Repeater User Manual ModelNAS-RP01Z1U
(S2 Version) Thank you for your support Please read the instruction manual carefully before operating Please keep the instruction manual for further reference This product can be included and operated in any Z-Wave network with other Z-Wave certified devices from other manufacturers and/or other applications. All non-battery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network. Operation configuration Specifications Power Supply Power Consumption Operational Temperature 85 240V AC, 50/60Hz Up to 0.8W 0 - 40 Communication frequency Range Detect temperature range 908.40MHz, 916.00MHz(US) Up to 80m indoors (depending on the building structure) Up to 100m outdoors.
-20~80 Compatible with any Z-Wave main controller. The use distance of the equipment can be increased by repeater, and the distance can be increased by up to 100 m. With a temperature probe, the temperature can be detected, the detection range is -20 ~ 80 Use of flame retardant materials Z-Wave Network Inclusion/Exclusion/Reset There is one button on the side of the device, it can be executed inclusion, exclusion and reset from Z-
Wave network. Add Remove 1 Power up the device. 2 Set Z-Wave Controller into inclusion mode 3 Press and hold the button for 5s until green led lights is on, then release the button before green led turn off. 1 Power up the device. 2 Set Z-Wave Controller into exclusion mode 3 Press and hold the button for 5s until Green led lights is on, then release the button before green led turn off. 1 Power up the device. Blue led will blink with 1s until inclusion successful. interval Blue led will blink with 1s until exclusion successful. interval Factory Reset Product Mode 2 Press and hold the button for 10s until Red led lights is on, then release the button before red led turn off. 1 Press and hold the button. Test 2 Power on the device, device will enter factory product test mode Send NIF Press and hold the button for 5s until Green led lights is on, then release the button before green led turn off. Notice 1: When device enters into inclusion mode, the device all functionality will be useless. The inclusion mode will be timeout after 30s, user can press and hold the button for 5s to terminate inclusion mode. Notice 2: Factory Reset will clear the device all Z-Wave Network data (include home id, node id, etc) saved in memory, and restore all configuration parameters to factory default. Please use this procedure only when the network primary controller is missing or otherwise inoperable. Notice 3: NIF Node Information Association The device supports 5 association groups, and each group supports max 5 associated nodes. Group 1, Lifeline All nodes which associated in group 1(lifeline group) will receive the messages that send by device through lifeline. Group 2, all nodes which associated in group 2 will be controlled by device through BASIC_SET command. When ambient temperature value is less than the setting value in Configuration: No.6, device will trigger a low temperature Alarm and send a BASIC_SET = 0xFF to the nodes that associated in group 2. And BASIC_SET = 0x00 will be sent when temperature value is large than the setting value in Configuration: No.6. Group 3, all nodes which associated in group 3 will be controlled by device through BASIC_SET command. When ambient temperature value is less than the setting value in Configuration: No.7, device will trigger a low temperature Alarm and send a BASIC_SET = 0xFF to the nodes that associated in group 3. And BASIC_SET = 0x00 will be sent when temperature value is large than the setting value in Configuration: No.7. Group 4, all nodes which associated in group 4 will be controlled by device through BASIC_SET command. When ambient humidity value is less than the setting value in Configuration: No.8, device will trigger a low humidity Alarm and send a BASIC_SET = 0xFF to the nodes that associated in group 4. And BASIC_SET = 0x00 will be sent when humidity value is large than the setting value in Configuration: No.8. Group 5, all nodes which associated in group 5 will be controlled by device through BASIC_SET command. When ambient humidity value is less than the setting value in Configuration: No.9, device will trigger a low humidity alarm and send a BASIC_SET = 0xFF to the nodes that associated in group 5. And BASIC_SET = 0x00 will be sent when humidity value is large than the setting value in Configuration: No.9. The Command Class supported by each association group is shown in the table below:
Group 1 (Lifeline) 2 (Control) 3 (Control) 4 (Control) 5 (Control) Command Class COMMAND_CLASS_SENSOR_MULTILEVEL COMMAND_CLASS_INDICATOR COMMAND_CLASS_DEVICE_RESET_LOCALLY COMMAND_CLASS_BASIC COMMAND_CLASS_BASIC COMMAND_CLASS_BASIC COMMAND_CLASS_BASIC Command SENSOR_MULTILEVEL_REPORT INDICATOR_REPORT DEVICE_RESET_LOCALLY_NOTIFICATION BASIC_SET BASIC_SET BASIC_SET BASIC_SET Device Functionality and Z-Wave Message Report This device has two main functions: repeater and ambient temperature and humidity measured. Repeater This device is a z-wave repeater device. In the z-wave network, it can be as a router to extend the communication distance. Temperature and humidity monitor The device have embeds a temperature and humidity sensor to monitor ambient temperature and humidity variation and report to z-wave hubs. Command Class Sensor Multilevel Temperature Sensor When the ambient temperature differential over 1.0 or 1.0 degree F(in default, and decides by Configuration No. 4), the device will unsolicited to send a SENSOR_MULTILEVEL_REPORT to nodes which associated in lifeline. Command Class Command Type Scale COMMAND_CLASS_SENSOR_MULTILEVEL SENSOR_MULTILEVEL_REPORT Air Temperature 0.1 Degree Celsius / Fahrenheit(US) Humidity Sensor When the relative humidity differential over 1.0%RH (in default, and decides by Configuration No. 5), the device will unsolicited to send a SENSOR_MULTILEVEL_REPORT to nodes which associated in lifeline. Command Class Command Type Scale COMMAND_CLASS_SENSOR_MULTILEVEL SENSOR_MULTILEVEL_REPORT Humidity 0.1% RH Command Class Configuration The device supports the controller to configure parameters of the device through Configuration Command Class, and the device has 11 parameters available for users to set according to their different needs:
Sensor Running Indicator Enable 1When sensor enters to measure mode, this setting decides the Led indicated or not. 0 No led blinks. 1 led blinks with red. Parameter Number 1 Size (Byte) 1 Available Settings 0, 1 Default value 1 2) OTA Led Disable WhenOTA is running, this setting decides the Led blinking or not. 0 No Led blinks. 1 Led blinks with yellow. Parameter Number 2 Available Settings 0, 1 Size (Byte) 1 Default value 1 3) Temperature OffsetValue The current measuring temperature value can be add and minus a value by this setting. Temperature OffsetValue = [Value] 0.1 Degree Celsius / Fahrenheit (US). Parameter Number 3 Available Settings
-120 ~ 120 Default value 0 Size (Byte) 1 4) Humidity Offset Value The current measuring humidity value can be add and minus a value by this setting. Humidity Offset Value = [Value] 0.1 RH%. Parameter Number 4 Available Settings
-120 ~ 120 Size (Byte) 1 Default value 0 5) Temperature D-Value Setting This configuration sets the changed value of the temperature. When the difference from the last report exceeds this setting value, the device will report current temperature value to Z-Wave Hubs. The D- Value = [Value] 0.1 Degree Celsius / Fahrenheit (US). Parameter Number 5 Available Settings 0 ~ 100 Default value 10 Size (Byte) 1 6) Humidity D-Value Setting This configuration sets the changed value of the humidity. When the difference from the last report exceeds this setting value, the device will report current humidity value to Z-Wave Hubs. The D- Value = [Value] 0.1 RH%. Parameter Number Size (Byte) 1 6 Default value (min) 20 Available Settings 0 ~ 100 7) Low Temperature Alarm Value This parameter is configuredthe threshold value that alarm level for low temperature. When the current ambient temperature value is less than this configuration value, device will trigger an alarm through the device associated in group 2. The Alarm Value = [Value] 0.1 Degree Celsius / Fahrenheit (US). Parameter Number 7 Available Settings
-200 ~ 600 Default value 180 Size (Byte) 2 8) HighTemperature Alarm Value This parameter is configuredthe threshold value that alarm level for High temperature. When the current ambient temperature value is large than this configuration value, device will trigger an alarm through the device associated in group 3. The Alarm Value = [Value] 0.1 Degree Celsius / Fahrenheit (US). Parameter Number 8 Available Settings
-200 ~ 600 Size (Byte) 2 Default value 300 9) Low Humidity Alarm Value This parameter is configuredthe threshold value that alarm level for low humidity. When the current ambient humidity value is less than this configuration value, device will trigger an alarm through the device associated in group 4. The Alarm Value = [Value] 0.1 RH%. Size (Byte) Parameter Number 9 2 Available Settings 200 ~ 850 Default value 400 10) HighHumidity Alarm Value This parameter is configuredthe threshold value that alarm level for high humidity. When the current ambient humidity value is large than this configuration value, device will trigger an alarm through the device associated in group 5. The Alarm Value = [Value] 0.1 RH%. Parameter Number 10 Available Settings 200 ~ 850 Default value 700 Size (Byte) 2 11) Sensor Measuring Interval This parameter is configuredthe time interval for sensor measuring interval time. This value is larger, the sensor values updates slowly. 0 Sensor Measuring Disable. Unit: Second. Parameter Number 11 Available Settings 0 ~ 30000 Default value 10 Size (Byte) 2 12) Heartbeat Time This parameter is configuredthe time interval for sensor values report to Z-Wave Hubs and ignore the sensor D-Values. 0 Heartbeat Time Disable, None Data Report to Hubs. Unit: Second. Parameter Number 12 Available Settings 0 ~ 30000 Default value 3600 Size (Byte) 2 Command Class Basic This device support COMMAND_CLASS_BASIC to control other devices associated in group 2, 3, 4, 5. The devices associated in group 2, 3 , 4, 5 must be the AOS device or FLiRS Device. The BASIC_SET value can refer to Association Group 2, 3, 4, 5 SmartStart SmartStart enabled products can be added into a Z-Wave network by scanning the Z-Wave QR Code present on the product with a controller providing SmartStart inclusion. No further action is required and the SmartStart product will be added automatically within 10 minutes of being switched on in the network vicinity. This device supports SmartStart function. QR code is printed on the label that pasted on on surface of product and the outside of packing box. And the full DSK code is printed can be found on the packing box. The device will enter SmartStart if the device is not included in network after power up. And then 2nd SmartStart time delay approximately 16s 3rd SmartStart time delay approximately 32s 4th SmartStart time delay approximately 64s 5th SmartStart time delay approximately 128s 6th SmartStart time delay approximately 256s 7th SmartStart time delay approximately 512s Afterwards, the Smartstart mode will be auto running with 512 second interval until device is included successfully. Security Network The device supports the security function with and S2 + SmartStart encrypted communication. The device will auto switch to the security mode when the device included with a security controller. In the security mode, the follow commands must use security or security_2 command class wrapped to communicate, otherwise the device will not response any commands. Security Keys This device supports security levels are listed in below table:
Support (Yes/No) Security Levels Yes SECURITY_KEY_S0 SECURITY_KEY_S2_UNAUTHENTICATED Yes Yes SECURITY_KEY_S2_AUTHENTICATED SECURITY_KEY_S2_ACCESS No All Supports Command Class in Each NIF Lists Command Class Version Not Included Non-secure Included S0 Included S2 Included Non-Secure Secure Non-Secure Secure COMMAND_CLASS_ZWAVEPLUS_INFO COMMAND_CLASS_SECURITY COMMAND_CLASS_SECURITY_2 2 1 1 COMMAND_CLASS_TRANSPORT_SERVICE COMMAND_CLASS_VERSION COMMAND_CLASS_POWERLEVEL COMMAND_CLASS_ASSOCIATION COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION COMMAND_CLASS_ASSOCIATION_GRP_INFO COMMAND_CLASS_MANUFACTURER_SPECIFIC COMMAND_CLASS_DEVICE_RESET_LOCALLY COMMAND_CLASS_SENSOR_MULTILEVEL COMMAND_CLASS_INDICATOR COMMAND_CLASS_CONFIGURATION COMMAND_CLASS_SUPERVISION COMMAND_CLASS_FIRMWARE_UPDATE_MD 2 3 1 2 3 1 2 1 11 3 4 1 5 Notice 1: When device is included with S0 level, COMMAND_CLASS_MANUFACTURER_SPECIFIC is supported non-securely. And when device is included with S2 level, COMMAND_CLASS_MANUFACTURER_SPECIFIC is supported securely only. Notice 2: Indicates the corresponding command class is supported in NIF, Blank means the command class is not supported. Led Color Indicator Led Color Red Green Blue Yellow Action Light On 1s When Power On Blink One Time Light On 1s Light On 1s When Power On Light On 1s Blink with 1s Interval Blink with 500ms Interval Description Not Add in Z-Wave Network Sensor Measuring Time Press And Hold Button 10s, Off at 11th Second Add in Z-Wave in Network Already Press And Hold Button 5s, Off at 6th Second Z-Wave Indicator OTA is Running FCC STATEMENT :
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation. Warning: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
receiver is connected. FCC Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body. Reorient or relocate the receiving an Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the Consult the dealer or an experienced radio/TV technician for help. tenna.