FCC ID: P27F3D100 F3D100 All-in-one Access Control Device Installation Prerequisite Installation to be performed only by certied installer!
Power Sourcing Requirement: PoE+ (802.3at Type 2) 30W!
Unit to be powered by UL294B certied IEEE PoE+ 802.3at Type 2 Power Sourcing Equipment using unshielded cat5e or better cable with a maximum cable length of 330 feet (100 meters)!
A ULC 60839-11-1 Listed power supply with appropriate grade is required to be provided for ULC installations!
Wiegand/OSDP Badge Reader max cable length: 5 ft - 22 AWG (1.5 m)!
Wiegand Panel max cable length: 500 ft - 22 AWG (152 m), 300 ft - 24 AWG (91 m) OSDP Panel max cable length: 4000 ft - 24 AWG (1,219 m), Connect Directly to an Electric Lock Fail Safe Lock There is normally a current owing through the relay on the Fail Safe lock. When the relay is activated, the current own is blocked, and the door lock will open. If the power supply is cut o"
due to a power failure or an external factor, the door will remain open. NC -Burgundy/Yellow COM - Brown/Red F3D100 Pigtail Connect the two NC wires together to the + wire on the lock. !
Connect the two COM (Brown/Red) wires to the
+ wire on the power source.!
Connect the - negative wire from the power source to the - negative on the lock.!
Each wire supports up to 1A, connecting together will allow for up to 2A current to ow.
Fail Secure Lock There is no current owing through the relay on the Fail Secure lock. When the relay is activated, the current ow is opened, and the door lock will open. If the power supply is cut o" due to a power failure or an external factor, the door will remain closed. NO - Orange/Red COM - Brown/Red F3D100 Pigtail Connect the two NO wires together to the + wire on the lock. !
Connect the two COM (Brown/Red) wires to the
+ on the power source.!
Connect the - wire from the power source to the
- on the lock.!
Each wire supports up to 1A, connecting together will allow for up to 2A current to ow.
Connect Power over Ethernet Cable (PoE) The F3D100 uses 802.3at (PoE+).!
Connect a Cat5/6 ethernet cable to the RJ45 located on the pigtail of the F3D100.!
To setup network connection use the Alocity setup app.!
Wiegand Input/Output Wiring Diagram Wiegand Output Wiegand 0 Green / Black Output Wiegand 1 Orange / Balck Input Wiegand 0 Burgundy / Blue Input Wiegand 1 Brown / White Ground Black OSDP Wiring Diagram OSDP / RS485 RS485 A RS485B Ground Orange /White Green / White Black Input for Exit button & Door Contact Sensor Wiring Diagram Inputs Input 1 Input 2 Ground Green / Yellow White Brown / Yellow Max number of face/templates enrolled shall not exceed 10,000!
Ethernet/PoE+ and Wiegand Cable to Reader and Panel are Class II/Power Limited !
Equipment not intended for connection to telephone, or outside wiring as covered by Article 800 in the National Electrical Code, NFPA 70!
FCC This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.!
CAUTION: Any changes or modications to this device not explicitly approved by the manufacturer could void your authority to operate this equipment.!
ATTENTION: Tout changement ou toute modication apports cet appareil sans lapprobation expresse du fabricant risque dinvalider lautorisation relative son utilisation.!
CE Marking Alcatraz AI hereby declares that these facial authentication devices are in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.