Installation and Setup Guide 5800SMOKEV Wireless Smoke/Heat Detector GENERAL INFORMATION This is a multi-criteria wireless smoke detector which employs advanced levels of detection and discrimination. This reduces common cooking nuisance alarms and allows faster detection to different types of fire conditions. It is intended for use with Control Panels that support 5800 series devices. To remove the mounting bracket, turn the top of the detector 15 degrees counterclockwise and separate the mounting bracket and top cover. 5800SMOKEV Open ENROLLMENT The smoke detector must be enrolled in the Control Panel before it can operate in the system. The 5800SMOKEV smoke/heat protection zone must be enrolled as Loop 1 and Input Type 3
(supervised RF). If programmed, this smoke detector is capable of monitoring the additional conditions of Maintenance (transmitted as Loop 2), and Low Temperature (transmitted as Loop 3). Tamper is transmitted as Loop 4, but does not require programming. To take advantage of the value added features of Maintenance and Low Temperature, you must program each loop as a separate zone in the 5800 series wireless compatible panel. 1. Enter the Controls Zone Programming mode. 2. Enter the zone number to be programmed. 3. Enter the applicable zone type when prompted. Program Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16), Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 19), and Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8). NOTE: Loop 2 High/Low Maintenance is supported only on commercial control panels such as the Vista-128FBP. 4. When prompted, enter Input Type 03 (3 on some control panels) Supervised RF Transmitter. 5. When prompted for the serial number, transmit from the detector by activating the tamper switch. To do this, hold the base of the detector in one hand, and rotate the detector counterclockwise on the base until it snaps open. Then return to clockwise position until the detector snaps into place. 6. When the serial number is displayed, transmit from the detector a second time by activating the tamper switch again as described in Step 5. The current loop number
(4) will begin to flash. 7. Manually change the loop number to the desired loop number for the zone (according to the application). 8. When programming for this zone is complete, program other zones for the transmitter as necessary (except for Tamper Loop 4, which does not require programming). WARNING: The fire protection zone enrolled must always be Loop 1. Otherwise, fire annunciations will not be reported by the Control Panel. 9. Exit Programming mode when programming is complete and test the detector. Refer to the Testing Section. See the Control Panels installation instructions for further details. PROGRAM Consult the Control Panels instructions to program the device in the system. This detector reports the following signals to the Control Panel:
Smoke and Heat detection
- Smoke Alarm when smoke is detected
- Heat Alarm when temperature of 135 F (57 C) or greater
- Rate-of-Rise Alarm when temperature is >104 F (40 C) @ 15 F/minute (8.33 C/minute). Maintenance: Contaminated chamber that requires cleaning End-of-Life Base Tamper: It sends a tamper signal to the Control Panel when the smoke head is removed from its base. Supervision: The detector will transmit its status every 60-70 minutes. TAMPER When the detector is removed from its base, it sends a tamper signal to the Control Panel. OPTIONAL: The detector can be made tamper-proof to prevent unauthorized removal from its base. Break off the small pillar on the base as shown. This causes the detector to latch to the base. From this point on, to remove the detector from its base, you must use a small screwdriver to release the catch
(push the catch towards the base) and twist the detector counterclockwise. A screw can be added to prevent removal from the base. MOUNT Refer to the Limitations of Fire Alarm Systems (P/N 800-15144) for detailed information on detector spacing, placement zoning and special applications. Copies of this document are available on www.resideo.com. NOTE: Before mounting the detector permanently, conduct a Walk test (see Control Panels instructions) to verify adequate signal strength and adjust the device location and orientation as necessary. The detector can be mounted on the ceiling or on the wall (if local ordinances permit). Select a location and mount using the included mounting hardware. DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown on the accompanying figure. 0 V
2 0 0
N O M M O C _ V E K O M S Mount TESTING The detector should be tested immediately after installation and at least once a year. Recommended: Notify the Central Station that the smoke detector is undergoing tests, so they do not dispatch authorities. After enrolling, verify adequate signal strength by conducting a sensor test (see the Control Panels instructions) with the device in its intended mounting location. Adjust the device location and orientation as necessary. Tests and testing methods There is no specific Test Mode that needs to be initiated to test smoke, heat, or Rate-of-Rise. These can be applied to the detector at any time as a test. Test Button When the Test Button is held down, the unit initiates a test on the smoke sensor, chamber, heat sensor, End-of-
Life, and battery. If all tests pass, it sounds a normal alarm and sends alarm signal to the Control Panel. However, if one of these tests fails, it sends a trouble signal to the Control Panel and provides fail status on the yellow led and sounder. The Test Button is also used to silence or Hush the detector. To Hush the detector, press and release the large Test Button. Depending on how much smoke is still in the chamber determines if the Hush feature silences the detector and make it send an Alarm restore to the Control Panel. If there is too much smoke still in the chamber, it does not Hush nor send a restore to the Control Panel. When Hush is successful, the sounder comes back on after 10 minutes and a restore signal is still not sent provided there is still enough smoke in the chamber to be considered an alarm. Once the smoke level is below threshold in the chamber, Hush causes the sounder to remain off and the restore signal is sent. See the LED and Sounder Indication Chart on the next page. Smoke Entry Test (canned smoke*) Can be done at any time. Once the chamber is clear, the sounder will stop, and it will send a restore signal to the Control Panel. Direct Heat Test (hair dryer 12 or further from the detector) Rate-of-Rise >104 F (40 C) @ 15 F/minute (8.33 C/minute). 135 F fixed Heat Detection CAUTION: The detector alarms when 135 F is exceeded and restore when it falls below 135 F. However, the thermistor is damaged at 195 F and the integrity of the detector itself is compromised and needs to be replaced. LEDS AND SOUNDER The 5800SMOKEV has one bi-color (red and yellow) LED with an 85dB sounder. Refer to the following table below for operation of these features. LED and Sounder Indication Chart Normal Operation Power Up Tamper Standby - Normal Sensing Smoke / Heat Alarm Hush Silence Sounding Alarm Silence Low Battery Silence Faulty Sensor
(only possible once) Silence End of Life (up to 30 days) Self-Diagnostics Low Battery Faulty Smoke Sensor Faulty Heat Sensor End of Life Maintenance Test Button Detector Status Good Normal Alarm Low Battery Faulty Sensor End of Life Maintenance Alarm Memory Action Pull Battery Tab Red LED 1 Flash Yellow LED 1 Flash Sounder Off Reaction Remove from base Off Smoke / Fire Condition Action Press & Release Button Press & Release Button Press & Release Button Press & Release Button Action Automatic every 16 minutes Automatic every 16 seconds Automatic every second Automatic every 4 hours Automatic every 16 seconds Action Press & Hold Button Press & Hold Button Press & Hold Button Press & Hold Button Press & Hold Button Action Off Rapid flashing Red LED 1 flash every 8 seconds Off Off Off Red LED Off Off Off Off Off Red LED Rapid flashing Off Off Off Off Red LED 2 flashes every 48 seconds for 24 hours Off Off Off Off Off Temporal 3 Evacuate Premises Yellow LED Sounder Reaction Off Off for 10 mins Off for 12 hours Off for 12 hours Replace both batteries 2 flashes every 48 seconds Off for 12 hours Replace unit Off for 72 hours Off for 72 hours Replace unit Yellow LED 1 flash every 48 seconds 2 flashes every 48 seconds 2 flashes every 48 seconds 3 flashes every 48 seconds Sounder 1 beep with 1 flash 2 beeps with 2 flashes 2 beeps with 2 flashes 3 beeps with 3 flashes Reaction Replace both batteries Replace unit Replace unit Replace unit 4 flashes every 48 seconds Off Yellow LED Sounder Clean unit; see Cleaning section Reaction Off Temporal 3 Release button 1 flash then rapid flashing 2 flashes then rapid flashing 3 flashes then rapid flashing 4 flashes then rapid flashing Yellow LED Off Off 1 beep then Temporal 3 Replace both batteries 2 beeps only Replace unit 3 beeps then Temporal 3 4 beeps then Temporal 3 Sounder Off Rapid chirping Replace unit Clean unit; see Cleaning section Reaction Press & Hold Button for Long Term Memory Memory is reset after releasing the test button 24 Hour Memory After Alarm Long Term Memory Press & Hold Button Rapid flashing CLEANING Recommended: To prevent unwanted alarms, notify the Central Station that the smoke detector system is undergoing maintenance before cleaning the detector. To clean the detector, carefully vacuum the side vents all the way around, then, wipe them with a clean damp cloth and dry thoroughly. Do NOT attempt to take the detector apart. This could result in damaging the unit. Cleaning BATTERY REPLACEMENT 1. Twist the front cover counterclockwise 15 degrees and separate it from the mounting bracket. 2. Remove both batteries and wait 10 seconds, then insert two new recommended batteries:
Panasonic CR123A 0 V
1 0 0
N O M M O C _ V E K O M S NOTE: Do not mix old and new batteries, battery types or manufacturers. 3. Reattach the detector to the mounting plate. BATTERY CAUTION: Risk of fire, explosion and burns. Do not recharge, disassemble, heat above 212 F (100 C) or incinerate. Dispose of used batteries properly. Keep away from children 5800SMOKEV Series transmitters draw quick bursts of current during transmission, then sit idle with very nominal current draw. Most batteries are not designed for this type of use, therefore, only batteries listed as compatible should be used if the expected battery life is to be attained. Each transmitters Installation Instructions has listed compatible battery manufacturers and their part numbers. When other non-approved batteries are used, the quick bursts of current draw kill the battery cells prematurely causing them to go low in a matter of months and can also cause unpredictable results. Other low-quality batteries have not been UL tested and pose a safety hazard if used. Replace Batteries SPECIFICATIONS Smoke Detection: .................................................................................................................................................................................. Photoelectric Heat Detection: ....................................................................................................................................................... 135 F (57 C) or greater +/- 5F Rate of Rise: ................................................................................................................................ >104 F (40 C) @ 15 F/minute (8.33 C/minute). dB Rating: ........................................................................................................................................................................... >85dBA (Minimum) at 9ft Batteries: ......................................................................................................................................................... Two 3V Lithium; Panasonic CR123A RF Frequency: .............................................................................................................................................................................................. 345MHz Tamper: ................................................................................................................................................................................................. Base Tamper Operating Temperature: ............................................................................................................................................. 40 to 100 F / 4.4 to 37.7 C Relative Humidity: ............................................................................................................................................................ 95% max. non-condensing Maximum Spacing:
............................................... 50ft x 50ft (refer to National Fire Alarm Code Standard NFPA 72 for application requirements) Dimensions: ................................................................................................. 4.74 in. Diameter x 2.31 in. Thick / 12.03 cm Diameter x 5.81 cm Thick Approval Listings FCC / IC UL Listed Conforms to UL 268 7th Edition Commercial and Residential Installations ULC Listed Certified to UL268 & CAN/ULC S529 Other Standards: State of California requirement free of substances that may cause cancer. Prop 65 US. NFPA 72 Note: Smoke detectors are not to be used with detector guards unless the combination is evaluated and found suitable for that purpose. REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED, FOR DETAILS REGARDING LIMITATIONS OF THE ENTIRE ALARM SYSTEM. FEDERAL COMMUNICATIONS COMMISSION (FCC) & ISED STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. FCC CLASS B DIGITAL DEVICE STATEMENT This equipment has been tested and found to comply with the limits for a Class B digital device, as defined by FCC Rules Part 15.105. The Class B Digital Device statement can be viewed at:
https://customer.resideo.com/en-US/support/residential/codes-and-standards/FCC15105/Pages/default.aspx ISED CLASS B STATEMENT This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numrique de la classe B est conforme la norme NMB-003 du Canada. FCC / ISED STATEMENT This device complies with Part 15 of the FCC Rules, and Industry Canadas license-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Cet appareil est conforme la partie 15 des rgles de la FCC et exempt de licence RSS dIndustrie Canada. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer dinterfrences nuisibles. (2) Cet appareil doit accepter toute interfrence reue y compris les interfrences causant une rception indsirable. Responsible Party / Issuer of Suppliers Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate Center Drive., Melville, NY 11747, Ph: 516-577-2000 The product should not be disposed of with other household waste. Check for the nearest authorized collection centers or authorized recyclers. The correct disposal of end-of-life equipment will help prevent potential negative consequences for the environment and human health. Any attempt to reverse-engineer this device by decoding proprietary protocols, de-compiling firmware, or any similar actions is strictly prohibited. For the latest documentation, support, and warranty information, please go to: www.resideo.com This product is manufactured by Resideo Technologies, Inc. and its affiliates. 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 2021 Resideo Technologies, Inc. www.resideo.com R800-26635A 2/21 Rev A