SynapSense P3 SmartPlug Power Meter User Guide Aug. 5, 2011 SynapSense P3 SmartPlug Power Meter User Guide
[Page Left Blank]
2 Revision 1.0 Copyright 2010 SynapSense Corporation SynapSense P3 SmartPlug Power Meter User Guide Contents Contents ................................................................................................................................................ 3 Figures ................................................................................................................................................... 4 Warnings and Precautions ................................................................................................................. 9 Introduction ........................................................................................................................................ 10 Overview ......................................................................................................................................... 10 Software Requirements ..................................................................................................................... 11 Power Meter and Electrical Specifications ..................................................................................... 11 P3 SmartPlug Power Meter Measurement Range: ................................................................ 11 P3 SmartPlug Maximum Electrical Ratings: .......................................................................... 11 Controller: ................................................................................................................................... 11 Maintenance and Calibration ................................................................................................... 11 Regulatory Information .................................................................................................................... 12 SmartPlug Radio (Viking Radio): ............................................................................................ 12 Controller Radios (WSN and Viking Radios): ..................................................................... 12 Power Meter: .............................................................................................................................. 12 Environmental Conditions ............................................................................................................... 12 P3 SmartPlug: ............................................................................................................................. 12 Controller: ................................................................................................................................... 12 Controller Power Adapter: ....................................................................................................... 12 Part Number and Model Information ............................................................................................ 13 P3 SmartPlug PowerMeter Part Number Explanation: ....................................................... 13 P3 SmartPlug PowerMeter Model Number Explanation: ................................................... 13 Installation .......................................................................................................................................... 14 Technical Support .............................................................................................................................. 15 Copyright 2010 SynapSense Corporation Revision 1.0 3 SynapSense P3 SmartPlug Power Meter User Guide Figures Figure 1 P3 SmartPlug Power Meter ............................................................................................. 10 Figure 2 P3 SmartPlugs installed in a server cabinet .................................................................. 14 4 Revision 1.0 Copyright 2010 SynapSense Corporation SynapSense P3 SmartPlug Power Meter User Guide SynapSense Corporation 2365 Iron Point Road, #100 Folsom, CA 95630 Tel: (916) 294-0110 Fax: (916) 294-0270 www.SynapSense.com Released 1.0 Status:
Revision:
Release Date: August 5, 2011 Changes From Previous Revision:
Add Part Number Explanation Page (Rev 0.2) Add model number in explanation page (Rev 0.3) Add French language to regulatory (Rev 0.4) Corrected headers and released (Rev 1.0) Copyright 2010 SynapSense Corporation Revision 1.0 5 SynapSense P3 SmartPlug Power Meter User Guide Trademarks SynapSense, the SynapSense logo and SynapSoft are trademarks of SynapSense Corporation. All third-
party brand and product names are the trademarks of their respective owners and are used solely for informational purposes. Copyright This documentation is protected by United States and international copyright and other intellectual and industrial property laws. It is solely owned by SynapSense Corporation and its licensors and is distributed under a restrictive license. This product, or any portion thereof, may not be used, copied, modified, reverse assembled, reverse compiled, reverse engineered, distributed, or redistributed in any form by any means without the prior written authorization of SynapSense Corporation. RESTRICTED RIGHTS: Use, duplication, or disclosure by the U.S. Government is subject to restrictions of FAR 52.227-14(g) (2)(6/87) and FAR 52.227-19(6/87), or DFAR 252.227-7015 (b)(6/95) and DFAR 227.7202-3(a), and any and all similar and successor legislation and regulation. Disclaimer This documentation is provided as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or fitness for a particular purpose. This documentation might include technical inaccuracies or other errors. Corrections and improvements might be incorporated in new versions of the documentation. SynapSense does not assume any liability arising out of the application or use of any products or services and specifically disclaims any and all liability, including without limitation consequential or incidental damages. SynapSense products are not designed for use in life support appliances, devices, or other systems where malfunction can reasonably be expected to result in significant personal injury to the user, or as a critical component in any life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness. SynapSense customers using or selling these products for use in such applications do so at their own risk and agree to fully indemnify and hold SynapSense and its officers, employees, subsidiaries, affiliates, and distributors harmless against all claims, costs, damages, and expenses, and reasonable attorney fees arising out of, directly or indirectly, any claim of personal injury or death associated with such unintended or unauthorized use, even if such claim alleges that SynapSense was negligent regarding the design or manufacture of its products. SynapSense reserves the right to make corrections, modifications, enhancements, improvements, and other changes to its products or services at any time and to discontinue any product or service without notice. Customers should obtain the latest relevant information before placing orders and should verify that such information is current and complete. All products are sold subject to SynapSense Corporation's terms and conditions of sale supplied at the time of order acknowledgment or sale. SynapSense does not warrant or represent that any license, either express or implied, is granted under any SynapSense patent right, copyright, mask work right, or other SynapSense intellectual property right relating to any combination, machine, or process in which SynapSense products or services are used. Information published by SynapSense regarding third-party products or services does not constitute a license from SynapSense to use such products or services or a warranty or endorsement thereof. Use of such information may require a license from a third party under the patents or other intellectual property of the third party, or a license from SynapSense under the patents or other intellectual property of SynapSense. SynapSense Corporation 2006 2010. All Rights Reserved Document Number: 000-0000 rev 1 SynapSense P3 SmartPlug Power Meter User Guide Regulatory Information Notice to Users:
This equipment has been tested and found to comply with the limits for Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, 6 Revision 1.0 Copyright 2010 SynapSense Corporation SynapSense P3 SmartPlug Power Meter User Guide there is no guarantee that interference will not occur in a particular installation. If the equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and the receiver. Plug the equipment into an outlet on a circuit different from that which the receiver is plugged. Consult the dealer or an experienced radio/TC technician for help. This product works using a radio frequency, so use on an airplane may be restricted due to interference. FCC Statement:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. The antenna(s) used for this transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. CE Statement:
This equipment has been tested and found to comply with the limits of the European Council Directive on the approximation of the law of the member states relating to electromagnetic compatibility (89/336/EEC) according to EN 55022 Class B. Industry Canada Equipment Notice:
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. En Franais:
Le prsent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorise aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radiolectrique subi, mme si le brouillage est susceptible d'en compromettre le fonctionnement. The Industry Canada certification identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Document(s). The Department does not guarantee the equipment will operate to the user's satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure, for their own protection, that the electrical ground connectors of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This presentation may be particularly important in rural areas. Caution: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority or electrician, as appropriate. Caution: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority or electrician, as appropriate. Warranty Information Limited One Year Warranty Our company warrants that for one year from the date of purchase, it will replace this product if found to be defective in materials or workmanship. For a prompt, no charge replacement of equivalent product, contact technical support at support@synapsense.com or by phone. Technical Support Center Telephone: +1.916.294.0110 option 2 Email: support@synapsense.com 2365 Iron Point Road, Suite 100 Copyright 2010 SynapSense Corporation Revision 1.0 7 SynapSense P3 SmartPlug Power Meter User Guide Folsom, CA 95682 United States of America This replacement is the company's sole obligation under this warranty. SynapSense Corporation will not be responsible for any incidental or consequential damages or for any loss arising in connection with the use or inability to use this product. Some states/provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty excludes defects or damage due to misuse, abuse, or neglect. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state/province to province. 8 Revision 1.0 Copyright 2010 SynapSense Corporation SynapSense P3 SmartPlug Power Meter User Guide Warnings and Precautions Installation of this equipment must be in accordance with local and national electrical codes. Do not use if damaged. Check for cuts or abrasions in power cords. Copyright 2010 SynapSense Corporation Revision 1.0 9 SynapSense P3 SmartPlug Power Meter User Guide Introduction This document provides instructions for the installation and use of the SynapSense P3 SmartPlug Power Meter in data center server cabinets. P3 SmartPlug Power Meters are a hardware power-monitoring component within the SynapSense Wireless Data Center Monitoring and Energy Management Solution. Overview P3 SmartPlug Power Meter is an inline power meter providing electrical data via a wireless connection. The SmartPlug basically consists of a server power cord with a small SynapSense node mounted in the middle of the power cord. The node housing encloses a power meter and radio. Typically, all of the computer servers within a given server cabinet
(rack) are metered with SmartPlugs. The P3 SmartPlug Controller provides the wireless link between the SmartPlug meters and the SynapSense Wireless Sensor Network (WSN). The Controller aggregates power meter data from the SmartPlugs and reports via the WSN to the host server. The Controller is also capable of collecting server cabinet environmental data (intake and exhaust air temperatures for the server cabinet). The Controller also supports a door contact switch for use in alerting when server cabinet doors are left ajar. Figure 1 P3 SmartPlug Power Meter Revision 1.0 Copyright 2010 SynapSense Corporation 10 SynapSense P3 SmartPlug Power Meter User Guide Software Requirements Requires SynapSoft 6.0 Device Manager software or newer (Device Manager, MapSense, and other software referenced in this document are included with SynapSoft 6.0). Power Meter and Electrical Specifications P3 SmartPlug Power Meter Measurement Range:
100 to 240 VAC RMS, 50/60Hz, Allowable current crest factor 3 0 to 10amps RMS (all models) Overload capacity 115% continuous, six times full load rating (inrush) Power Consumption:
Not to exceed 4VA in current circuit Not to exceed 2W and 10VA elsewhere Accuracy:
Parameter Voltage Current Energy (0.7 to 1.0 PF) Energy (0.5 to 0.7 PF) Accuracy Specification
+/-0.5% Measurement
+/-0.5% Measurement, +/-0.5% Full Scale
+/-1.0% Measurement
+/-1.5% Measurement P3 SmartPlug Maximum Electrical Ratings:
Rated Input Voltage: 100 to 240 VAC RMS, 50/60Hz Rated Maximum Current:
18/3AWG power cord (C13/C14 models): 10amps RMS 14/3AWG power cord (C19/C20 models): 15amps RMS Controller:
Voltage Input:
12 to 27VDC; 2.1x5.5mm center positive barrel jack connector AC Adapter Included with the Controller Kit:
Voltage: 100 to 240VAC (L-L or L-N) Frequency: 50/60Hz Maintenance and Calibration SmartPlugs are factory calibrated and require no field maintenance. Copyright 2010 SynapSense Corporation Revision 1.0 11 SynapSense P3 SmartPlug Power Meter User Guide Regulatory Information SmartPlug Radio (Viking Radio):
FCC Part 15, Subpart C, 15.247 U62-SJA100 Industry Canada 7265A-SRA100 CE Marking EN 300 328; V1.7.1 (2006-05) and EN 300 440-2 V1.1.2 (2004-07) Controller Radios (WSN and Viking Radios):
FCC Part 15, Subpart C, 15.247 U62-SRS100 (WSN Radio) U62-SSC100 (Viking Radio) Industry Canada 7265A-SRS100 (WSN Radio) 7265A-SSC100 (Viking Radio) CE Marking EN 300 328; V1.7.1 (2006-05) and EN 300 440-2 V1.1.2 (2004-07) Power Meter:
UL 61010 Designed to meet IEC 62053 Class 1, ANSI C12.20 Class 1 accuracy requirements Environmental Conditions P3 SmartPlug:
Operating: 0C to +60C, 10-90% relative humidity (non-condensing) Storage: -40C to +70C, 10-90% relative humidity (non-condensing) Controller:
Operating: 0C to +60C, 10-90% relative humidity (non-condensing) Storage: -40C to +70C, 10-90% relative humidity (non-condensing) Controller Power Adapter:
Operating: 0C to +40C*, 10-90% relative humidity (non-condensing) Storage: -40C to +70C, 10-90% relative humidity (non-condensing)
* The lower max operating temperature of the Controller power supply brick is typically overcome by mounting the power supply outside of the server cabinet confines. The power cord for the Controller power supply is 1.8meters (6feet) on both sides of the brick. This long length allows the brick to mounted outside of the cabinet when the AC cord is plugged in to an outlet strip inside the cabinet and still reaching over to the Controller DC jack receptacle. 12 Revision 1.0 Copyright 2010 SynapSense Corporation SynapSense P3 SmartPlug Power Meter User Guide Part Number and Model Information P3 SmartPlug PowerMeter Part Number Explanation:
All P3 SmartPlug Powermeters will have a product label documenting the SynapSense part number. The part number breaks down as follows:
99-0642-xxx-yyy Part numbers starting 99-0642 will come with C13 and C14 plugs Part numbers starting 99-0643 will come with C19 and C20 plugs Where xxx is the length (mm) of the server cord side Where yyy is the length (mm) of the outlet cord side EXAMPLE: Part Number: 99-0642-150-150 C13 Server Side Plug, length 150mm C14 Outlet Side Plug, length 150mm P3 SmartPlug PowerMeter Model Number Explanation:
MODEL 0642:
Part numbers starting 99-0642 come with C13/C14 plugs, 18/3AWG cord, 10amp max MODEL 0643:
Part numbers starting 99-0643 come with C19/C20 plugs, 14/3AWG cord, 15amp max Copyright 2010 SynapSense Corporation Revision 1.0 13 SynapSense P3 SmartPlug Power Meter User Guide Installation The P3 SmartPlug is an inline power cord that replaces the power cord of the equipment to be monitored. The SmartPlug installation process requires the use of the SmartPlug Configuration Software Utility to associate the SmartPlug with the SmartPlug Controller and SynapSoft Web Console. The utility will also collect information about the server configuration and electrical outlet for use in the SynapSoft software. The SmartPlug is associated with the Controller by scanning (or manually entering) the SmartPlug identification number located on the product label. The Controller is connected to a PC (typically laptop) via the USB interface (USB Type A to Micro-B cable required). The Controllers association with the server cabinet (rack) that it is mounted on, along with rack environmentals, is also configured in the host server software (typically SynapSenses MapSense configuration utility). Figure 2 P3 SmartPlugs installed in a server cabinet Revision 1.0 Copyright 2010 SynapSense Corporation 14 SynapSense P3 SmartPlug Power Meter User Guide Technical Support For all technical support issues, contact SynapSense Technical Support:
Tel: (916) 294-0110, option 2 Email: support@SynapSense.com Web: http://www.SynapSense.com Copyright 2010 SynapSense Corporation Revision 1.0 15