secure Mode .......................... 39 6.3.1 Changing from Secure Mode to Normal Mode .......................... 39 6.3.2 Changing from Normal Mode to Bypass Mode .......................... 40 6.3.3 Changing from Bypass Mode to Normal Mode .......................... 40 6.3.4 6.4 Auxiliary Input & Output ...................................................... 40 Door Alarms ....................................................................... 41 6.5 Internal Case and Back Tamper ............................................ 41 6.6 6.7 Lockout Feature (Keypad/Card Tamper) ................................ 41 REX Function ...................................................................... 41 6.8 Secured Series Intelligent Power Supply ................................ 42 6.9 Programming the AYC-E/Q60 .............................................. 42 6.10 6.10.1 Entering Programming Mode ..................................................... 43 Exiting Programming Mode ....................................................... 44 6.10.2 Changing Lock Strike Code ....................................................... 44 6.10.3 Changing Auxiliary Code ........................................................... 45 6.10.4 Changing the Programming Code ............................................. 46 6.10.5 6.10.6 Changing the Normal/Secure Code ........................................... 47 Changing the Normal/Bypass Code and Door Chime Settings ... 47 6.10.7 iv AYC-E/Q60 Family Instruction Manual Table of Contents 6.10.8 Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time .............................................................................. 48 Defining the Auxiliary Input and Output .................................... 50 6.10.9 Detailed Reference Guide .......................................................... 52 6.10.10 Setting the Lockout Feature ....................................................... 56 6.10.11 Setting the Backlight Behavior ................................................... 57 6.10.12 Selecting the Rosslare PROX and HID Prox Format ..................... 57 6.10.13 Enrolling Primary and Secondary Codes ..................................... 58 6.10.14 Deleting Primary and Secondary Codes ...................................... 62 6.10.15 Relay Codes Assignment ............................................................ 64 6.10.16 PIN Code Length/Factory Default Settings .................................. 66 6.10.17 Replacing a Lost Programming Code ......................................... 67 6.10.18 6.10.19 Replacing a Lost Normal/Secure Code ........................................ 67 A. Declaration of Conformity...................................... 68 B. Limited Warranty .................................................... 69 AYC-E/Q60 Family Instruction Manual v List of Figures List of Figures Figure 1: Drilling & Mounting Template ........................................................ 14 Figure 2: Back Plate ...................................................................................... 16 Figure 2: Controller Application Wiring Diagram .......................................... 18 Figure 3: Auxiliary Output Connection with Internal Power .......................... 19 Figure 4: Auxiliary Output Connection with External Power.......................... 19 Figure 5: Reader Application Wiring Diagram ............................................... 20 vi AYC-E/Q60 Family Instruction Manual List of Tables List of Tables Table 1: Wiring Colors .................................................................................. 17 Table 2: Reader Programming Menu ............................................................ 22 Table 3: Keypad Transmission Format ........................................................... 25 Table 4: Controller Programming Menu ....................................................... 43 Table 5: Quick Reference Guide for Auxiliary Mode Setting .......................... 51 AYC-E/Q60 Family Instruction Manual vii Notice and Disclaimer Notice and Disclaimer This manuals sole purpose is to assist installers and/or users in the safe and efficient installation and usage of the system and/or product, and/or software described herein. Before attempting to install and/or use the system, the installer and the user must read this manual and become familiar with all safety requirements and operating procedures. The system must not be used for purposes other than those for which it was designed. The use of the software associated with the system and/or product, if applicable, is subject to the terms of the license provided as part of the purchase documents. REL, RSP Inc. and/or their related companies and/or subsidiaries
(hereafter:"ROSSLARE") exclusive warranty and liability is limited to the warranty and liability statement provided in an appendix at the end of this document. This manual describes the maximum configuration of the system with the maximum number of functions, including future options. Therefore, not all functions described in this manual may be available in the specific system and/or product configuration you purchased. Incorrect operation or installation, or failure of the user to effectively maintain the system, relieves the manufacturer (and seller) from all or any responsibility for consequent noncompliance, damage, or injury. The text, images and graphics contained in the manual are for the purpose of illustration and reference only. In no event shall manufacturer be liable for any special, direct, indirect, incidental, consequential, exemplary or punitive damages (including, without limitation, any and all damages from business interruption, loss of profits or revenue, cost of capital or loss of use of any property or capital or injury). All graphics in this manual are for reference only, some deviation between the image(s) and the actual product may occur. All wiring diagrams are intended for reference only, the photograph or graphic of the PCB(s) are intended for clearer illustration and understanding of the product and may differ from the actual PCB(s). viii AYC-E/Q60 Family Instruction Manual Introduction 1. Introduction The AYC-E/Q60 is a Rosslare goPROX & PIN Reader with Genuine HID Technology, as well as Rosslare's Convertible technology. The AYC-
E/Q60 series automatically determines whether to function as a reader or as a secured standalone controller. If the unit is connected to a standard access control unit, then it functions as a reader. If the unit is connected to a Rosslare secured intelligent power supply such as the PS-A25T, PS-C25T, or PS-C25TU, it functions as a 500 user secured standalone controller. As a reader, the units can read all HID Prox cards/tags (125 kHz FSK) using Genuine HID Technology and outputs HID Prox card data in Wiegand according to the number of bits of data stored on the card. The units also read Rosslare PROX cards (125 kHz) and can output Rosslare PROX card data as Wiegand 26-Bit, Clock & Data, and Wiegand + PIN. As a controller, the units accept up to 500 users, and allow entry via a personal identification number (PIN) and/or by presenting a proximity card. The PIN code length for the controller has several options. The PIN code length can be a set number of 4, 5, or 6 digits or it can be flexible from 4 to 8 digits. This manual contains the following chapters:
Wiring Instructions Reader Functionality Controller Functionality 1.1 Upon power-on reset, the AYC-E/Q60 searches for the presence of a Rosslare secured intelligent power supply. If a secured intelligent power supply is detected, then the AYC-E/Q60 is automatically configured as a secure access control unit. This is indicated by two Technical Specifications Installation Reader/Controller Types AYC-E/Q60 Family Instruction Manual 9 Introduction Box Content short beeps. If the secured controller is not detected, it is automatically configured as a reader, indicated by one short beep. 1.2 Before beginning, verify that all of the following is in the box. If anything is missing, please report the discrepancy to your nearest Rosslare office. One AYC-E/Q60 unit Installation kit includes security Torx screw and security Torx Screw tool Installation and operating instructions 1.3 The following equipment is required to complete your installation:
When functioning as a reader:
Ancillary Equipment Compatible Host Controller (not supplied) UL listed access control unit (such as model AC-215U) When functioning as a controller:
A secured series intelligent power supply such as the PC-25T, PS-A25T, PS-C25T, or PS-C25TU secure controllers. This unit connects to the following:
Electric lock strike mechanism or a magnetic lock device, which implements fail safe (power to lock) or fail secure
(power to open) functions Request to Exit (REX) button normally open type. Switch is closed when pressed Door monitor switch Rosslare accessories can be found on www.rosslaresecurity.com. 10 AYC-E/Q60 Family Instruction Manual Technical Specifications Technical Specifications 2. Specifications Electrical Characteristics Power Supply Type Operating Voltage Range AYC-E/Q60 Linear type recommended 516 VDC (when used as a controller, provided by the secured series intelligent power supply) 110 mA Input current standby (12 VDC) Input Current Max (16 VDC) 130 mA LED Control Input Tamper Output Cable Distance to Host Controller Max Proximity Card Read Range*
Dry contact N.O. Open collector, active low, 32 mA max sink current Up to 500 ft (150 meters) using an 18AWG cable Rosslare PROX: E 40 mm, Q 45 mm HID Prox: E 40 mm, Q 45 mm Proximity Card Modulation Rosslare PROX/HID Prox at 125 KHz Proximity Card Compatibility Card Transmit Format
(Reader) Rosslare PROX/HID Prox cards Rosslare PROX cards: Wiegand 26-bit, or Clock & Data HID cards: According to card type Programmable PIN code formats Keypad Transmit Format
(Reader) LED Indicators Communication Two tri-colored LEDs Data1/C1, Data0/C2open collector, 5 V termination
* Measured using a Rosslare proximity card (AT-R14) or equivalent. Range also depends on electrical environment and proximity to metal. AYC-E/Q60 Family Instruction Manual 11 Technical Specifications Specifications AYC-E/Q60 Environmental Characteristics Operating Temp. Range
-22F to 150F (-30C to 65C) Operating Humidity 0 to 95% (non-condensing) Outdoor Usage Mechanical Weather-resistant, meets IP-65, epoxy potted, suitable for indoor and outdoor use Size
(Height x Width x Depth) E: 6.10 x 3 x 0.827 in. (155 x 1.73 x 0.35 mm) Q: 4.72 x 2.99 x 0.83 in. (120 x 76 x 21 mm) Weight E: 0.32 lb (143 g) Q: 1.06 lb (480 g) Key Features 2.1 The key features for the AYC-E/Q60 series are:
Built-in Proximity Card Reader (125 KHz Rosslare PROX/HID Prox Modulation) Programmable blue backlit keypad Optical back tamper sensor and open collector tamper output Comes with mounting template for easier installation Comes with an installation kit that includes a security screw and a Lockout feature on wrong entry (keypad/card tamper) Internal buzzer provides audible interface feedback Two status/programming interface LEDs (tri-colored) Fully-potted construction for outdoor use security screw tool 12 AYC-E/Q60 Family Instruction Manual Technical Specifications Reader 2.1.1 Rosslare PROX card transmission formats:
Programmable keypad transmission format LED control input Programmable Facility code Clock & Data Wiegand 26-Bit Card + PIN HID Prox Card Transmission Format Wiegand (outputs per format on the card) Controller 2.1.2 Bi-directional secure communication Code Search feature that helps make maintaining user codes Three user levels: Normal, Secure, Master easier Three modes of operation: Normal, Bypass, Secure REX input Chime bell and siren features are available Programmable Lock Strike Release, Siren, and Alarm Delay timers Programmable auxiliary input with versatile functions Programmable auxiliary output functions Programmable PIN code length AYC-E/Q60 Family Instruction Manual 13 Installation Installation Mounting the AYC-E60 3. 3.1 To mount the AYC-E60:
1. Select the location to mount the AYC-E/Q60. This location should be at shoulder height. 2. For wall mounting, use the included mounting template as a guide for drilling holes for mounting screws and wiring. For US Gang Box mounting, no drilling is necessary. Figure 1: Drilling & Mounting Template 3. When the unit is used as a reader, route the interface cable from the AYC-E60 to the controller. A linear type power supply is recommended when using the unit as a reader 14 AYC-E/Q60 Family Instruction Manual Installation 4. When the unit is used as a secured controller, route the interface cable from the AYC-E60 to a Rosslare secured series intelligent power supply. 5. Screw the AYC-E60 to its mounting location. 6. Return the AYC-E60 front cover to the mounted back plate. 7. Secure the front cover by using the supplied security Torx screw in the controllers installation kit. A Torx security screw tool is provided for use when tightening the security Torx screw. Mounting the AYC-Q60 3.2 Attach the reader to a surface before connecting it to its power and the access control computer. To mount the AYC-Q60:
1. Remove the reader's front cover using the security spline key. The screw holes on the back plate are now visible. 2. Select an approximate location for the reader. 3. Peel off the back of the self-adhesive installation template and attach the template to the required location. 4. Using the template as a guide, drill four holes into the surface. The required hole size is marked on the template. AYC-E/Q60 Family Instruction Manual 15 Installation Figure 2: Back Plate 5. Drill an additional 7/16 (10-mm) hole for the cable. When installing the reader on a metallic surface, cover the inside of the hole with a grommet or electrical tape. 6. Route the reader's cable to the power and access control system. A regulated linear power supply is recommended. 7. Screw the back plate into the surface. Ensure the screws are the size specified on the installation template. 8. Alternatively, the reader can be mounted with any strong epoxy glue:
a. Apply the glue. b. Hold the reader's back plate firmly in place until the glue dries. 9. Re-attach the reader's front cover. 16 AYC-E/Q60 Family Instruction Manual Wiring Instructions 4. Wiring Instructions The unit is supplied with a 22-inch pigtail, having a 6-conductor cable. To connect the unit to the controller, perform the following:
Prepare the unit's cable by cutting the cable jacket back 1 inches and strip the wire inch. Splice the units pigtail wires to the corresponding controller wires and cover each connection. Refer to Table 1 and to the wiring diagrams provided on the following pages. Table 1: Wiring Colors Reader Controller Color Functionality 5~16 VDC 5~16 VDC Red
+DC Input Shield/Ground Shield/Ground Black Ground Data 1/Clock Data 0/Data C 1 C 2 White Communication Green Communication G.LED/LEDCTL AUX. IN Brown LED Control/Auxiliary Input Tamper Tamper Purple Tamper If the tamper output is used, connect the purple wire to the correct input on the controller when used as a reader, or to a zone input of an intruder alarm system when used as a controller. Trim and cover all unused conductors. AYC-E/Q60 Family Instruction Manual 17 Wiring Instructions The individual wires from the unit are color-coded according the Wiegand standard. When using a separate Power Supply for the Reader, this Power Supply and that of the Controller must have a common ground. The Readers cable shield wire should preferably be attached to an earth ground, or a signal ground connection at the panel, or power supply end of the cable. This configuration is best for shielding the Reader cable from external interference Figure 3 shows the wiring for the Controller Application using a secured intelligent power supply. Figure 3: Controller Application Wiring Diagram Rosslare PS-X25 AYCE/Q60 18 AYC-E/Q60 Family Instruction Manual Wiring Instructions Figure 4 shows the auxiliary output connection using internal power. Figure 4: Auxiliary Output Connection with Internal Power Rosslare PS-X25 Figure 5 shows the auxiliary output connection using the external power. Figure 5: Auxiliary Output Connection with External Power ZONE INPUT Rosslare PS-X25 AYC-E/Q60 Family Instruction Manual 19 Wiring Instructions Figure 6 shows how to wire a reader to an access control panel. Figure 6: Reader Application Wiring Diagram AYC-E/Q60 20 AYC-E/Q60 Family Instruction Manual Reader Functionality 5. Reader Functionality The AYC-E/Q60 series can function both as a reader and as a controller. If the unit is connected to standard access controller, it functions as a reader, indicated by one beep immediately after power-
on reset. The following explains how the AYC-E/Q60 series functions as a reader. 5.1 When the AYC-E/Q60 is in Transmit Mode, it is ready to receive data from a presented Proximity Card or an entered PIN code. Transmit Mode When the reader is in Transmit Mode, the Transmit LED is red and the Program LED is off. Mode/Transmit Red Door/Program When a Proximity Card or Keyboard entry is being transmitted, the Transmit LED flashes green. Keyboard data can be sent via one of eight different Keypad Transmission Formats. For more information, see Section 5.2.3. Proximity Cards presented to the reader are always sent in either Wiegand, Clock & Data or, Wiegand Card + PIN format. See Section 5.2.5 for more information. 5.2 Programming the AYC-E/Q60 series is done solely via the unit's keypad driven Programming Menu System. To reach the Programming Menu System the AYC-E/Q60 must first be placed into Programming Mode. During the AYC-E/Q60s manufacturing process, certain codes and settings are pre-programmed. These settings are called the Default Factory Settings. Programming the AYC-E/Q60 Series AYC-E/Q60 Family Instruction Manual 21 Reader Functionality Table 2 shows the names of all the AYC-E/Q60 menus. Default Factory Settings are marked by a "*" sign. Table 2: Reader Programming Menu Menu Description Default 1 2 Selecting Keypad Transmission Format Single Key, Wiegand 6-Bit (Rosslare Format) Single Key, Wiegand 6-Bit with Nibble + Parity Bits Single Key, Wiegand 8-Bit, Nibbles Complemented 4 Keys Binary + Facility code, Wiegand 26-Bit 1 to 5 Keys + Facility code, Wiegand 26-Bit 6 Keys Binary-Coded Decimal (BCD) and Parity Bits, Wiegand 26-Bit Single Key, 3x4 Matrix Keypad 1 to 8 Keys BCD, Clock & Data Single key, Wiegand 4-Bit Selecting Rosslare PROX Card Transmission Format Wiegand 26-Bit Clock & Data Wiegand Card + PIN 3 Changing the Programming code 4 Changing the Facility code 6 Setting the Backlight Always off Always on 10 sec. backlight after key press otherwise off 10 sec. backlight after key press otherwise dimmed Setting Reader Format Rosslare PROX HID Prox Rosslare PROX + HID Prox 6 0 Return to Factory Default Settings
1234 0
22 AYC-E/Q60 Family Instruction Manual Reader Functionality 5.2.1 To enter Programming mode:
Entering Programming Mode 1. Press the # key 4 times. Transmit LED turns off. Program LED turns red. Mode/Transmit Door/Program Red 2. Enter your 4-digit Programming code. If the Programming code is valid, the door LED turns green and the AYC-E/Q60 is in Programming mode. Mode/Transmit Door/Program Green The factory 4-digit Programming code is 1234. If a Programming code is not entered within 30 seconds, the AYC-E/Q60 returns to Transmit mode. 5.2.2 To exit Programming mode:
Exiting Programming Mode 1. Press the # key. You hear a beep. The Program LED is off. The Transmit LED turns red. Mode/Transmit Red Door/Program This indicates that the AYC-E/Q60 has returned to Transmit mode. Wrong entries may reset the reader back to Transmit mode. While in Programming mode, if no key is pressed for 30 seconds, the AYC-E/Q60 exits Programming mode and returns to Transmit mode. AYC-E/Q60 Family Instruction Manual 23 Reader Functionality Selecting Keypad Transmission Format 5.2.3 The AYC-E/Q60 has nine different keypad transmission formats to select from. Follow the steps below to select the appropriate keypad transmission format that you wish to use. To select the keypad transmission format:
1. Enter Programming mode. 2. Press 1 to enter Menu 1. Mode/Transmit Door/Program Green The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3. Enter the appropriate option number for the keypad transmission format that you wish to select (see table below). If an incorrect option number is entered, the reader returns to Transmit mode and the keypad transmission format remains unchanged. See Table 3 for more information on keypad transmission formats. The system returns to Transmit mode. You hear three beeps. The Program LED turns off. The Transmit LED turns red. Mode/Transmit Red Door/Program 24 AYC-E/Q60 Family Instruction Manual Reader Functionality Only one keypad transmission format can be active at any one time. When using the keypad transmission format "1 to 8 keys BCD, Clock & Data" (Option 8) an additional input is required to specify the number of keys in the PIN code. Keypad Transmission Format Option Number 5.2.4 See Table 3 to determine the Option Number for the Keypad Transmission Format you wish to select. Table 3: Keypad Transmission Format Keypad Transmission Format Option Number Single Key, Wiegand 6-Bit (Rosslare Format) 1*
Single Key, Wiegand 6-Bit with Nibble + Parity Bits Single Key, Wiegand 8-Bit, Nibbles Complemented 4 Keys Binary + Facility code, Wiegand 26-Bit 1 to 5 Keys + Facility code, Wiegand 26-Bit 6 Keys BCD and Parity Bits, Wiegand 26-Bit Single Key, 3x4 Matrix Keypad 1 to 8 Keys BCD, Clock & Data Single Key Single key, Wiegand 4-Bit 2 3 4 5 6 7 8 9
* Option 1 is the default factory setting. More information on each of the different keypad transmission formats is available in the following subsections. AYC-E/Q60 Family Instruction Manual 25 Reader Functionality 5.2.4.1 Option 1: Single Key, Wiegand 6-Bit (Rosslare Format) Each key press immediately sends 4 bits with 2 parity bits added even parity for the first 3 bits and odd parity for the last 3 bits. 0 = 1 1010 0 ="A" in Hexadecimal 1 = 0 0001 0 2 = 0 0010 0 3 = 0 0011 1 4 = 1 0100 1 5 = 1 0101 0 5.2.4.2 Option 2: Single Key, Wiegand 6-Bit Nibble and 6 = 1 0110 0 7 = 1 0111 1 8 = 1 1000 1 9 = 1 1001 0
* = 1 1011 1 ="B" in Hexadecimal
# = 0 1100 1 ="C" in Hexadecimal Parities Each key press immediately sends 4 bits with 2 parity bits added even parity for the first 3 bits and odd parity for the last 3 bits. 0 = 0 0000 1 1 = 0 0001 0 2 = 0 0010 0 3 = 0 0011 1 4 = 1 0100 1 5 = 1 0101 0 5.2.4.3 Option 3: Single Key, Wiegand 8-Bit Nibbles 6 = 1 0110 0 7 = 1 0111 1 8 = 1 1000 1 9 = 1 1001 0
* = 1 1010 0 = "A" in Hexadecimal
# = 1 1011 1 = "B" in Hexadecimal Complemented This options inverts the most significant bits in the message leaving the least 4 significant bits as BCD representation of the key. The host system receives an 8-bit message. 0 = 11110000 1 = 11100001 2 = 11010010 3 = 11000011 4 = 10110100 5 = 10100101 6 = 10010110 7 = 10000111 8 = 01111000 9 = 01101001
* = 01011010 = "A" in Hexadecimal
# = 01001011 = "B" in Hexadecimal 26 AYC-E/Q60 Family Instruction Manual Reader Functionality 5.2.4.4 Option 4: 4 Keys Binary + Facility Code, Wiegand 26-
Bit This option buffers 4 keys and outputs keypad data with a 3-digit Facility code like a standard 26-bit card output. The Facility code is set in Programming Menu 4 and can be in the range 000 to 255. The factory default setting for the Facility code is 000 (see Section 5.2.8 for more information). The keypad PIN code is 4 digits in length and can range between 0000 and 9999. On the fourth key press of the 4-digit PIN code, the data is sent across the Wiegand Data lines as binary data in the same format as a 26-bit card. If the "*" key or the "#" key are pressed during PIN code entry, the keypad clears the PIN code entry buffer, generates a beep, and is ready to receive a new 4-digit keypad PIN code. If the entry of the 4-digit keypad PIN code is disrupted and no number key is pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a beep, and is ready to receive a new 4-digit keypad PIN code:
(EP) FFFF FFFF AAAA AAAA AAAA AAAA (OP) Where:
EP = Even parity for first 12 bits OP = Odd parity for last 12 bits F = 8-Bit Facility code A = 16-Bit code generated from keyboard 5.2.4.5 Option 5: 1 to 5 Keys + Facility Code, Wiegand 26-Bit Option 5 buffers up to 5 keys and outputs keypad data with a Facility code like a 26-bit card output. The Facility code is set in Programming Menu 4 and can be in the range 000 to 255. The factory default setting for the Facility code is 000 (see Section 5.2.8 for more information). The keypad PIN code can be one to five digits in length and can range between 1 and 65,535. When entering a keypad PIN code that is less than 5 digits in AYC-E/Q60 Family Instruction Manual 27 Reader Functionality length, the "#" key must be pressed to signify the end of PIN code entry. For keypad PIN codes that are 5 digits in length, on the fifth key press of the 5-digit PIN code, the data is sent across the Wiegand Data lines as binary data in the same format as a 26-bit card. If the "*" key is pressed during PIN code entry or a PIN code greater than 65,535 is entered, the keypad clears the PIN code entry buffer, generates a beep and is ready to receive a new 5-digit keypad PIN code. If the entry of the 1- to 5-digit keypad PIN code is disrupted and no number key or "#" key is pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a medium length beep, and is ready to receive a new 1- to 5-digit keypad PIN code:
(EP) FFFF FFFF AAAA AAAA AAAA AAAA (OP) Where:
EP = Even parity for first 12 bits OP = Odd parity for last 12 bits F = 8-Bit Facility code A = 16-Bit code generated from keyboard 5.2.4.6 Option 6: 6 Keys BCD and Parity Bits, Wiegand 26-Bit This option sends buffer of 6 keys, adds parity, and sends a 26-bit BCD message. Each key is a four bit equivalent of the decimal number. The keypad PIN code must be 6 key presses in length. On the sixth key press of the 6-digit PIN code, the data is sent across the Wiegand Data lines as a BCD message. If the entry of the 6-digit keypad PIN code is disrupted and no number key is pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a medium length beep, and is ready to receive a new 6-digit keypad PIN code:
(EP) AAAA BBBB CCCC DDDD EEEE FFFF (OP) 28 AYC-E/Q60 Family Instruction Manual Reader Functionality Where:
EP = Even parity for first 12 bits OP = Odd parity for last 12 bits D = Fourth key entered E = Fifth key entered. F = Sixth key entered A = The first key entered. B = Second key entered C = Third key entered 5.2.4.7 Option 7: Single Key, 3x4 Matrix Keypad (MD-P64) This unique mode is intended to let the host controller scan the AYC-
E/Q60 keypad while still keeping the proximity card readers Wiegand 26-Bit or Clock & Data formats active. An optional interface board must be used between the AYC-E/Q60 and the host system. Each key press is immediately sent on DATA0 as an ASCII character at a baud rate of 9600 bits per second. When a key is pressed, DATA1 is pulled "low" until the key is released at which point DATA1 is set to "high". This allows the controller to detect the duration of the key press. The MD-P64 interface unit outputs the data received to 7 outputs emulating a keyboard. The interface unit does not affect any data that it receives from the proximity reader whether it is Wiegand 26-Bit or Clock & Data. Key pressed = ASCII Value 6 = '6' ( 0x36 hex ) 7 = '7' ( 0x37 hex ) 8 = '8' ( 0x38 hex ) 9 = '9' ( 0x39 hex )
*= '* ' ( 0x2A hex )
# = '#' ( 0x23 hex ) 0 = '0' ( 0x30 hex ) 1 = '1' ( 0x31 hex ) 2 = '2' ( 0x32 hex ) 3 = '3' ( 0x33 hex ) 4 = '4' ( 0x34 hex ) 5 = '5' ( 0x35 hex ) 5.2.4.8 Option 8: 1 to 8 Keys BCD, Clock & Data Option 8 buffers up to 8 keys and outputs keypad data without a Facility code like standard Clock and Data card output. The keypad PIN code can be one to eight digits in length. The PIN code length is selected while programming the reader for Option 8. AYC-E/Q60 Family Instruction Manual 29 Reader Functionality The reader transmits the data when it receives the last key press of the PIN code. The data is sent across the two data output lines as binary data in Clock & Data format. If the "*" key or the "#" key is pressed during PIN code entry, the keypad clears the PIN code entry buffer, generates a beep, and is ready to receive a new keypad PIN code. If the entry of the digit keypad PIN code is disrupted and no number key or "#" key is pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a medium length beep, and is ready to receive a new keypad PIN code. When using the keypad transmission format "1 to 8 keys BCD, Clock & Data" (Option 8), an additional input is required to specify the number of keys in the PIN code. 5.2.4.9 Option 9: Single Key, Wiegand 4-Bit With this option, each key press immediately sends 4 bits of data, with no parity bits added. 0 = 0000 1 = 0001 2 = 0010 3 = 0011 4 = 0100 5 = 0101 6 = 0110 7 = 0111 8 = 1000 9 = 1001
*= 1010 ="A" in Hexadecimal
#=1011 ="B" in Hexadecimal 5.2.5 Selecting HID Prox Card Transmission Format The AYC-E/Q60 can read all HID Prox Cards/Tags (125 kHz) using Genuine HID Technology and outputs HID Prox card data in Wiegand according to the number of bits of data stored on the card. 5.2.6 Selecting Rosslare PROX Card Transmission Format The AYC-E/Q60 can read Rosslare PROX cards (125 kHz) and can output Rosslare PROX card data as Wiegand 26-Bit, Clock & Data, and Wiegand + PIN. 30 AYC-E/Q60 Family Instruction Manual Reader Functionality To select the Rosslare PROX Card transmission format:
1. Enter Programming mode. 2. Press 2 to enter Menu 2. Mode/Transmit Door/Program Green The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3. Enter the appropriate option number for the Rosslare PROX card transmission format that you wish to select:
Option 1: Wiegand 26-Bit Option 2: Clock & Data Option 3: Wiegand Card + PIN If an incorrect option is entered, the reader returns to Transmit mode and the keypad transmission format remains unchanged. Door/Program Red Mode/Transmit
"Wiegand Card + PIN" Transmission Format The Program LED turns off. The Transmit LED turns red. The system returns to Transmit mode. You hear three beeps. 5.2.6.1 This unique mode is intended to let host controllers get card and keypad data simultaneously. This option overrules the selected Keypad Transmission Format and sends the keypad data as described below. After a card is presented to AYC-E/Q60, the program LED starts to flash in green and indicates that AYC-E/Q60 is waiting for the PIN code. If the entry of one- to five-digit keypad PIN code is disturbed and no digit key or # key is pressed within 5 seconds, the keypad clears the card buffer and the PIN code entry buffer, generates a medium length beep, and is ready to receive a new card. AYC-E/Q60 Family Instruction Manual 31 Reader Functionality The keypad PIN code can be one to five digits in length in the range of 0 to 99,999. When entering a keypad PIN code, the # key must be pressed to signify the end of the PIN entry. When pressing the # key, the data is sent by the Wiegand data lines. If the * key is pressed, the keypad clears the card buffer and the PIN code entry buffer, generates a medium length beep, and is ready to receive a new card. The AYC-E/Q60 output card data is in Wiegand 26-Bit with the following keypad data in Wiegand 26-Bit format. Card Data: (EP) AAAA AAAA AAAA BBBB BBBB BBBB (OP) Where:
EP =Even parity for first 12 A bits OP =Odd parity for last B 12 bits PIN Data: (EP) 0000 AAAA BBBB CCCC DDDD EEEE (OP) Where:
D = Fourth key entered E = Fifth key entered. OP =Odd parity for last 12 bits. A = The first key entered. B = Second key entered C = Third key entered EP =Even parity for first 12 bits. If the PIN code is less than 5 digits, all the most significant nibbles are filled with 0. Example: (EP) 0000 0000 0000 0000 AAAA BBBB (OP) Where:
A = The first key entered. EP =Even parity for first 12 bits. B =Second key entered OP =Odd parity for last 12 bits. 32 AYC-E/Q60 Family Instruction Manual Reader Functionality 5.2.7 To change the Programming code:
Changing the Programming Code 1. Enter Programming mode. 2. Press 3 to enter Menu 3. Mode/Transmit Door/Program Green The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3. Enter the new 4-digit code you wish to set as the Programming code. The system returns to Transmit mode. You hear three beeps. The Program LED turns off. Mode/Transmit Red Door/Program The Programming code cannot be erased; the code 0000 is invalid and does not erase the Programming code. The factory default 4-digit Programming code is 1234. Changing the Facility Code 5.2.8 To change the Facility code:
1. Enter Programming mode. 2. Press 4 to enter Menu 4. The Transmit LED turns red. 3. Enter the new 3-digit code you wish to set as the Facility code. Door/Program Green Door/Program Green Mode/Transmit Mode/Transmit Red AYC-E/Q60 Family Instruction Manual 33 Reader Functionality The system returns to Transmit mode. You hear three beeps. The Program LED turns off. Mode/Transmit Red Door/Program The Facility code can be in the range of 000 to 255. The default Facility code is 0. Setting the Backlight Behavior 5.2.9 To set the backlight behavior:
1. Enter Programming mode. 2. Press 6 to enter Menu 6. Door/Program Green Mode/Transmit The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3. Enter one of the following codes:
10 for always off 11 for always on 12 for 10 sec. backlight after a key is pressed otherwise off 13 for 10 sec. backlight after a key is pressed otherwise dimmed The system returns to Transmit mode. You hear three beeps. The Program LED turns off. Mode/Transmit Red Door/Program 34 AYC-E/Q60 Family Instruction Manual Reader Functionality 5.2.10 Setting the Reader Format To set the reader format:
1. Enter Programming mode. 2. Press 6 to enter Menu 6. Mode/Transmit Door/Program Green The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3. Enter the appropriate option number for the Reader Format 61 for Rosslare PROX 62 for HID Prox 63 for Rosslare PROX +
HID Prox (default) The system returns to Transmit mode. You hear three beeps. The Program LED turns off. Mode/Transmit Red Door/Program 5.2.11 Return to Factory Default Settings You must be very careful before using this command! This erases the entire memory and returns all codes to their factory default setting. To return to factory default settings:
1. Enter Programming mode. 2. Press 0 to enter Menu 0. Mode/Transmit Door/Program Green The Transmit LED flashes red. The Program LED flashes red. Mode/Transmit Red Red Door/Program AYC-E/Q60 Family Instruction Manual 35 Reader Functionality 3. Enter your 4-digit Programming code. If the Programming code is valid, all memory is erased, you hear three beeps and the controller returns to Normal mode. If the Programming code is invalid, you hear a long beep and the controller returns to Normal mode without erasing the memory of the controller. 5.2.12 Replacing a Lost Programming Code In the event that the Programming code is forgotten, the AYC-E/Q60 may be reprogrammed in the field using the following instructions:
To replace a lost Programming code:
1. Remove power from the reader. 2. Activate the tamper by removing the reader from the wall or removing the reader's case. 3. Apply power to the reader. 4. You now have 10 seconds to enter Programming Mode using the factory default Programming code 1234. 36 AYC-E/Q60 Family Instruction Manual Controller Functionality 6. Controller Functionality The AYC-E/Q60 series can function both as a reader and as a controller. If the unit is connected to a Rosslare secured series intelligent power supply, it functions as a controller indicated by two beeps immediately after power-on reset. The Lock Strike Output and Request to Exit input are not located on the AYC-E/Q60 unit, eliminating the possibility of unauthorized entry to the restricted area. This chapter explains how the AYC-E/Q60 series functions as a controller. 6.1 The AYC-E/Q60 accepts up to 500 users and provides entry via the use of PIN codes and/or Proximity cards. Each user is provided with two code memory slots: Memory Slot 1 (Primary code) and Memory Slot 2 (Secondary code). The PIN code length has several options. The PIN code length can be a set number of 4, 5 or 6 digits or it can be a 48 digits option. When choosing the 48 digit option, please note that you should either enter zeros before the code, or press # at the end (for example if your code is 12345, enter either 00012345 or 12345#). Normal, Secure, and Master Users Entering a code refers to either PIN or Card depending on the model you have. The way in which the two memory slots are programmed determines a users access level and also determines the way in which the AYC-
E/Q60 grants access in its three modes of operation. There are three user levels:
Normal User A Normal User only has a Primary code and is only granted access when the AYC-E/Q60 is in Normal or Bypass mode. AYC-E/Q60 Family Instruction Manual 37 Controller Functionality Secure User A Secure User must have a Primary and Secondary code programmed; the two codes must not be the same. The Secure User can gain access when the AYC-E/Q60 is in any of its three modes of operation. In Normal mode, the Secure User must use the Primary code to gain entry. In Secure Mode, the Secure User must present both the Primary and Secondary codes to gain entry. Master User A Master User must have both Primary and Secondary codes programmed with the same code. The Master User can gain access during any mode of operation by presenting the PIN code and/or Proximity card once to the controller. (The Master User is convenient but is less secure than a Secure User.) Modes of Operation 6.2 The AYC-E/Q60 has three modes of operation:
6.2.1 Normal Mode Mode/Transmit Door/Program Green The Mode LED is green. Normal mode is the default mode. In Normal mode, the door is locked until a Primary code is presented to the controller. Special codes such as Lock Strike code and Auxiliary code are active in Normal mode.
(See Sections 6.10.3 and 6.10.4 for more information.) 6.2.2 Bypass Mode Mode/Transmit Door/Program Orange The Mode LED is orange. In Bypass Mode, access to the premises is dependent on whether the controller's Lock Strike Relay is programmed for Fail Safe Operation or Fail Secure Operation. When the Lock Strike is programmed for Fail Secure Operation, the door is locked until the "*" button is pressed. When the Lock Strike is programmed for Fail Safe Operation, the door is constantly unlocked. 38 AYC-E/Q60 Family Instruction Manual Controller Functionality 6.2.3 Secure Mode Mode/Transmit Red Door/Program The Mode LED is red. Only Secure and Master Users can access the premises during the Secured Mode. A Secure User must enter their Primary and Secondary codes to gain entry. After entering their Primary code, the Door LED flashes green for 10 seconds, during which the Secondary code must be entered. A Master User only needs to present the code once to gain entry. 6.3 6.3.1 The default factory setting for the Normal/Secure code is 3838. To change from Normal to Secure mode:
Changing from Normal Mode to Secure Mode Changing the Modes of Operation 1. Enter the Normal/Secure code. The Mode LED flashes red. Mode/Transmit Green Mode/Transmit Red 2. Press the # key to confirm the mode change. The Mode LED turns red. Mode/Transmit Door/Program Door/Program Door/Program Changing from Secure Mode to Normal Mode 6.3.2 The default factory setting for the Normal/Secure code is 3838. To change from Secure to Normal mode:
Red 1. Enter the Normal/Secure code. The Mode LED flashes green. Mode/Transmit Red Mode/Transmit Green Door/Program Door/Program AYC-E/Q60 Family Instruction Manual 39 Controller Functionality 2. Press the # key to confirm the mode change. The Mode LED turns green. Mode/Transmit Door/Program Green Changing from Normal Mode to Bypass Mode 6.3.3 See Section 6.10.7 to create/modify the Normal/Bypass code. To change from Normal to Bypass mode:
1. Enter the 4-digit Normal/Bypass code. The Mode LED flashes orange. Mode/Transmit Green Mode/Transmit 2. Press the # key to confirm the mode change. The Mode LED turns orange. Orange Mode/Transmit Orange Door/Program Door/Program Door/Program Changing from Bypass Mode to Normal Mode 6.3.4 See Section 6.10.7 to create/modify the Normal/Bypass code. To change from Bypass to Normal mode:
1. Enter the 4-digit Normal/Bypass code. Mode/Transmit Orange The Mode LED flashes green. Mode/Transmit 2. Press the # key to confirm the mode change. The Mode LED turns green. Mode/Transmit Door/Program Door/Program Door/Program Green Green Auxiliary Input & Output 6.4 For optimum usability in different applications, the controllers auxiliary input and output can be configured in 10 different modes of operation. 40 AYC-E/Q60 Family Instruction Manual Controller Functionality Door Alarms Internal Case and Back Tamper Lockout Feature (Keypad/Card Tamper) 6.5 Door alarms can be generated by connecting the Auxiliary Input to a Door Position Switch. Either Door-Forced or Door-Ajar conditions are supported, as well as a configurable delay timer for each alarm type. Only one door-alarm is enabled at any one time. Door alarms may activate auxiliary output and siren depending on the auxiliary settings. 6.6 If the unit is forcibly opened or it is removed from the wall, a tamper event is triggered. A tamper output opens sending a signal to the connected alarm system (purple wire); the event closes when the tamper is closed (case is re-closed or re-attached to the wall). The tamper event can also activate the auxiliary output if the controller is in Auxiliary Mode 3 (refer to Table 5). 6.7 If the controller is presented with wrong codes (PIN or Card) consecutively several times, the unit goes into Lockout mode. When a lockout occurs, the controllers reader and keypad are de-
activated so no codes can be entered until the set lockout period expires. During Lockout, Mode LED is off, the Door LED flashes red, and the controller beeps every two seconds. 6.8 The REX button is connected to a Rosslare secured series intelligent power supply. The REX button must be located inside the premises to be secured and is used to open the door without the use of a PIN code. It is usually located in a convenient location, such as inside the door or at a receptionist's desk. The function of the REX button depends on whether the Lock Strike Relay is programmed for Fail Safe Operation or Fail Secure Operation. BREX Function AYC-E/Q60 Family Instruction Manual 41 2 1 Controller Functionality Fail Secure Operation: From the moment the REX button is pressed, the door is unlocked until the Lock Strike Release Time passes. After this time, the door is locked even if the REX button is not released. Fail Safe Operation: From the moment the REX button is pressed, the door is unlocked until the REX button is released, plus the Lock Strike Release Time. In this case, the Lock Strike Relay only begins its count down once the REX button is released. Secured Series Intelligent Power Supply 6.9 Rosslares secured series intelligent power supplies are designed for use with Rosslare's secured series standalone access control units, including AYC-E/Q60. It is designed to operate indoors and installed within the secured premises. The AYC-E/Q60 must be used with one of Rosslares secured series intelligent power supplies, which provide Lock Strike output and REX input. Both units communicate through a proprietary Rosslare protocol, which provides a secure link between the AYC-E/Q60 and the secured series intelligent power supply unit. This in turn activates the door lock. The units also function as the power supply for the AYC-E/Q60; each unit also contains a speaker connection for all sounder abilities. For more information, see the specific secured series intelligent power supply manual. 6.10 Programming the AYC-E/Q60 is performed solely via the unit's keypad driven Programming Menu System. To reach the Programming Menu System, the AYC-E/Q60 must first be placed into Programming mode. See Section 6.10.1 for more information. During the AYC-E/Q60's manufacturing process, certain codes and settings are pre-
programmed. These settings are the called the Default Factory Programming the AYC-E/Q60 42 AYC-E/Q60 Family Instruction Manual Controller Functionality Settings. Table 4 shows the names of all the AYC-E/Q60 menus. It also shows of all the AYC-E/Q60s default factory codes and settings. Table 4: Controller Programming Menu Menu No. Menu Description 1 2 3 4 5 6 7 8 9 0 Changing Lock Strike Code Changing Auxiliary Code Changing Program Code Changing Normal/Secure Code Changing Normal/Bypass Code Changing Door Release Time Defining auxiliary inputs/outputs Set Lockout Backlight Behavior Rosslare PROX/HID Prox format Enrolling PIN Code Deleting PIN Code Code assignment with strike/auxiliary Return to factory defaults/Change PIN code Length 6 digits 48 digits Default 5 4 digits digits 2580 25802 258025 25802580 0852 08520 085208 08520852 1234 12341 123412 12341234 3838 38383 383838 38383838 N/A 0004 2004 4000 5100 6300 You will find a complete description and instructions for each of the above menu items on the following subsections. 6.10.1 Entering Programming Mode To enter Programming mode:
1. Press the # key twice within 2 seconds. The Mode LED turns off and the Door LED turns red Mode/Transmit Door/Program Red AYC-E/Q60 Family Instruction Manual 43 Controller Functionality 2. Enter your Programming code. The Door LED turns green and the AYC-E/Q60 enters Programming Mode. Mode/Transmit Door/Program Green The AYC-E/Q60 must be in Normal mode to enter Programming mode. The factory four-digit Programming code is 1234. If a Programming code is not entered within five seconds, the AYC-E/Q60 returns to Normal mode. 6.10.2 Exiting Programming Mode To exit Programming mode:
1. Press the # key twice within 2 seconds. You hear 3 beeps. The Door LED turns off and the Mode LED returns to Normal. Mode/Transmit Door/Program Green Wrong entries may reset the controller back to Normal mode. While in Programming mode, if no key is pressed for one minute, the AYC-E/Q60 exits Programming mode and returns to Normal mode. Mode/Transmit Green Door/Program 6.10.3 Changing Lock Strike Code The Lock Strike code is mainly used as a method to quickly test the Lock Strike Relay during installation. When the first user is added to the controller, the default Lock Strike code is automatically deleted. Once the code is programmed again, it is not deleted with the entry of additional User codes. 44 AYC-E/Q60 Family Instruction Manual Controller Functionality To change the Lock Strike code:
1. Enter Programming mode. 2. Press 1 to enter Menu 1. The Mode LED turns red. 3. Enter the new code you wish to set as the Lock Strike code. The system returns to Normal mode. You hear three beeps. Mode/Transmit Red Door/Program Green Mode/Transmit Green Door/Program Lock Strike code does not work in the Secure mode. Wrong entries return the controller to Normal mode. Code 0000 erases the Lock Strike code. The factory DEFAULT 4-digit Lock Strike code is 2580. 6.10.4 Changing Auxiliary Code The Auxiliary code is mainly used as a method to quickly test the Auxiliary Relay during installation. To change the Lock Strike code:
1. Enter Programming mode. 2. Press 2 to enter Menu 2. The Mode LED turns red. 3. Enter the new code you wish to set as Auxiliary code. Mode/Transmit Mode/Transmit Red Door/Program Green Door/Program Green AYC-E/Q60 Family Instruction Manual 45 Controller Functionality The system returns to Normal mode. You hear three beeps. Mode/Transmit Green Door/Program Auxiliary code does not work in the Secure mode. Wrong entries return the controller to Normal mode. Code 0000 erases the Auxiliary code. The factory default 4-digit Auxiliary code is 0852. 6.10.5 Changing the Programming Code To change the Programming code:
1. Enter Programming mode. 2. Press 3 to enter Menu 3. The Mode LED turns green. Mode/Transmit 3. Enter the new code you wish to set as Programming code. Mode/Transmit Green Green Door/Program Door/Program Green The system returns to Normal mode. You hear three beeps. Mode/Transmit Green Door/Program The Programming code cannot be erased; the code 0000 is invalid and does not erase the Programming code. The factory default 4-digit Programming code is 1234. 46 AYC-E/Q60 Family Instruction Manual Controller Functionality 6.10.6 Changing the Normal/Secure Code To change the Normal/Secure code:
1. Enter Programming mode. 2. Press 4 to enter Menu 4. The Mode LED flashes red. Mode/Transmit Mode/Transmit 3. Enter the new code you wish to set as Normal/Secure code. Door/Program Green Red Green Door/Program The system returns to Normal mode. You hear three beeps. Mode/Transmit Green Door/Program 6.10.7 Code 0000 erases the Normal/Secure code. This code is disabled if the Auxiliary Input is set to toggle between Normal and Secure access modes. The default Normal/Secure code is 3838. BChanging the Normal/Bypass Code and Door Chime Settings To change the Normal/Bypass code and door chime settings:
1. Enter Programming mode. 2. Press 5 to enter Menu 5. Door/Program Green The Mode LED flashes orange. Door/Program 3. There are four different ways to program the Normal/Bypass code Mode/Transmit Orange Green and door chime:
Mode/Transmit AYC-E/Q60 Family Instruction Manual 47 5 1 Controller Functionality Disable both Bypass code and the door chime. Enter the code 0000. Disable Bypass code and enable the door chime. Enter the code 0001. Enable Bypass code and disable the door chime. Enter any code ending with 0. Enable Bypass code and enable the door chime. Enter a code not ending with 0. The system returns to Normal mode. You hear three beeps. The Door LED turns off. The Mode LED turns green. Mode/Transmit Door/Program Green 6.10.8 Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time To set the Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time:
1. Enter Programming mode. Press 6 to enter Menu 6. The Mode LED flashes green. Mode/Transmit Mode/Transmit Door/Program Green Green Green Door/Program 48 AYC-E/Q60 Family Instruction Manual Controller Functionality 2. Construct a code using the following instructions:
First Digit For Fail Secure Operation, the first digit should be 0. For Fail Safe Operation the first digit should be 1. Second Digit Siren Time in minutes (1-9, 0-disabled) Third and Fourth Digits Enter the number of seconds (from 1 to 99) that you want the Lock Strike to be released. For example, 0312 means a Fail Secure Operation consisting of a 3-minute siren and a 12-second Lock Strike release time. The system returns to Normal mode. You hear three beeps. The Door LED turns off and the Mode LED turns green. Mode/Transmit Green Door/Program The default value is 0004, which corresponds to Fail Secure operation, no siren, and 4-seconds Lock Strike release time. AYC-E/Q60 Family Instruction Manual 49 Controller Functionality 6.10.9 Defining the Auxiliary Input and Output The default auxiliary setting is 2004. To define the auxiliary input and output:
1. Enter Programming mode. 2. Press 6 to enter Menu 6. The Mode LED flashes green. 3. Construct a code using the following instructions:
Auxiliary Mode Auxiliary Setting Auxiliary Mode Mode/Transmit Mode/Transmit Door/Program Green Green Green Door/Program In addition to the Lock Strike Relay and Lock Strike REX, the AYC-E/Q60 features an Auxiliary Input. The Auxiliary Mode defines the function of the Auxiliary Input. Auxiliary Settings Each of the Auxiliary Modes has a two digit setting that affects how the Auxiliary Mode functions. The system returns to Normal mode. You hear three beeps. The Door LED turns off and the Mode LED turns green. Mode/Transmit Green Door/Program 50 AYC-E/Q60 Family Instruction Manual Controller Functionality Table 5: Quick Reference Guide for Auxiliary Mode Setting Auxiliary Mode 0 Auxiliary Input Function AUX REX Auxiliary Output Activated by Valid code or AUX REX N.O. Auxiliary Relay Normal/Secure switch Valid code Normal/Secure switch Star button () Normal/Secure switch Tamper event Normal/Secure switch Door Monitor Door Monitor Door Monitor LED control Green Direct shunt Shunt Forced door Door ajar Valid code LED control Red Valid code N.O. N.O. N.C. N.O. N.C. N.C. N.C. N.O. N.O. 1 2 3 4 5 6 7 8 9 Auxiliary Settings
(in seconds) 01 to 99 Aux. relay release time 00 Aux. relay toggle 01 to 99 Aux. relay release time 00 Aux. relay toggle 01 to 99 Aux. relay release time 00 Aux. relay toggle 01 to 99 Aux. relay release time 00 Aux. relay tamper activated 01 to 99 Shunt time 01 to 99 Maximum shunt time 01 to 99 Forced delay 01 to 99 Ajar delay 01 to 99 Aux. relay release time 00 Aux. relay toggle 01 to 99 Aux. relay release time 00 Aux. relay toggle AYC-E/Q60 Family Instruction Manual 51 Controller Functionality 6.10.10 Detailed Reference Guide The following are brief descriptions of each auxiliary mode. To implement the features of each mode, refer to Section 6.10.9. 6.10.10.1 Auxiliary Mode 0 Auxiliary input function: Activates the auxiliary output Auxiliary output activated by: Valid user code, Auxiliary code, Auxiliary input For example, in Auxiliary Mode 0, the controller can function as a two-door controller. The auxiliary relay is to be attached to the lock on the second door. The auxiliary setting defines the door open time for the second door. The auxiliary input is to be attached to the REX pushbutton for the second door. The Door Monitor input feature for the second door is not enabled when using this mode. 6.10.10.2 Auxiliary Mode 1 Auxiliary input function: Toggles Normal/Secure modes Auxiliary output activated by: Valid user code, Auxiliary code For example, in Auxiliary Mode 1, the controller can function as a two-door controller. The auxiliary relay is to be attached to the lock on the second door. REX feature for the second door is not enabled when using this mode. The auxiliary setting defines the door open time for the second door. The auxiliary input can switch the mode of operation of the controller between Normal and Secure mode. By connecting a switch timer or alarm system output to the auxiliary input, the controller can be automatically switched from Normal mode (during office hours) to Secure mode (after office hours). 6.10.10.3 Auxiliary Mode 2 Auxiliary input function: Toggles normal/secure modes Auxiliary output activated by: Asterisk Button (*) For example, in Auxiliary Mode 2, the auxiliary relay can function as a general purpose time switch that can be activated when the asterisk button (*) is depressed. The auxiliary setting establishes for how long 52 AYC-E/Q60 Family Instruction Manual Controller Functionality the auxiliary relay is to be activated. The auxiliary input can switch the mode of operation of the controller between Normal and Secure modes. By connecting a switch timer or alarm system output to the auxiliary input, the controller can be automatically switched from Normal mode (during office hours) to Secure mode (after office hours). 6.10.10.4 Auxiliary Mode 3 Auxiliary input function: Toggles Normal/Secure modes Auxiliary output activated by: Alarms For example, in Auxiliary Mode 3, the auxiliary output is activated if the controller is tampered; that is, if the case is forcibly opened or removed from the wall. The auxiliary input can switch the mode of operation of the controller between Normal and Secure modes. By connecting a switch timer or alarm system output to the auxiliary input, the controller can be automatically switched from Normal mode (during office hours) to Secure mode (after office hours). 6.10.10.5 Auxiliary Mode 4 Auxiliary input function: Toggles Normal/Secure modes Auxiliary output activated by: Direct shunt (explanation below) For example, in Auxiliary Mode 4, the controller is capable of bypassing an alarm zone by shunting an alarm systems door sensor. The auxiliary output is to be wired in parallel to the door sensor output. When in use, the auxiliary output is normally open and the door sensor functions normally. When a valid code is entered, the auxiliary relay shunts the door sensor for the duration of the shunt time, as defined by the auxiliary setting. If the door is left open longer than the shunt time, an alarm is triggered. AYC-E/Q60 Family Instruction Manual 53 Controller Functionality 6.10.10.6 Auxiliary Mode 5 Auxiliary input function: Door Monitor Auxiliary output activated by: Shunt (explanation below) For example, in Auxiliary Mode 5, the controller is capable of shunting an alarm system. In this mode, the auxiliary input is to be wired to the magnetic contact switch on the door. The auxiliary relay is wired to the alarm system. Without a valid code entered, the auxiliary relay matches the condition of the magnetic contact switch; if the door opens, the auxiliary relay opens; if the door closes, the auxiliary relay closes. When a valid code is entered, a countdown for maximum shunt time, as defined by the auxiliary setting, begins; if the door is not closed before the maximum shunt time, the alarm is triggered. 6.10.10.7 Auxiliary Mode 6 Auxiliary input function: Door Monitor Auxiliary output activated by: Forced entry For example, in Auxiliary Mode 6, the controller can trigger the auxiliary relay if the door has been forced. If the siren settings are enabled, the siren is activated. In this mode, the auxiliary input functions as a door monitor switch and is wired to the magnetic contact switch on the door. The auxiliary relay is to be wired to the alarm system. If the door is forced open, the controller waits for the period of the forced door delay time to elapse and then it activates the auxiliary relay. The auxiliary setting sets the forced door delay period. 6.10.10.8 Auxiliary Mode 7 Auxiliary input function: Door Monitor Auxiliary output activated by: Door Ajar (door held open) For example, in Auxiliary Mode 7, the controller can trigger the auxiliary relay, if it detects that the door has been held open (ajar) too long. In this mode, the auxiliary input functions as a door monitor switch and is wired to the magnetic contact switch on the door. The auxiliary relay is to be wired to the alarm system. If the door is opened, the controller waits for the Door Ajar Delay time to elapse 54 AYC-E/Q60 Family Instruction Manual Controller Functionality and if the door does not close prior to the end of this period, the controller activates the auxiliary relay. The auxiliary setting defines the door-ajar time. 6.10.10.9 Auxiliary Mode 8 Auxiliary input function: Green LED control Auxiliary output activated by: Valid user code, Auxiliary code For example, in Auxiliary Mode 8, the controller can function as a two-door controller and also provide indicator functionality control. The auxiliary relay is connected to the lock on the second door. The auxiliary setting defines the door open time for the second door. The auxiliary input is used to control the door indicator. If the auxiliary input is open, the indicator flashes green; if the auxiliary input is closed, the door indicator flashes red. This mode takes control of the Door Indicator LED. The indicator LED is not lit when:
A valid code is entered While in Secure mode when waiting for secondary code. 6.10.10.10 Auxiliary Mode 9 Auxiliary input function: Red LED control Auxiliary output activated by: Valid user code, Auxiliary code For example, in Auxiliary Mode 9, the controller can function as a two-door controller and also provide indicator functionality control. The auxiliary relay is connected to the lock on the second door. The auxiliary setting defines the door open time for the second door. The auxiliary input is used to control the indicator. If the auxiliary input is open, the door indicator flashes red; if the auxiliary input is closed the door indicator flashes green. This mode takes control of the Door Indicator LED. The indicator LED is not lit when:
A valid code is entered While in Secure mode when waiting for secondary code. AYC-E/Q60 Family Instruction Manual 55 Controller Functionality 6.10.11 Setting the Lockout Feature If the controller is presented with wrong codes consecutively several times, the unit goes into Lockout mode. When a lockout occurs, the controller keypad and reader are locked so no codes can be entered until the set lockout period expires. During Lockout, Mode LED is off, the door LED flashes red, and the controller beeps every two seconds. The default setting for the Lockout Feature is 4000 (Lockout Disabled). Using the lockout feature is highly recommended, especially when using a short PIN code length (4 or 5 digits). Mode/Transmit Mode/Transmit Door/Program Green Green Green Door/Program To set the lockout feature:
1. Enter Programming mode. 2. Press 6 to enter Menu 6. The Mode LED flashes green. 3. Construct a code using the following instructions:
Set the number of wrong code attempts, which causes a Lockout between 0 and 9 attempts. Sets the Duration of the lockout, between 00 and 99; the value is multiplied by ten, resulting in 0 to 990 seconds. 56 AYC-E/Q60 Family Instruction Manual Controller Functionality 6.10.12 Setting the Backlight Behavior The controller allows you to define the way the units' Backlight works. To set the backlight operation:
1. Enter Programming mode. 2. Press 6 to enter Menu 6. The Mode LED flashes green. Mode/Transmit Mode/Transmit Door/Program Green Green Green Door/Program 3. Enter one of the following codes:
5000 Backlight Off 5100 Backlight On (default) 5200 Backlight Off, activated on any key press for ten seconds. 5300 Backlight Dimmed, backlight activated on any key press for ten seconds 6.10.13 Selecting the Rosslare PROX and HID Prox Format The controller allows you to select the Rosslare PROX and HID Prox format. To select the Rosslare PROX and HID Prox format:
Mode/Transmit 1. Enter Programming mode. Green 2. Press 6 to enter Menu 6. Door/Program The Mode LED flashes green. Mode/Transmit Green Green Door/Program AYC-E/Q60 Family Instruction Manual 57 Controller Functionality 3. Enter one of the following codes:
6100 Rosslare PROX 6200 HID Prox 6300 Rosslare PROX + HID Prox (default) 6.10.14 Enrolling Primary and Secondary Codes Primary codes Primary codes can only be enrolled to an empty user slot, meaning a slot where there is no existing primary code. Primary codes must be unique, meaning one users Primary code may not be the same as other users Primary code. Primary codes cannot be the same as any system codes, such as the Normal/Secure code or Lock Strike code. Users who hold a Primary code can gain entry only during Normal mode. Secondary codes Secondary codes can only be enrolled to user slot that already has a Primary code enrolled but no Secondary code. Secondary codes do not have to be unique, meaning multiple users can all hold the same Secondary code. Secondary codes cannot be the same as any system codes, such as the Normal/Secure code or Lock Strike codes. Users who hold Secondary codes can gain entry in any mode of operation. There are two methods to enroll Primary and Secondary codes:
Standard Method The Standard Method is mainly used when the user slot number for the user you wish to program is known. You can program both Primary and Secondary codes using the Standard Method
(see Section 6.10.14.1). 58 AYC-E/Q60 Family Instruction Manual Controller Functionality Code Search Method The Code Search Method is mainly used when enrolling a users Secondary code and the User Slot code is unknown. The Code Search method only works if a users Primary code is already enrolled but the Secondary code is not (see Section 6.10.14.2). 6.10.14.1 Enrolling Primary and Secondary Codes using the Standard Method To enroll primary and secondary codes using the Standard method:
Mode/Transmit Door/Program Green Door/Program Orange 1. Enter Programming mode. 2. Press 7 to enter Menu 7. The Mode LED turns orange. 3. Perform one of the following:
Enter the 3-digit user slot number between 001and 500 for the slot to which you wish to enroll a Primary or Secondary code. For example, User Slot 003 represents User #3. Present your user card. If the selected slot has no Primary code, the Mode LED flashes green, indicating that the controller is ready to accept a Primary code. Mode/Transmit Mode/Transmit Green Orange Door/Program AYC-E/Q60 Family Instruction Manual 59 Controller Functionality If the selected slot already has a Primary code but no Secondary code, the Mode LED flashes red, indicating that the controller is ready to accept a Secondary code. If the selected slot already has a Primary and Secondary code, you hear a long beep and the controller returns to Normal mode. 4. Perform one of the following:
Enter the PIN code that you want to assign as the Primary or Secondary code for this slot number. Present your user card. Mode/Transmit Red Orange Door/Program Door/Program Mode/Transmit Green If the PIN or user card presented is valid, the Mode LED stops flashing and the controller is ready for you to enter the next 3-
digit slot number (refer to Step 3) for the slot to which you want to assign a code. 5. Do one of the following:
Press the # key to move to the next slot number. If you do not wish to continue enrolling codes, press the
# key twice and the controller returns to Normal mode. 60 AYC-E/Q60 Family Instruction Manual Controller Functionality 6.10.14.2 Enrolling Secondary Codes using the Code Search Method The Code Search feature enables you to quickly enroll a Secondary code to a user who already has a Primary code. To enroll secondary codes using the Code Search method:
1. Enter Programming mode. 2. Press 7 to enter Menu 7. The Mode LED turns orange. 3. Perform one of the following:
a. Enter 000 as the 3-digit user slot number. b. Present your user card. The Door LED flashes orange. Mode/Transmit Door/Program Green Mode/Transmit Mode/Transmit Door/Program Orange Orange Door/Program The controller is now waiting for the Primary code of the user to whom you want to add a Secondary code. 4. Perform one of the following:
a. Enter the Primary code belonging to the user for whom you wish to add a Secondary code. b. Present your user card. 5. The Mode LED flashes red. Mode/Transmit Red Orange Door/Program If the Primary code entered is not valid, you hear a long beep and the AYC-E/Q60 continues to wait for a valid Primary code. AYC-E/Q60 Family Instruction Manual 61 Controller Functionality 6. Perform one of the following:
a. Enter the code to be used as the Secondary code. b. Present your user card. If the Secondary code is valid, the controller beeps three times and returns to Normal mode. If the Secondary code is invalid, the controller sounds a long beep, and the AYC-E/Q60 continues to wait for a valid Secondary code to be entered. BDeleting Primary and Secondary Codes 6.10.15 5 There are two methods to delete Primary and Secondary codes: the Standard Method and the Code Search Method. When deleting a user slot, both the Primary code and the Secondary code are erased. 6.10.15.1 8 BDeleting Primary and Secondary Codes using the Standard Method To delete the Primary and Secondary codes using the Standard Method:
1. Enter Programming mode. 2. Press 8 to enter Menu 8. The Mode LED turns orange and the Mode LED turns red. 3. Enter the 3-digit User Slot code you wish to delete. Mode/Transmit Mode/Transmit Door/Program Green Red Orange Door/Program 62 AYC-E/Q60 Family Instruction Manual 9 6 Controller Functionality The Mode LED flashes red indicating the controller is waiting for the Programming code to confirm the deletion. If the user slot is empty, you hear a long beep and the AYC-
E/Q60 returns to Normal mode. 4. Enter your Programming code to confirm the deletion. Mode/Transmit Red Orange Door/Program If the Programming code is valid, three beeps are heard and the controller returns to Normal mode. If the Programming code is invalid, a long beep is heard and the controller returns to Normal mode. It is recommended that a record be kept of added and deleted users so that it is easier to keep track of which user slots are empty and which user slots are not. 6.10.15.2 Deleting Primary and Secondary Codes using the Code Search Method To delete the Primary and Secondary codes using the Code Search Method:
1. Enter Programming mode. 2. Press 8 to enter Menu 8. The Mode LED turns red and the Door LED turns orange. 3. Enter 000 as the 3-digit user slot number. The Door LED flashes orange. Mode/Transmit Mode/Transmit Door/Program Green Red Orange Door/Program Mode/Transmit Red Orange Door/Program AYC-E/Q60 Family Instruction Manual 63 Controller Functionality The controller is now waiting for the Primary code of the user you want to delete. 4. Enter the 4-8 digit PIN code of the Primary code belonging to the user you want to delete. The Mode LED flashes red. Mode/Transmit Red Orange Door/Program 5. Enter your Programming code to confirm the deletion. If the Programming code is valid, you hear three beeps and the unit returns to Normal mode. If the Programming code is invalid, you hear a long beep and the unit returns to Normal mode. It is recommended that a record be kept of added and deleted users so that it is easier to keep track of which user slots are empty and which user slots are not. 6.10.16 Relay Codes Assignment When a primary code is enrolled for any user, the user is authorized to activate the Lock Strike relay. However, different user codes may be set to operate the auxiliary relay instead or operate both the Lock strike and auxiliary relay. Assignment of such codes is achievable for any valid user code entered in the controller. There are two methods to assign relay codes to users: a standard method and a search method. 6.10.16.1 Relay Code Assignment using the Standard Method To assign relay code using the Standard method:
1. Enter Programming mode. 2. Press 9 to enter Menu 9. The Mode LED turns green and the Door LED turns orange. Mode/Transmit Door/Program Green Mode/Transmit Door/Program Green Orange 64 AYC-E/Q60 Family Instruction Manual Controller Functionality 3. Enter the 3-digit user slot for code assignment. The Mode LED flashes green. Mode/Transmit Door/Program Green Orange 4. Enter the assignment digit for the current user slot:
1 activates the Lock Strike relay only default 2 activates the Auxiliary relay only 3 activates the Lock Strike and Auxiliary relays If the assignment code is valid, the Mode indicator stops flashing. The controller is now waiting for another slot number. 5. Press the # key to move to the next slot or enter a new slot 6. number. If you do not wish to continue, press the # key twice and the controller returns to Normal mode. 6.10.16.2 Relay Code Assignment using the Search Method To assign relay code using the Search method:
1. Enter Programming mode. 2. Press 9 to enter Menu 9. The Mode LED turns green and the Door LED turns orange. 3. Enter 000 for user slot access. The Door LED flashes orange. Mode/Transmit Door/Program Green Mode/Transmit Door/Program Green Orange Mode/Transmit Door/Program Green Orange The controller is now waiting for the primary code of the user. 4. Enter the primary code belonging to the user. AYC-E/Q60 Family Instruction Manual 65 Controller Functionality 5. The Mode LED flashes green. Mode/Transmit Door/Program Green Orange 6. Enter the assignment digit for the current user slot:
1 activates the Lock Strike relay only default 2 activates the Auxiliary relay only 3 activates the Lock Strike and Auxiliary relays If the assignment digit is valid, three beeps are heard and the controller returns to Normal mode. If the assignment digit is invalid, a long beep sounds and the controller waits for another assignment digit to be entered. 6.10.17 PIN Code Length/Factory Default Settings You must be very careful before using this command!
Changing the PIN code length also erases the entire memory contents, including all user and special codes, and return all codes to their factory-default settings. 1. Enter Programming mode. Mode/Transmit 2. Select the desired PIN code length as follows:
Door/Program Green 00 Returns to factory defaults and sets a 4-digit code. 05 Returns to factory defaults and sets a 5-digit code. 06 Returns to factory defaults and sets a 6-digit code. 08 Returns to factory defaults and sets a 4-8 digit code Note: When choosing the 4 -8 option, please note that you should either enter zeros before the code, or press pound at the end (for example if your code is 12345, enter either 00012345 or 12345#). Both the Mode and Door LEDs flash red. Mode/Transmit Red Red Door/Program 3. Enter your 4- to 8-digit Programming code. 66 AYC-E/Q60 Family Instruction Manual Controller Functionality If the Programming code is valid, all memory is erased. You hear three beeps and the controller returns to Normal mode. If the Programming code is invalid, you hear a long beep and the controller returns to Normal mode without erasing the memory contents. 6.10.18 Replacing a Lost Programming Code The AYC-E/Q60 must be in Normal mode; otherwise, this does not work. Make sure that the Mode LED is green before proceeding. 1. Remove power from the Power Supply Unit. 2. Press the REX button on the Power Supply Unit. 3. Apply power to the unit with REX button pressed. 4. Release the REX button. 5. You now have 15 seconds to program a new Programming code into the Access Control unit using the default code based on the PIN code length you chose (see Table 4) before the controller reverts to the existing code. 6.10.19 Replacing a Lost Normal/Secure Code The AYC-E/Q60 must be in Secure mode; otherwise, this does not work. Make sure that the Mode LED is red before proceeding. 1. Remove power from the Power Supply Unit. 2. Press the REX button on the Power Supply Unit. 3. Apply power to the unit with the REX button pressed. 4. Release the REX button. 5. You now have 15 seconds to program a new Normal/Secure code into the Access Control unit using the default code based on the PIN code length you chose (see Table 4) before the controller reverts to the existing code. AYC-E/Q60 Family Instruction Manual 67 Declaration of Conformity A. Declaration of Conformity This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. The manufacturer is not responsible for any radio or TV interference caused by unauthorized modifications to this equipment. Such modifications could void the user's authority to operate the equipment. 68 AYC-E/Q60 Family Instruction Manual Limited Warranty B. Limited Warranty ROSSLARE ENTERPRISES LIMITED (ROSSLARE) FIVE-YEAR LIMITED WARRANTY is applicable worldwide. This warranty supersedes any other warranty. ROSSLARE'S TWO-YEAR LIMITED WARRANTY is subject to the following conditions:
WARRANTY Warranty of ROSSLARE'S products extends to the original purchaser
(Customer) of the ROSSLARE product and is not transferable. PRODUCTS COVERED BY THIS WARRANTY AND DURATION ROSSLARE ENTERPRISES LTD. AND/OR SUBSIDIARIES (ROSSLARE) warrants the AYC-E/Q60 Metal Convertible Reader/Secured Controller Family (as listed above) to be free from defects in materials and assembly in the course of normal use and service. The warranty period commences with the date of shipment to the original purchaser and extends for a period of 5 years (60 months). WARRANTY REMEDY COVERAGE In the event of a breach of warranty, ROSSLARE will credit Customer with the price of the Product paid by Customer, provided that the warranty claim is delivered to ROSSLARE by the Customer during the warranty period in accordance with the terms of this warranty. Unless otherwise requested by a ROSSLARE representative, return of the failed product(s) is not immediately required. If ROSSLARE has not contacted the Customer within a sixty (60) day holding period following the delivery of the warranty claim, Customer will not be required to return the failed product(s). All returned Product(s), as may be requested at ROSSLARES sole discretion, shall become the property of ROSSLARE. To exercise the warranty, the user must contact ROSSLARE Enterprises Ltd. to obtain an RMA number after which, the product must be returned to the Manufacturer freight prepaid and insured. In the event ROSSLARE chooses to perform a product evaluation within the sixty (60) day holding period and no defect is found, a AYC-E/Q60 Family Instruction Manual 69 Limited Warranty minimum US$ 50.00 or equivalent charge will be applied to each Product for labor required in the evaluation. ROSSLARE will repair or replace, at its discretion, any product that under normal conditions of use and service proves to be defective in material or workmanship. No charge will be applied for labor or parts with respect to defects covered by this warranty, provided that the work is done by ROSSLARE or a ROSSLARE authorized service center. EXCLUSIONS AND LIMITATIONS ROSSLARE shall not be responsible or liable for any damage or loss resulting from the operation or performance of any Product or any systems in which a Product is incorporated. This warranty shall not extend to any ancillary equipment not furnished by ROSSLARE, which is attached to or used in conjunction with a Product, nor to any Product that is used with any ancillary equipment, which is not furnished by ROSSLARE. This warranty does not cover expenses incurred in the transportation, freight cost to the repair center, removal or reinstallation of the product, whether or not proven defective. Specifically excluded from this warranty are any failures resulting from Customer's improper testing, operation, installation, or damage resulting from use of the Product in other than its normal and customary manner, or any maintenance, modification, alteration, or adjustment or any type of abuse, neglect, accident, misuse, improper operation, normal wear, defects or damage due to lightning or other electrical discharge. This warranty does not cover repair or replacement where normal use has exhausted the life of a part or instrument, or any modification or abuse of, or tampering with, the Product if Product disassembled or repaired in such a manner as to adversely affect performance or prevent adequate inspection and testing to verify any warranty claim. ROSSLARE does not warrant the installation, maintenance, or service of the Product. Service life of the product is dependent upon the care it receives and the conditions under which it has to operate. In no event shall ROSSLARE be liable for incidental or consequential damages. 70 AYC-E/Q60 Family Instruction Manual Limited Warranty LIMITED WARRANTY TERMS This warranty sets forth the full extent of ROSSLARES warranty. The terms of this warranty may not be varied by any person, whether or not purporting to represent or act on behalf of ROSSLARE. This limited warranty is provided in lieu of all other warranties. All other warranties expressed or implied, including without limitation, implied warranties of merchantability and fitness for a particular purpose, are specifically excluded. In no event shall ROSSLARE be liable for damages in excess of the purchase price of the product, or for any other incidental, consequential or special damages, including but not limited to loss of use, loss of time, commercial loss, inconvenience, and loss of profits, arising out of the installation, use, or inability to use such product, to the fullest extent that any such loss or damage may be disclaimed by law. This warranty shall become null and void in the event of a violation of the provisions of this limited warranty. AYC-E/Q60 Family Instruction Manual 71 AYC-E/Q60 Family Latin America Rosslare Latin America Buenos Aires, Argentina support.la@rosslaresecurity.com China Rosslare Electronics (Shenzhen) Ltd. Shenzhen, China Tel:
+86 755 8610 6842 Fax: +86 755 8610 6101 support.cn@rosslaresecurity.com Asia Pacific, Middle East, Africa Rosslare Enterprises Ltd. Kowloon Bay, Hong Kong Tel:
+852 2795-5630 Fax: +852 2795-1508 support.apac@rosslaresecurity.com United States and Canada Rosslare Security Products, Inc. Southlake, TX, USA Toll Free:
Local: +1-817-305-0006 Fax:
+1-817-305-0069 support.na@rosslaresecurity.com Europe Rosslare Israel Ltd. Rosh HaAyin, Israel
+972 3 938-6838 Tel:
Fax: +972 3 938-6830 support.eu@rosslaresecurity.com
+1-866-632-1101 www.rosslaresecurity.com 0 0
9 3 4 0 6 9 0
6 0 7 0
frequency | equipment class | purpose | ||
---|---|---|---|---|
1 | 2012-03-28 | 0.125 ~ 0.125 | DCD - Part 15 Low Power Transmitter Below 1705 kHz | Original Equipment |
app s | Applicant Information | |||||
---|---|---|---|---|---|---|
1 | Effective |
2012-03-28
|
||||
1 | Applicant's complete, legal business name |
Rosslare Enterprises Ltd
|
||||
1 | FCC Registration Number (FRN) |
0008472821
|
||||
1 | Physical Address |
Room 905
|
||||
1 |
Kowloon Bay, Kowloon, N/A
|
|||||
1 |
Hong Kong
|
|||||
app s | TCB Information | |||||
1 | TCB Application Email Address |
T******@TIMCOENGR.COM
|
||||
1 | TCB Scope |
A1: Low Power Transmitters below 1 GHz (except Spread Spectrum), Unintentional Radiators, EAS (Part 11) & Consumer ISM devices
|
||||
app s | FCC ID | |||||
1 | Grantee Code |
GCD
|
||||
1 | Equipment Product Code |
AYC-Q60
|
||||
app s | Person at the applicant's address to receive grant or for contact | |||||
1 | Name |
J******** L********
|
||||
1 | Title |
Engineering Manager
|
||||
1 | Telephone Number |
847-8********
|
||||
1 | Fax Number |
847-8********
|
||||
1 |
j******@rel-napdc.com
|
|||||
app s | Technical Contact | |||||
n/a | ||||||
app s | Non Technical Contact | |||||
n/a | ||||||
app s | Confidentiality (long or short term) | |||||
1 | Does this application include a request for confidentiality for any portion(s) of the data contained in this application pursuant to 47 CFR § 0.459 of the Commission Rules?: | No | ||||
1 | Long-Term Confidentiality Does this application include a request for confidentiality for any portion(s) of the data contained in this application pursuant to 47 CFR § 0.459 of the Commission Rules?: | No | ||||
if no date is supplied, the release date will be set to 45 calendar days past the date of grant. | ||||||
app s | Cognitive Radio & Software Defined Radio, Class, etc | |||||
1 | Is this application for software defined/cognitive radio authorization? | No | ||||
1 | Equipment Class | DCD - Part 15 Low Power Transmitter Below 1705 kHz | ||||
1 | Description of product as it is marketed: (NOTE: This text will appear below the equipment class on the grant) | CONVERTIBLE READER AND CONTROLLER | ||||
1 | Related OET KnowledgeDataBase Inquiry: Is there a KDB inquiry associated with this application? | No | ||||
1 | Modular Equipment Type | Does not apply | ||||
1 | Purpose / Application is for | Original Equipment | ||||
1 | Composite Equipment: Is the equipment in this application a composite device subject to an additional equipment authorization? | No | ||||
1 | Related Equipment: Is the equipment in this application part of a system that operates with, or is marketed with, another device that requires an equipment authorization? | No | ||||
1 | Is there an equipment authorization waiver associated with this application? | No | ||||
1 | If there is an equipment authorization waiver associated with this application, has the associated waiver been approved and all information uploaded? | No | ||||
app s | Test Firm Name and Contact Information | |||||
1 | Firm Name |
Waltek Services(Shenzhen) Co., Ltd.
|
||||
1 | Name |
P****** z****
|
||||
1 | Telephone Number |
0086-********
|
||||
1 | Fax Number |
0086-********
|
||||
1 |
p******@waltek.com.cn
|
|||||
Equipment Specifications | |||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Line | Rule Parts | Grant Notes | Lower Frequency | Upper Frequency | Power Output | Tolerance | Emission Designator | Microprocessor Number | |||||||||||||||||||||||||||||||||
1 | 1 | 15C | 0.12500000 | 0.12500000 |
some individual PII (Personally Identifiable Information) available on the public forms may be redacted, original source may include additional details
This product uses the FCC Data API but is not endorsed or certified by the FCC