WICON WFS-205BW [IIoT WiFi Gateway]
USER MANUAL FCC ID: 2AO6A-WFS-205BW 1 RF Exposure This equipment complies with FCC radiation exposure limits set forth for an uncontrolled envi-ronment. This equipment should be installed and operated with minimum distance 20cm be-tween the radiator and your body. This transmitter must not be co-located or operating in con-junction with any other antenna or transmitter. 2 Contents 1. Summary ................................................................................................................................................................................4 1.1 System summary .....................................................................................................................................................4 1.2. Device specification ..............................................................................................................................................5 1.3 Sensor input specification ...................................................................................................................................5 1.4 Device order number- example ........................................................................................................................5 2. Product outline ....................................................................................................................................................................6 2.1 View ..............................................................................................................................................................................6 2.2 Size (unit : mm) .......................................................................................................................................................6 3. Device detail description .................................................................................................................................................7 3.1 Power port .................................................................................................................................................................7 3.1 LED ................................................................................................................................................................................7 3.3 Reset button .............................................................................................................................................................8 3.4 Sensor connector ....................................................................................................................................................8 4. Sensor wiring example .....................................................................................................................................................9 4.1 Thermocouple sensor wiring (only K-type) .................................................................................................9 4.2 Analog input wiring ( volt, current, resistance ) ........................................................................................9 4.3 Digital input wiring ............................................................................................................................................. 10 5. WICON Setting ................................................................................................................................................................. 12 5.1 Wicon manager download .............................................................................................................................. 12 5.2 Search device ......................................................................................................................................................... 12 5.3 Serial number ........................................................................................................................................................ 13 5.4 Device information .............................................................................................................................................. 13 5.5 View Wim-X ........................................................................................................................................................... 14 3 1. Summary 1.1 System summary
- This product is for Smart Factory. It collects analog and digital signals and sends them to the cloud server. Users can analyze sensor data on cloud servers through WIM-
X(trend, alarm, report.). Thus, the improvement of the production quality can be expected. The device consists of three modules. (Bluetooth module-for setting, WiFi module-for transmission, Sensor connection module-for sensor) The device supports four types of analog input and three types of digital input
(Thermocouple, volt, current, resistance / NPN, PNP, dry contact). Compared to other company devices, it is compact and easy to install (Settings can be made using a smartphone). The magnet mounted cradle will make installation comfortable. This is a good choice when you need to install a small number of sensors. 4 1.2. Device specification Specification Input Voltage Power Consumption Operation temperature Processor Clock RAM ROM Bluetooth WiFi Security WiFi Max Throughput WiFi RX Sensitivity value USB power supply DC 5V / 1A 10W Under
-30~ 75 ARM Cortex-M3 / M4 48Mhz / 80Mhz 28kByte / 256kByte 128Kbyte / 4Mbyte BLE only 4.0 802.11 b/g/n (20Mhz only) WPA 13Mbps 95.7 dBm / 74.0 dBm Remark Except Sensor BLE / Wifi BLE / Wifi BLE / Wifi BLE / Wifi Application level 1 DSSS / 54 OFDM Antenna gain Chip antenna 1.9dBi 1.3 Sensor input specification Input Type Thermocouple K-type Volt Analog Measurement Range 0~1000 0~10 V Current 0~20 mA Resistance 50~10k Digital DC 12~24V Unused Remark
+-2 Accuracy Range 0~250
(within Reference Junction 25~100) 16it Resolution 16it Resolution Not support 3-wire RTD, But if you want to use it, short the calibration line and use it. 3kv isolation NPN, PNP, Dry contact Order Number K V C O D X 1.4 Device order number- example
- You should check the order number when ordering the product.
> WFS-205DS-KKKK -> thermocouple (total 4ch)
> WFS-205DS-VXXX -> analog volt input (total 1ch)
> WFS-205DS-VCDX -> analog volt,currnet input, digital input (total 3ch) 5 2. Product outline 2.1 View
- To protect the product, you must use the cradle when using the product. Power connector
(USB Micro 5pin) Sensor wiring connector
(Plug type) 2.2 Size (unit : mm) 50 77.2 6 WFS-205BW(BLE) for setting WFS-205BW(WiFi) for communication WFS-205DS
(Sensor Connectino Module) Cradle that can be attached to metal 121. 2 3. Device detail description 3.1 Power port
- Connect the 5V 1A power supply with the enclosed cable. 3.1 LED
- Display device status Blinking BLUE when sampling Light on RED when power on See table below Blinking BLUE when communicating Table 1 WFS-205BW(WiFi) RED LED status LED status Device status Remark Fast blink Light on Slow Blink AP connection attempt 250msec AP connection completed AP connection Fail 1sec 10sec Very Slow Blink Server connection Fail
- LED status afer power on (Normal setting status) WFS-205BW (BLE, WiFi) RED LED on WFS-205BW (WiFi) RED LED fast blink ( 250msec ) WFS-205BW (WiFi) RED LED light on WFS-205BW (WiFi) BLUE ELD blink ( every 1sec ) 7 3.3 Reset button
- Reset or initialization.( Each click should be within 0.5 seconds.)
> 1 click is device reset.
> 2 click is device hibernation.
> 3 click is device device initialization. 3.4 Sensor connector
- No.1 and No.2 are default. But There are differences between sensor types. NO TH-K 1 2 3 4 5 6 Thermocouple +
Thermocouple -
GND Reserved
+24V
+5V Table 2 Connector pin map AI-V Volt (0~10V) GND GND AI-C AI-O DI-D Current (0~20mA) Register +
DC + (12~24V) GND GND GND GND DC -
GND Reserved Reserved Reserved Reserved
+24V
+5V
+24V
+5V
+24V
+5V
+24V
+5V 8 4. Sensor wiring example 4.1 Thermocouple sensor wiring (only K-type)
- Default port number is 1,2 (No.1 + No.2 )
- If not connected, the temperature is 1000
- You wind the sensor cable 2~3 times to the ferrite core for data reliability and electromagnetic shielding. Figure 1 Thermocouple wiring 4.2 Analog input wiring ( volt, current, resistance )
- Default port number is 1,2
- Power supply No.3(GND), No.5(+24V), No.6(+5V)
- You wind the sensor cable 2~3 times to the ferrite core for data reliability and electromagnetic shielding.
> Example. Voltage output Sensor ( MM2001 Humidity Red:+5V, Black:GND, Yellow:Signal ) Figure 2 Voltage output sensor Example 9
> Example. Current output Sensor ( Calex PC151HT Red:+24V, Black:Signal ) Figure 3 Current output sensor example
> Example. Resistance output Sensor ( PT100 ), Not support 3-wire RTD, but if you want to use it, short the calibration line and use it. Figure 4 Resistance output sensor 4.3 Digital input wiring
- Depends on type (NPN, PNP)
- You wind the sensor cable 2~3 times to the ferrite core for data reliability and electromagnetic shielding.
> Example. NPN Proximity sensor (Brown : +24, Blue : GND, Black : Signal) Figure 5 NPN-sensor, Need for wiring(1-5) 10
> Example. PNP Proximity sensor (Brown : +24, Blue : GND, Black : Signal) Figure 6 PNP-sensor, Need for wiring(2-3)
> Example. Dry contact (General purpose relay contact) Realy Power Figure 7 General purpose relay, Need for wiring(2-3) 11 5. WICON Setting 5.1 Wicon manager download Connect to www.wim-x.com by smartphone and download wicon manager
(Membership required)
#Note: Wi-Fi data transfer (cloud server transfer) is not performed when wicon is in configuration mode during operation.5.1 Wicon manager download. 5.2 Search device Connect the power of the product, run Wicon manager and select WF-000000. If you can not find WF-000000, press the search button. 12 5.3 Serial number Enter the serial number directly or enter it as a barcode scan. If the serial number is entered correctly, proceed to the next step. 5.4 Device information If the smartphone and the BLE module are connected, the following screen will be displayed. Led of WiFi module alternately blinks blue and red. Enter the SSID, password, and sensor type, and then click B. In normal cases, the LED will flash quickly and then reset. If the reset does not work or the screen seems to be frozen, start from 5.2 again. (Connection Fail- >
Attempt to reconnect) 13 5.5 View Wim-X Access www.wim-x.com to register categories and devices. Then set up the dashboard. Check the WIM-X manual for details. 14